2018-14075 I (Plans)OLIVENHAIN MUNICIPAL WATER DISTRICT NOTES 1.POTABLE WATER WORKS SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE DETAILS AND MATERIALS AS SPECIFIED IN THE MOST RECENT EDITION OF THE OLIVENHAW MUNICIPAL WATER DISTRICT (DISTRICT) STANDARD SPECIFICATIONS AND DRAWINGS FOR THE CONSTRUCTION OF WATER MAINS AND FACILITIES, INCLUDING ALL AMENDMENTS ADOPTED PRIOR TO THE DISTRICT APPROVAL DATE ON THESE PLANS. CONTRACTOR SHALL HAVEA COPY OF THE STANDARD SPECIFICATIONS ON THE JOB SITEATALL TIMES. 2.7HE SUBMISSION AND REVIEW OF ALL SUBMITTALS (SHOP DRAWINGS SIX SETS) AS REQUIRED BY THE STANDARD SPECIFICATIONSARE TO BEACCOMPLISHED PRIOR TO THE PRE - CONSTRUCTION MEETING WITH THE DISTRICTS INSPECTOR. 3.UNLESS OTHERWISE NOTED, CONNECTIONS TO EXISTING MAINS SHALL BE MADE DRY. THE TIME AND DURATION OF ANY SHUTDOWNS OF EXISTING MAWS SHALL BE SUBJECT TO APPROVAL BY THE DISTRICT. DISTRICT SHALL BE NOTIFIED TWO WEEKS MINIMUM INADVANCE OFANYSHUTDOWN. 4. CONTRACTOR SHALL COORDINATE WITH DISTRICT ALL ARRANGEMENTS FOR HIGH - LINING TEMPORARY SERVICES PRIOR TO SHUTDOWNS. NO SHUTDOWNS WILL BE SCHEDULED DNA MONDAYOR FRIDAY. 5. CONTRACTOR SHALL REVIEW ALL PROPOSED TRENCH WORK WITH CAL/OSHA. A COPY OF EXEMPTION LETTER OR TRENCHING PERMIT, IF REQUIRED, SHALL BE SUBMITTED TO THE DISTRICT PRIOR TO CONSTRUCTION. 6.NO WORK MAY BEGIN OR PROCEED WITHOUT DIRECTION OF DISTRICTS INSPECTOR. CONTRACTOR SHALL NOTIFY THE DISTRICT INSPECTIONS DEPARTMENT 48 HOURS PRIOR TO THE BEGINNING OF WORK TOARRANGE FOR INSPECTION OF THE PROJECT. 7THE CONTRACTOR MUST CALL 'DIG ALERT OF SOUTHERN CALIFORNIA" TO HAVE UNDERGROUND SERVICE UTILITIES LOCATED PRIOR TO CONSTRUCTION. THIS CALL WILL BE MADE AT LEAST 48 HOURS IN ADVANCE PRIOR TO ANY WORK BEING PERFORMED IN PUBLIC RIGHT -OF -WAY. (DIGALERT PHONE: 800- 227 -2600) 8.ALL EXISTING FACILITIES WHICH MAYAFFECT PROJECT CONSTRUCTION, I.E., LINE CROSSINGS, LINE PARALLELING, OR PROPOSED CONNECTIONS SHALL BE FIELD VERIFIED BEFOREANY CONSTRUCTION BEGINS. 9. THE CONTRACTOR SHALL FURNISH AND INSTALL PER THE STANDARD SPECIFICATIONS THE APPROPRIATE BURIED UTILITY WARNING AND IDENTIFICATION TAPE ABOVE ALL PUBLIC WATER LINES INCLUDING WATER LATERALS LOCATED IN PUBLIC RIGHT -OF -WAY. 10. WHERE ELEVATIONS AND GRADES ARE NOT SHOWN ON THE WATER MAIN PROFILE, TOP OF PIPE PROFILE IS 48- INCHES BELOW CENTERLINE OF FINISH GRADE OF STREET. 11. ALL DEFLECTIONS (HORIZONTAL AND VERTICAL) SHALL BE MADE BY USE OF JOINT COUPLINGS WITH 4 MAXIMUM DEFLECTION PER COUPLING (2° PER JOINT). NO BENDING (CURVING) OF PIPE SHALL BE PERMITTED. 12. MANUALAIR RELEASES SHALL BE INSTALLEDATALL HIGH POINTSAND BLOW - OFFSATALL LOW POINTS IN THE WATER MAIN PROFILE PLACE MANUALAIR RELEASES AND BLOW -OFFS WITHIN METER BOXAND LOCATE BEHIND CURB UNLESS OTHERWISE APPROVED BYDISTRICTS REPRESENTATIVE. FIRE HYDRANTS MAYBE USED IN LIEU OFA MANUALAIR RELEASE OR BLOW -OFF WHEN LOCATEDAT OR NEAR HIGH OR LOW POINTS, ASAPPROVED BY THE DISTRICTS REPRESENTATIVE 13. INSTALL A MINIMUM 1 -INCH WATER SERVICE TO EACH LOT. METER TO BE LOCATED 5 -FEET FROM A SIDE LOT LINE A 314 -INCH HIGH LETTER '1N" SHALL BE CHISELED IN TOP OF EXISTING CURB OR IMPRINTED IN NEW CURBATALL WATER SERVICE CROSSINGS. 14. METER BOXES SHALL NOT BE PLACED WITHIN DRIVEWAYS OR SIDEWALKS WITHOUT THE DISTRICT'S PRIOR WRITTEN CONSENT. 15.ALL WATER SERVICES FOR IRRIGATION ULTIPLE RESIDENTIAL ESIDENTIAL COMPLEXES COMMERCWL OR INDUSTRIAL DEVELOPMENT H S ALL HAVEAPPROVED BACKFLOW PREVENTION DEVICE ON CUSTOMER'S SIDE OF WATER METER. 16.CONTR4CTOR SHALL TIE OFF ALL VALVE LOCATIONS AND PROVIDE WRITTEN DIMENSIONS TO INSPECTOR IMMEDIATELY UPON INSTALLATION OF VALVES. 17 LINE VALVES, WHERE REQUIREDAT STREET INTERSECTIONS SHALL BE LOCATEDAT THE TEE WHENEVER POSSIBLE. 18. FIRE HYDRANTS, AS APPROVED BY THE APPROPRIATE FIRE DISTRICTAND MEETING THE DISTRICT'S STANDARD SPECIFICATIONS, ARE TO BE INSTALLEDAT LOCATIONS SPECIFIED BY THE FIRE DISTRICT. 19.ALL DESIGN CHANGES TO THE WATER SYSTEM SHALL BE APPROVED BY THE DISTRICT REPRESENTATIVE IN WRITING PRIOR TO CONSTRUCTIONANDACCEPTANCE OF THE CHANGE. 20. THE WATER SYSTEM SHALL BE PRESSURE TESTED IN ACCORDANCE T WI H THE PROCEDURES IN THE OMWD STANDARD SPECIFICATIONS. THE CLASS OF PIPE SHALL BE USED AS THE DESIGNATED WORKING PRESSURE FOR TESTING ALL PIPE, VALVES (CLOSED) ANDAPPURTENANCES 21.PIPELINES AND APPURTENANCES SHALL BE DISINFECTED IN ACCORDANCE WITH SECTION 15041 OF THE OMWD STANDARD SPECIFICATIONS PRIOR TO TIE -IN OR CONNECTION TO EXISTING SYSTEM FACILITIES, BACTERIOLOGIC QUALITY TEST RESULTS SHALL CONFORM TO THE CRITERIA SPECIFIED IN THAT SPECIFICATION, 22. CONTRACT RECORD DRAWINGS MUST BE SUBMITTED PRIOR TO FINAL ACCEPTANCE OF WORK THE PLANS MUST PROVIDE POST CONSTRUCTION VERIFICATION OF THE LOCATIONAND ELEVATION OF PIPES ANDAPPURTENANCES. 23. CONTRACTOR SHALL GUARANTEE ALL WORK FOR A PERIOD OF ONE (1) YEAR AFTER THE DATE OF ACCEPTANCE FOR THE PROJECT. CONTRACTOR SHALL REPAIR OR REPLACE ANY OR ALL SUCH WORK, TOGETHER WITH ANY OTHER WORK WHICH MAY BE DISPLACED IN SO DOING THAT MAY PROVE DEFECTIVE IN WORKMANSHIP AND /OR MATERIALS WITHIN THE ONE -YEAR PERIOD FROM THE DATE OF ACCEPTANCE WITHOUT EXPENSE WHAT SO EVER TO THE DISTRICT ORDINARY WEAR AND TEAR, UNUSUAL ABUSE OR NEGLECTEXCEPTED. 24.ALL IRRIGATION METERS SHALL BE SERVED WITH RECYCLED WATER UNLESS PREVIOUSLY APPROVED IN WRITING BY THE DISTRICT 25. ALL BURIED FITTINGSAND VALVES SHALL BE WAX TAPE WRAPPED W ACCORDANCE WITH OMWD STANDARD SPECIFICATIONS PCC SIDEWALK PL / PER SDRSD G -7 GENERAL RECYCLED WATER SYSTEM NOTES 1. THE RECYCLED WATER SYSTEM SHALL CONFORM TO THE RULES AND REGULATIONS FOR RECLAIMED AND NON - POTABLE WATER SERVICE OF THE OLIVENHAIN MUNICIPAL WATER DISTRICT, ORDINANCE NO. 175, DATED MARCH 1989, AND ALL SUBSEQUENT AMENDMENTS. 2. RECYCLED WATER WORKS SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE DETAILS AND MATERIALS AS SPECIFIED IN THE MOST RECENT EDITION OF THE OLIVENHAIN MUNICIPAL WATER DISTRICT (DISTRICT) STANDARD SPECIFICATIONS FOR THE CONSTRUCTION OF WATER MAINS AND FACILITIES, INCLUDING ALL AMENDMENTS ADOPTED PRIOR TO THE DISTRICT APPROVAL DATE ON THESE PLANS. CONTRACTOR SHALL HAVEA COPY OF THE OMWD STANDARD SPECIFICATIONS ON THE JOB SITEATALL TIMES. 3. THE SUBMISSION AND REVIEW OF ALL SUBMITTALS (SHOP DRAWINGS, SIX SETS) AS REQUIRED BY THE OMWD STANDARD SPEC/FICATIONSARE TO BEACCOMPLISHED PRIOR TO THE PRE - CONSTRUCTION MEETING WITH THE DISTRICTS INSPECTOR. 4.UNLESS OTHERWISE NOTED, CONNECTIONS TO EXISTING MAINS SHALL BE MADE DRY. THE TIME AND DURATION OF ANY SHUTDOWNS OF EXISTING MAINS SHALL BE SUBJECT TO APPROVAL BY THE DISTRICT.' DISTRICT SHALL BE NOTIFIED TWO WEEKS MINIMUM W ADVANCE OFANY SHUTDOWN. SCONTRACTOR SHALL COORDINATE WITH DISTRICT ALL ARRANGEMENTS FOR HIGH - LINING TEMPORARY SERVICES PRIOR TO SHUTDOWNS. NO SHUTDOWNS WILL BE SCHEDULED DNA MONDAY OR FRIDAY. 6. CONTRACTOR SHALL REVIEW ALL PROPOSED TRENCH WORK WITH CAIOSHA. A COPY OF EXEMPTION LETTER OR TRENCHING PERMIT, IF REQUIRED, SHALL BE SUBMITTED TO THE DISTRICT PRIOR TO CONSTRUCTION! 7 N WORK MAY BEGIN OR PROCEED WITHOUT DIRECTION OF DISTRICTS INSPECTOR, CONTRACTOR SHALL NOTIFY THE DISTRICT INSPECTIONS DEPARTMENT 48 HOURS PRIOR TO THE BEGINNING OF WORK TOARRANGE FOR INSPECTION OF THE PROJECT. 8.7HE CONTRACTOR MUST CALL 'DIG ALERT OF SOUTHERN CALIFORNIA" TO HAVE UNDERGROUND SERVICE UTILITIES LOCATED PRIOR TO CONSTRUCTION. THIS CALL WILL BE MADE AT LEAST 48 HOURS IN ADVANCE PRIOR TO ANY WORK BEING PERFORMED IN PUBLIC RIGHT -OF -AMY. 9.ALL EXISTING FACILITIES WHICH MAY AFFECT FINAL CONSTRUCTION, LE, LINE CROSSINGS, LINE PARALLELING, OR PROPOSED CONNECTIONS SHALL BE FIELD VERIFIED. 10. THE CONTRACTOR SHALL FURNISHAND INSTALL PER THE OMWD STANDARD SPECIFICATIONS THE APPROPRIATE BURIED UTILITY WARNING AND IDENTIFICATION TAPE ABOVE ALL PUBLIC RECYCLED WATER LINES INCLUDING RECYCLED WATER LATERALS LOCATED IN PUBLIC RIGHT -OF -WAY. 11. RECYCLED WATER MAIN SHALL BE PURPLE PVC PIPE AWWA C 900, WITH TWO CONTINUOUS METALLIC TAPE STRIPS, STAMPED "RECYCLED WATER. " STRIPS SHALL BE SETAT TOP OF PIPEANDAT 24 "ABOVE THE PIPE. 12. WHERE ELEVATIONS AND GRADES ARE NOT SHOWN ON THE WATER MAIN PROFILE, TOP OF PIPE PROFILE IS 66- INCHES BELOW CENTERLINE OF FINISH GRADE OF STREET. 13. ALL DEFLECTIONS (HORIZONTALAND VERTICAL) SHALL BE MADE BY USE OF JOINT COUPLINGS WITH 4° MAXIMUM DEFLECTION PER COUPLING (2° PER JOINT). NO BENDING (CURVING) OF PIPE SHALL BE PERMITTED. 14.M4NUAL AIR RELEASES SHALL BE INSTALLED AT ALL HIGH POINTS AND BLOW -OFFS AT ALL LOW POINTS IN THE WATER MAIN PROFILE. MANUAL AIR RELEASES AND BLOW-OFFS SHALL BE LOCATED BEHIND CURB UNLESS OTHERWISE APPROVED BY DISTRICT'S REPRESENTATIVE. 15 INSTALL RECYCLED WATER SERVICE(S) IN ACCORDANCE WITH SIZE(S) DEFINED ON THE DRAWINGS, LOCATIONS OF RECYCLED WATER METERS ARE SUBJECT TO APPROVAL BY DISTRICTS INSPECTOR. 314 -INCH HIGH LETTERS 'RW' SHALL BE CHISELED IN TOP OF EXISTING CURB OR IMPRINTED IN NEW CURBATALL RECYCLED WATER SERVICE CROSSINGS. 16. METER BOXES SHALL NOT BE PLACED WITHIN DRIVEWAYS OR SIDEWALKS WITHOUT THE DISTRICT'S PRIOR WRITTEN CONSENT. 17 CONTRACTOR TO TIE OFF ALL VALVE LOCATIONS AND PROVIDE WRITTEN DIMENSIONS TO INSPECTOR IMMEDIATELY UPON INSTALLATION OF VALVES. 18. LINE VALVES, WHERE RE UIREDATSTREE S Q T INTERSECTIONS SEC ION SHALL BE LOCATEDAT THE TEE WHENEVER POSSIBLE. 19.ALL DESIGN CHANGES TO THE RECYCLED WATER SYSTEM SHALL BE APPROVED BY THE DISTRICT REPRESENTATIVE IN WRITING PRIOR TO CONSTRUCTIONANDACCEPTANCE OF THE CHANGE. 20: THE RECYCLED WATER SYSTEM SHALL BE PRESSURE TESTED IN ACCORDANCE WITH THE PROCEDURES IN THE OMWD STANDARD SPECIFICATIONS. THE CLASS OF PIPE SHALL BE USED AS THE DESIGNATED WORKING PRESSURE FOR TESTING ALL PIPE, VALVES (CLOSED) AND APPURTENANCES. 21.CONTRACT RECORD DRAWINGS MUST BE SUBMITTED PRIOR TO FINAL ACCEPTANCE OF WORK THE PLANS MUST PROVIDE POST CONSTRUCTION VERIFICATION OF THE LOCATIONAND ELEVATION OF PIPESANDAPPORTENANCES. 22. CONTRACTOR SHALL GUARANTEE ALL WORK FOR A PERIOD OF ONE (1) YEAR AFTER THE DATE OF ACCEPTANCE FOR THE PROJECT. CONTRACTOR SHALL REPAIR OR REPLACE ANY OR ALL SUCH WORK, TOGETHER WITH ANY OTHER WORK WHICH MAY BE DISPLACED IN SO DOING THAT MAY PROVE DEFECTIVE IN WORKMANSHIP AND /OR MATERIALS WITHIN THE ONE -YEAR PERIOD FROM THE DATE OF ACCEPTANCE WITHOUT EXPENSE WHATSOEVER TO THE DISTRICT, ORDINARY WEAR AND TEAR, UNUSUAL ABUSE OR NEGLECT EXCEPTED. 23, ALL BURIED FITTINGSAND VALVES SHALL BE WAX TAPE WRAPPED INACCORDANCE WITH OMWD STANDARD SPECIFICATIONS. 24.ALL IRRIGATION METERS SHALL BE SERVED WITH RECYCLED WATER UNLESS PREVIOUSLY APPROVED IN WRITING BY THE DISTRICT VEGETATED SWALE (SLOPE PER STREET) 0 - TC = SDWK FS _ 2„ 5.0' ROCK RIP RAP PCC - - -- -- CURB 3.0' OPENING�1 *�.. .- ...�...�_.. TO PER 1 SHEET 3 6" PCC C &G PER FL = PER END V OPENINGS IN PCC SDRSD G -2 WITH 1' PLAN C &G: TRANSITION TO OPENINGS 20' O.C. OUTLET TO =PER SHEET 3 TYPICAL DETAIL - OUTLET FROM ROADSIDE SWALE NOT TO SCALE EXISTING TORREY PINE TREE FO BE 't REMOVED r PROPOSED STREET TREE: SEE DETAIL THIS SHEET FOR ROOTBARRIER INFO CONSTRUCT5 "PCC _ SIDEWALK PER 2.0% SDRSD G -7 CONSTRUCT ROADSIDE BIORETENTION BASIN PER DETAIL THIS SHEET CONSTRUCT MODIFIED G -2 PCC CURB & GUTTER PER DETAIL THIS SHEET APPROXIMATE LOCATION OF EXISTING 3" HP GAS LINE INSTALL MIN 5 "AC OVER 6" CLASS II AB OR PER GEOTECH RECOMMENDATION R VEGETATED PL p SWALE (SLOPE PCC SIDEWALK 1 PER STREET PER SDRSD G -7 21 21 Ld a 2.1 - 2 :1 TC PER FACE OF LONG. SLOPE 6" PCC C &G PER SHEET 3 CURB A (PER PLAN) SDRSD G -2 WITH V OPENINGS 20'0. C. TYPICAL DETAIL - ROADSIDE VEGETATED SWALE 4.5' SCALE. I"= 5' HORIZONTAL 50' FROM BC PROPOSED TORREY PINE TREE 4" PCC SIDEWALK PER SDRSD G -7 2.0% . H _ 2p VEG. SWALE 20' LONG X 48" DEEP 10' LONG X 24" DEEP ROOT ROOTBARRIER BARRIER CENTEREDAT CENTEREDATNEW STREET TREE LOCATIONS L L:- TORREY PINE LOCATIONS 3" THICK MULCH OVER 12" ENGINEERED SOIL LAYER; *SEE NOTE BELOW SECTION A A BIKE�TR41 LANE NOT TO SCALE q - le.0 _ IL.V' MEL LANE STRIPED MEDIAN 3" DROP TO TOP OF MULCHAT V CURB OPENINGS (TYP.) EXISTING TORREY PINE TREE TO BE REMOVED m 6" PCC C &G PER SDRSD G -2; STREET DE4PENAS NECESSARY TO TREE (TYP.) EXTEND BENEATH SWALE y AC PAVEMENT 10' LONG X 36" DEEP ROOT BARRIER CENTEREDAT STREET TREE LOCATIONS 'NOTE ENGINEERED SOIL LAYER SHALL BE EVENLY MIXED COMPOSITION OF WASHED SAND, SANDY LOAM TOPSOIL, AND HUMIC COMPOST. THE MIX SHALL CONTAIN 65% SAND, 20% TOPSOIL, AND 15% COMPOST OR HARDWOOD MULCH IN ACCORDANCE WITH COUNTY OF SAN DIEGO LID BIOSWALE MEDIA B1065 CUT SHEET EXISTINGAC PAVING EXISTINGAC BERM VAKIG) STDS MW 0 TC = SDWK FG - FL FS +0.5' +0.1' 6" PCC CURB PROPERTY LINE / RIGHT -OF -WAY @ 15°ANGLE RECOMMENDATIONS TO FLOW <' W INSTALL 6" SEWER LATERAL SDRSD SS -01 S------OS GENERAL RECYCLED WATER SYSTEM NOTES 1. THE RECYCLED WATER SYSTEM SHALL CONFORM TO THE RULES AND REGULATIONS FOR RECLAIMED AND NON - POTABLE WATER SERVICE OF THE OLIVENHAIN MUNICIPAL WATER DISTRICT, ORDINANCE NO. 175, DATED MARCH 1989, AND ALL SUBSEQUENT AMENDMENTS. 2. RECYCLED WATER WORKS SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE DETAILS AND MATERIALS AS SPECIFIED IN THE MOST RECENT EDITION OF THE OLIVENHAIN MUNICIPAL WATER DISTRICT (DISTRICT) STANDARD SPECIFICATIONS FOR THE CONSTRUCTION OF WATER MAINS AND FACILITIES, INCLUDING ALL AMENDMENTS ADOPTED PRIOR TO THE DISTRICT APPROVAL DATE ON THESE PLANS. CONTRACTOR SHALL HAVEA COPY OF THE OMWD STANDARD SPECIFICATIONS ON THE JOB SITEATALL TIMES. 3. THE SUBMISSION AND REVIEW OF ALL SUBMITTALS (SHOP DRAWINGS, SIX SETS) AS REQUIRED BY THE OMWD STANDARD SPEC/FICATIONSARE TO BEACCOMPLISHED PRIOR TO THE PRE - CONSTRUCTION MEETING WITH THE DISTRICTS INSPECTOR. 4.UNLESS OTHERWISE NOTED, CONNECTIONS TO EXISTING MAINS SHALL BE MADE DRY. THE TIME AND DURATION OF ANY SHUTDOWNS OF EXISTING MAINS SHALL BE SUBJECT TO APPROVAL BY THE DISTRICT.' DISTRICT SHALL BE NOTIFIED TWO WEEKS MINIMUM W ADVANCE OFANY SHUTDOWN. SCONTRACTOR SHALL COORDINATE WITH DISTRICT ALL ARRANGEMENTS FOR HIGH - LINING TEMPORARY SERVICES PRIOR TO SHUTDOWNS. NO SHUTDOWNS WILL BE SCHEDULED DNA MONDAY OR FRIDAY. 6. CONTRACTOR SHALL REVIEW ALL PROPOSED TRENCH WORK WITH CAIOSHA. A COPY OF EXEMPTION LETTER OR TRENCHING PERMIT, IF REQUIRED, SHALL BE SUBMITTED TO THE DISTRICT PRIOR TO CONSTRUCTION! 7 N WORK MAY BEGIN OR PROCEED WITHOUT DIRECTION OF DISTRICTS INSPECTOR, CONTRACTOR SHALL NOTIFY THE DISTRICT INSPECTIONS DEPARTMENT 48 HOURS PRIOR TO THE BEGINNING OF WORK TOARRANGE FOR INSPECTION OF THE PROJECT. 8.7HE CONTRACTOR MUST CALL 'DIG ALERT OF SOUTHERN CALIFORNIA" TO HAVE UNDERGROUND SERVICE UTILITIES LOCATED PRIOR TO CONSTRUCTION. THIS CALL WILL BE MADE AT LEAST 48 HOURS IN ADVANCE PRIOR TO ANY WORK BEING PERFORMED IN PUBLIC RIGHT -OF -AMY. 9.ALL EXISTING FACILITIES WHICH MAY AFFECT FINAL CONSTRUCTION, LE, LINE CROSSINGS, LINE PARALLELING, OR PROPOSED CONNECTIONS SHALL BE FIELD VERIFIED. 10. THE CONTRACTOR SHALL FURNISHAND INSTALL PER THE OMWD STANDARD SPECIFICATIONS THE APPROPRIATE BURIED UTILITY WARNING AND IDENTIFICATION TAPE ABOVE ALL PUBLIC RECYCLED WATER LINES INCLUDING RECYCLED WATER LATERALS LOCATED IN PUBLIC RIGHT -OF -WAY. 11. RECYCLED WATER MAIN SHALL BE PURPLE PVC PIPE AWWA C 900, WITH TWO CONTINUOUS METALLIC TAPE STRIPS, STAMPED "RECYCLED WATER. " STRIPS SHALL BE SETAT TOP OF PIPEANDAT 24 "ABOVE THE PIPE. 12. WHERE ELEVATIONS AND GRADES ARE NOT SHOWN ON THE WATER MAIN PROFILE, TOP OF PIPE PROFILE IS 66- INCHES BELOW CENTERLINE OF FINISH GRADE OF STREET. 13. ALL DEFLECTIONS (HORIZONTALAND VERTICAL) SHALL BE MADE BY USE OF JOINT COUPLINGS WITH 4° MAXIMUM DEFLECTION PER COUPLING (2° PER JOINT). NO BENDING (CURVING) OF PIPE SHALL BE PERMITTED. 14.M4NUAL AIR RELEASES SHALL BE INSTALLED AT ALL HIGH POINTS AND BLOW -OFFS AT ALL LOW POINTS IN THE WATER MAIN PROFILE. MANUAL AIR RELEASES AND BLOW-OFFS SHALL BE LOCATED BEHIND CURB UNLESS OTHERWISE APPROVED BY DISTRICT'S REPRESENTATIVE. 15 INSTALL RECYCLED WATER SERVICE(S) IN ACCORDANCE WITH SIZE(S) DEFINED ON THE DRAWINGS, LOCATIONS OF RECYCLED WATER METERS ARE SUBJECT TO APPROVAL BY DISTRICTS INSPECTOR. 314 -INCH HIGH LETTERS 'RW' SHALL BE CHISELED IN TOP OF EXISTING CURB OR IMPRINTED IN NEW CURBATALL RECYCLED WATER SERVICE CROSSINGS. 16. METER BOXES SHALL NOT BE PLACED WITHIN DRIVEWAYS OR SIDEWALKS WITHOUT THE DISTRICT'S PRIOR WRITTEN CONSENT. 17 CONTRACTOR TO TIE OFF ALL VALVE LOCATIONS AND PROVIDE WRITTEN DIMENSIONS TO INSPECTOR IMMEDIATELY UPON INSTALLATION OF VALVES. 18. LINE VALVES, WHERE RE UIREDATSTREE S Q T INTERSECTIONS SEC ION SHALL BE LOCATEDAT THE TEE WHENEVER POSSIBLE. 19.ALL DESIGN CHANGES TO THE RECYCLED WATER SYSTEM SHALL BE APPROVED BY THE DISTRICT REPRESENTATIVE IN WRITING PRIOR TO CONSTRUCTIONANDACCEPTANCE OF THE CHANGE. 20: THE RECYCLED WATER SYSTEM SHALL BE PRESSURE TESTED IN ACCORDANCE WITH THE PROCEDURES IN THE OMWD STANDARD SPECIFICATIONS. THE CLASS OF PIPE SHALL BE USED AS THE DESIGNATED WORKING PRESSURE FOR TESTING ALL PIPE, VALVES (CLOSED) AND APPURTENANCES. 21.CONTRACT RECORD DRAWINGS MUST BE SUBMITTED PRIOR TO FINAL ACCEPTANCE OF WORK THE PLANS MUST PROVIDE POST CONSTRUCTION VERIFICATION OF THE LOCATIONAND ELEVATION OF PIPESANDAPPORTENANCES. 22. CONTRACTOR SHALL GUARANTEE ALL WORK FOR A PERIOD OF ONE (1) YEAR AFTER THE DATE OF ACCEPTANCE FOR THE PROJECT. CONTRACTOR SHALL REPAIR OR REPLACE ANY OR ALL SUCH WORK, TOGETHER WITH ANY OTHER WORK WHICH MAY BE DISPLACED IN SO DOING THAT MAY PROVE DEFECTIVE IN WORKMANSHIP AND /OR MATERIALS WITHIN THE ONE -YEAR PERIOD FROM THE DATE OF ACCEPTANCE WITHOUT EXPENSE WHATSOEVER TO THE DISTRICT, ORDINARY WEAR AND TEAR, UNUSUAL ABUSE OR NEGLECT EXCEPTED. 23, ALL BURIED FITTINGSAND VALVES SHALL BE WAX TAPE WRAPPED INACCORDANCE WITH OMWD STANDARD SPECIFICATIONS. 24.ALL IRRIGATION METERS SHALL BE SERVED WITH RECYCLED WATER UNLESS PREVIOUSLY APPROVED IN WRITING BY THE DISTRICT VEGETATED SWALE (SLOPE PER STREET) 0 - TC = SDWK FS _ 2„ 5.0' ROCK RIP RAP PCC - - -- -- CURB 3.0' OPENING�1 *�.. .- ...�...�_.. TO PER 1 SHEET 3 6" PCC C &G PER FL = PER END V OPENINGS IN PCC SDRSD G -2 WITH 1' PLAN C &G: TRANSITION TO OPENINGS 20' O.C. OUTLET TO =PER SHEET 3 TYPICAL DETAIL - OUTLET FROM ROADSIDE SWALE NOT TO SCALE EXISTING TORREY PINE TREE FO BE 't REMOVED r PROPOSED STREET TREE: SEE DETAIL THIS SHEET FOR ROOTBARRIER INFO CONSTRUCT5 "PCC _ SIDEWALK PER 2.0% SDRSD G -7 CONSTRUCT ROADSIDE BIORETENTION BASIN PER DETAIL THIS SHEET CONSTRUCT MODIFIED G -2 PCC CURB & GUTTER PER DETAIL THIS SHEET APPROXIMATE LOCATION OF EXISTING 3" HP GAS LINE INSTALL MIN 5 "AC OVER 6" CLASS II AB OR PER GEOTECH RECOMMENDATION R VEGETATED PL p SWALE (SLOPE PCC SIDEWALK 1 PER STREET PER SDRSD G -7 21 21 Ld a 2.1 - 2 :1 TC PER FACE OF LONG. SLOPE 6" PCC C &G PER SHEET 3 CURB A (PER PLAN) SDRSD G -2 WITH V OPENINGS 20'0. C. TYPICAL DETAIL - ROADSIDE VEGETATED SWALE 4.5' SCALE. I"= 5' HORIZONTAL 50' FROM BC PROPOSED TORREY PINE TREE 4" PCC SIDEWALK PER SDRSD G -7 2.0% . H _ 2p VEG. SWALE 20' LONG X 48" DEEP 10' LONG X 24" DEEP ROOT ROOTBARRIER BARRIER CENTEREDAT CENTEREDATNEW STREET TREE LOCATIONS L L:- TORREY PINE LOCATIONS 3" THICK MULCH OVER 12" ENGINEERED SOIL LAYER; *SEE NOTE BELOW SECTION A A BIKE�TR41 LANE NOT TO SCALE q - le.0 _ IL.V' MEL LANE STRIPED MEDIAN 3" DROP TO TOP OF MULCHAT V CURB OPENINGS (TYP.) EXISTING TORREY PINE TREE TO BE REMOVED m 6" PCC C &G PER SDRSD G -2; STREET DE4PENAS NECESSARY TO TREE (TYP.) EXTEND BENEATH SWALE y AC PAVEMENT 10' LONG X 36" DEEP ROOT BARRIER CENTEREDAT STREET TREE LOCATIONS 'NOTE ENGINEERED SOIL LAYER SHALL BE EVENLY MIXED COMPOSITION OF WASHED SAND, SANDY LOAM TOPSOIL, AND HUMIC COMPOST. THE MIX SHALL CONTAIN 65% SAND, 20% TOPSOIL, AND 15% COMPOST OR HARDWOOD MULCH IN ACCORDANCE WITH COUNTY OF SAN DIEGO LID BIOSWALE MEDIA B1065 CUT SHEET EXISTINGAC PAVING EXISTINGAC BERM VAKIG) STDS MW SUBDIVISION BOUNDARY (EXISTING) �-2 0 VARIES VARIES CENTERLINE OF ROAD TO SATISFACTION OF CITY ENGINEER - PROPERTY LINE / RIGHT -OF -WAY (4" THICK MIN) RECOMMENDATIONS INSTALL 6" PRIVATE WATER MAIN SEE 14075 -G W INSTALL 6" SEWER LATERAL SDRSD SS -01 S------OS INSTALL 2" DOMESTIC WATERSERVICE, OMWDB- 1.21C -2.1 W ---ca= METER & BACKFLOW it INT. INSATLLI .5 " IRRIGATION WATER SERVICE, OMWDB-1.21C-2.1 W ---p -Q METER & BACKFLOW 14075 -1 INSTALL 6" FIRE SERVICE WITH RPDA OMWO C -3.3 W W -O EXISTING WATER U41N (SIZE PER PLAN) U d EXISTING OVERHEAD UTILITIES ---- OHE EXISTING SEWER MAIN (SIZE PER PLAN) TYLER G LAWSON DATE ------- - - - - -- s. EXISTING SEWER MANHOLE GRIND & OVERLAY PER DETAIL THIS SHEET SAWCUT LINE APPROXIMATE LOCATION - OF EXISTING 10 "AC WATER EXISTING EDGE MAIN PER RS 1802 OF PAVEMENT APPROXIMATE LOCATION OF EXISTING 8" PVC SEWER MAIN PER TM 3960 -1 TYPICAL SECTION - SOUTH EL CAMINO REAL NOT TO SCALE LEGEND: THE QUANTITIES LISTED BELOWARE PROVIDED FOR REFERENCE ONLYAND DO NOT RELIEVE THE CONTRACTOR FROM COMPLETINGAN INDEPENDENTANALYSIS OF THE QUANTITIESAND COSTSASSOCIATED WITH THE IMPROVEMENTS REQUIRED FOR THIS PROJECT ITEM & STD. DWG. STDS SYMBOL SUBDIVISION BOUNDARY (EXISTING) & GUTTER PER SDRSD - CENTERLINE OF ROAD TO SATISFACTION OF CITY ENGINEER - PROPERTY LINE / RIGHT -OF -WAY (4" THICK MIN) RECOMMENDATIONS INSTALL 6" PRIVATE WATER MAIN SEE 14075 -G W INSTALL 6" SEWER LATERAL SDRSD SS -01 S------OS INSTALL 2" DOMESTIC WATERSERVICE, OMWDB- 1.21C -2.1 W ---ca= METER & BACKFLOW INT. INSATLLI .5 " IRRIGATION WATER SERVICE, OMWDB-1.21C-2.1 W ---p -Q METER & BACKFLOW 14075 -1 INSTALL 6" FIRE SERVICE WITH RPDA OMWO C -3.3 W W -O EXISTING WATER U41N (SIZE PER PLAN) U d EXISTING OVERHEAD UTILITIES ---- OHE EXISTING SEWER MAIN (SIZE PER PLAN) TYLER G LAWSON DATE ------- - - - - -- s. EXISTING SEWER MANHOLE !ail PROPOSED EASEMENT - - - - - EXISTING EASEMENT RECORD FROM: ROS 18416 ELEVATION: 37.521' DATUM: NAVD -88 - PROPOSED CONTOUR 82 NEWAC PAVEMENT (5-AC OVER 6" CLASS II AB OR PER GEOTECH) INSPECTOR REMOVE & REPLACE EXISTINGAC PAVEMENT SHEET 2 OF 4 xsfiw ' (5 "AC OVER 6" CLASS 11 AB OR PER GEOTECH) PCC PAVEMENT (PER PLAN) TRENCH RESURFACING SDRSD G -24A 6 "PCC CURB SDRSD G -1 6" PCC CURB & GUTTER SDRSD G -2 SAWCUT EXISTINGAC PAVEMENT CURB OUTLET SDRSD D -25 ABBREVIATION LEGEND BIN = BOTTOM OF WALL ELEVATION FS =FINISHED SURFACE FG = FINISHED GRADE FL = FLOWLINE FF= FINISHED FLOOR ELEVATION w z m U 28.0' (TYP.) 26.0' (TYP.) 20' v I GF = GARAGE FACE ELEVATION IE = INVERT ELEVATION TG = TOP OF GRATE ELEVATION TF = TOP OF FOOTING ELEVATION TW = TOP OF WALL ELEVATION COLD PLANEAND OVERLAY (2" MIN DEPTH) TO PROVIDE SMOOTH TRANSITION _ EXISTING AC PAVEMENT �R014" No. 80356 Exp. 12/31,120 CIV1� NOT TO SCALE Lo 0 N rn U x �w00 U Z m o LO U) J N ¢Wm oa¢� w w Lu �_LL C/) ('4 W 0 OD rn O co U Z m a�a PASCO LARET SUITER & ASSOCIATES CIVIL ENGINEERING + LAND PLANNING + LAND SURVEYING 535 North Highway 101, Ste A. Solana Beach, CA 92075 ph 858.259.8212 1 fa 858.259.4812 1 plasengineering.com INSTALL MINIMUM 5 "AC OVER 6" CLASS INSTALL 6" PCC CURB II AB OVER NATIVE SUBGRADE & GUTTER PER SDRSD COMPACTED TO 95% REL. COMP OR - G-2; EXTEND BASE TO SATISFACTION OF CITY ENGINEER MATERIAL UNDER C &G OR GE07ECHNICAL ENGINEER (4" THICK MIN) RECOMMENDATIONS TYPICAL DETAIL - SAWCUTAC PAVEMENT �R014" No. 80356 Exp. 12/31,120 CIV1� NOT TO SCALE Lo 0 N rn U x �w00 U Z m o LO U) J N ¢Wm oa¢� w w Lu �_LL C/) ('4 W 0 OD rn O co U Z m a�a PASCO LARET SUITER & ASSOCIATES CIVIL ENGINEERING + LAND PLANNING + LAND SURVEYING 535 North Highway 101, Ste A. Solana Beach, CA 92075 ph 858.259.8212 1 fa 858.259.4812 1 plasengineering.com PLSA 2235 -02 CHANGE NO. DESCRIPTION APPROVED DATE BENCHMARK AS -BUILT APPROVALS DESIGNED BY: DRAWN BY: cHECKEO BY: ENGINEERING DIVISION APPROVALS CITY OF ENCINITAS - DEVELOPMENT SERVICES DEPARTMENT DRAWING NO. K BAN TGL DESCRIPTION: STATION "ENC -36" POINT 1038 LOCATION: NE CORNER OF DRAINAGE CURB INLET IN EAST SIDE OF MANCHESTER AVE, 0.1 MILE SOUTH OF ELCAMINOREALINTERSECTION INT. DATE PLANS PREPARED UNDER SUPERVISION OF DATE: ,r -2, - /% �J R.C.E. NO.: 80356 �►1� �+-- TYLER G LAWSON EXP.: 12/31/20 RECOMMENDED: AP V .14 ��� --�4'� JESS WENS DWARDJ.WI ER CITY E iGIN d/7/1e' o DATE '7 ' DATE1 LEGEND, NOTES, AND TYPICAL DETAILS FOR: WESTMONT OF ENCINITAS 1920 S. EL CAMINO REAL APN: 262- 160 -26 & 27 I PLANNING CASE NO: 16 -131 MUP / DR / PMW / CDP 14075 -1 PUBLIC WORKS TYLER G LAWSON DATE PLANNING RECORD FROM: ROS 18416 ELEVATION: 37.521' DATUM: NAVD -88 EDWARD J. WIMMER DATE CITY ENGINEER REVIEWER INSPECTOR SHEET 2 OF 4 PLSA 2235 -02 Jr Jr j ! EXISTING PCC C &G ` AND ! j KTO REMAIN ! � REMAIN f r� Ell ~ 1 j86.62 TC) i j't �E {(86.62 FL) I ECRSTA56 +85.32; - 53.0LT- r 1(? (86.52 TC); (86,02 FL) f f EXISTING" GAS j ' 4.5' \ f f M41NTOOEMAIN 86.50 TC i W 86.00 FL ao E o o 6" PCC CURB � Ch 'u P ER SDRSD r � G-1 I J 0 ` <> < > �} ECR STA 56 +871J' -5$.0' LT I C.; 85.93 FS / TC -0 r \~ i SDRSD G -31 TW?E'D' PED EXISTING TR�+ - I L / TO BE REMOVES RAMP WITH G-30, YELLOW ' DOMES 1 v PORTION EXIS*G EXISTING OVERHEA CURB TO BE UTILITIES TO BE r t ! REMOVED !' LMIDERGROUND / f i 'a FL 1 r FL -` W, W \ ✓' \ eta SLIRVEYMONUMENITO f;9 `O I �R�N1bYEDAND REPLACEW - t E - _ E SEE CORNER RECORD o{ EXISTING MAILBOXES I k TO BE RELOCATED UXCYN8TA4+ - ... BEHIND SIDEWALK _ f `- 12.0'LT 4 86.85 TC; 86.35 �JOSTING POWER POLE TO BE { EMOVED Lu 4 PCC CROSS 0 I� t D J ! t (STING OVERHEAD GUTTER' \ I �i U ILITIES TO BE / a ` \ U DERGROUND 85.65 FL "'185. 85. FS 4t O Lu ) I p �/ 0 V REMOVEEXISTING L /A CAN f ON 17RIVEN44YAPRON � { �I DRIVE LIJ T. 86.5 TO - = ' p (GRO$ \ 85. U 2,1E 86.50 TC I \ G R t l 86.00 FL \ � t 1 W 86.40 Tip ' `l 86.40 FL It 85.69 � i U e 85 It 69 FS E TA56 +31.88 -56.7 LT 8a ?S; G-27 TYP A' CURB po j- RAMAW /'1 ELBOW (INCATED r \�1 I °� 1�1it'S PER SL)R 0 8.70 FS / I \ 6.18 FS / C� . 1r I'., cn "� 86.62 FS t > -- . . _ _____- _ 1 l! __..___ r EXISTING 3" I 86.68 FS f / �� o Y" HP GAS MAIN( I �.Y 70 FS �, i 86,25 FS �/ 6:13 FS 1 i ECR ' S ffi6 +22.05 537 (n .860.70 4'5FL [r 5 X4 LANDING W W V�r - 20%1 � � W - 86.19 FS uj 1 / o� 86.09E W W W ; W W- t PVT. STORM DRAIN ECR PER 14075 -G 8610 FS o -53~01 f i Imo. 85 A $8. aFL i PIED RAMPAND CURB RETURN DETAILS - EL CAMINO REAL NOT TO SCALE .f I C , 3' 'B BO , 86. rr p A 81. IN T p!N 418SQ1 S .5 IN r i t I I 1 ! + ` PL 1 r iAWCSIDE BMP E; SEE DETAIL r f W / {}EET 2 L0 EXISTING GAS MAIN k l }{ TO REMAIN Lu W C9 ECR STA 52 +99.75 -5 .0' LT l 1 ` OUTLETFROMROAD IDESWALE;,'�" �\ T SEE DETAIL SHEET 21 } 81.73 TC; 81,23 FL (9 �, 1 -81351EOUT,-`' I 26�CP8 Q10D I -, PROPOSED X X � . B Ld PL (81.25FS) 7j (77 %)_ 1 MODIFIED TYPE A' (81.3 FS) (8j.25 FS) r STORM DRAIN C.O.; 1 L =9; M6; 87.5 RIM i MATCH { J l� SIDEEWALK (81.1 FS) f Q EXISTING DWY t TO REMAIN � , k i Lti r fjr jl f EXALL ISTING TO (81.1 FS) REMAIN (By.dFS) TYPICAL DETAIL - CURB OUTLET SCALE: 1 "= 5'HORIZONTAL 0 EXISTIN WATER SERVICEAND METER OXES TO BE ABANDONED IN ACCORDANCE WITH OMWD SPECS W ILj+ W - L W 71 W -- - W j 81.01E I. 80.951E i0 EXISTINGDRYUTIL. STRUCTURE L BE PROTECTED IN N PLACE (81.3 TC) � (80.8 FL) ECR STA 52TA+81- I BEGIN DWYAPRON WING P SDRSD G -14B, MATCH `{ TO EXISTING; (80.7 FL)� F LEADAND TAG SURVE MONUMENT TO BE RE O0 AND REPLACED; SEE O(2A RECORD�� { \ - EXISTING PCC DWYTO REM41N CONNECT D -25 CURB OUTLET 18" PVC S.D. TO MODIFIED STORM DRAIN CONNECT D -25 CURB OUTLET BEYOND, C.O.; 81.251E OUT TO MODIFIED STORM DRAIN 81.41E IN C.O.; 81.351EOUT SECTION B -B: D -25 CURB OUTLET FROM C. 0. NOT TO SCALE EXISTING LANE STRIPING TO REMAIN ;l V 114{ J ( F 1 (J 63' 51f i I \1 f41f Ir(�lli II I t 1 t (t \\ \ PROPOSED 8' WIDE BIKE LANE WITH6 "WHITE LINES it i� IM VN PER CALTRANS STD PLAN i A20D DETAIL 39 AND 39A 1 1 I �EXIPTING LAN STRIRIN(� REF RESH / ( IIN E� STING Ld STRIPING ATION T �� SATISFACTION FCITYOF ° ttm,\EWtIY}I S EXISTING LANE I 1 STRIPING TO BE REMOVED �`riI li 1` it BIKE LANE LEGEND A + f PER CALTRANS STD PLANA24AANDA24D ,- >t I I I1'/ 15' CENTER LANE 11 SIPIN G� 6" CURB &GUTTER REFRESH RII N RE IN EXISTING \ PER SDRSD 0-2; ; 1111 L-: LOCATI9N TO- SAP*779N SEE SHEET 3 .1 111 �' O CI71"OFFJNCCINITAS PROPOSED 8' WIDE BIKE ) " EXTIN(3 ORTHBOUND I LANEWITH6 "WHITE ( j1 LINES PER CALTRANS STD \ i I I I'� TRAVEL ES PLANA20D DETAIL 39 ; . - 8' \ y If o? _ i 4r f2 t uj V�GETAilC)N VZ 21 EXISTING i ! w STRIPING TO f I I \ 1 \ \ BE REMOVED ! _j It `; - t PROPOSED 8' WIDE BIKE LANE WITH GREEN TRAFFIC 15' Y4 +/ z +) 2' +/ 11'+ 14' + PAINT FOR 50 FEET FROM / f START OF CONFLICT ZONE �ISTING SQGTHBOUND TRAVEL LANES >6 / f , 6" CURB &GUTTER PER SDRSD G -2; SEE SHEET 3 { f I 1 / TRANSITION 8' WIDE BIKE LANE TO MATCH EXISTING GREEN BIKE ; LANE, SEE CALTRANS STD PLAN' I : t I I �) A20D D-EtAIL 39AWITH GREEN` END PROPOSED LANE \1 i ! t ( TRAFFIC PAINT / STRIPING MATCH TOg��j"" l EXISTING EXISTING RIGHT t TURN LANE TO REMAIN zs' m, 0 63' !F IC 1 6311 1 / STRIPING PLAN - EL CAMINO REAL SCALE: 1"= 40' HORIZONTAL y No. 80356 z Exp. 12/31/20 PASCO LARET SUITER & ASSOCIATES CIVIL ENGINEERING + LAND PLANNING + LAND SURVEYING 595 North Highway 101, Ste A, Solana Beach, CA 92075 ph 858.259.8212 1 ft 858.259.4812 1 piaaenglneering.com CHANGE NO. DESCRIPTION APPROVED DATE 4` EXISTING LANE STRIPING TO REMAIN ;l V 114{ J ( F 1 (J 63' 51f i I \1 f41f Ir(�lli II I t 1 t (t \\ \ PROPOSED 8' WIDE BIKE LANE WITH6 "WHITE LINES it i� IM VN PER CALTRANS STD PLAN i A20D DETAIL 39 AND 39A 1 1 I �EXIPTING LAN STRIRIN(� REF RESH / ( IIN E� STING Ld STRIPING ATION T �� SATISFACTION FCITYOF ° ttm,\EWtIY}I S EXISTING LANE I 1 STRIPING TO BE REMOVED �`riI li 1` it BIKE LANE LEGEND A + f PER CALTRANS STD PLANA24AANDA24D ,- >t I I I1'/ 15' CENTER LANE 11 SIPIN G� 6" CURB &GUTTER REFRESH RII N RE IN EXISTING \ PER SDRSD 0-2; ; 1111 L-: LOCATI9N TO- SAP*779N SEE SHEET 3 .1 111 �' O CI71"OFFJNCCINITAS PROPOSED 8' WIDE BIKE ) " EXTIN(3 ORTHBOUND I LANEWITH6 "WHITE ( j1 LINES PER CALTRANS STD \ i I I I'� TRAVEL ES PLANA20D DETAIL 39 ; . - 8' \ y If o? _ i 4r f2 t uj V�GETAilC)N VZ 21 EXISTING i ! w STRIPING TO f I I \ 1 \ \ BE REMOVED ! _j It `; - t PROPOSED 8' WIDE BIKE LANE WITH GREEN TRAFFIC 15' Y4 +/ z +) 2' +/ 11'+ 14' + PAINT FOR 50 FEET FROM / f START OF CONFLICT ZONE �ISTING SQGTHBOUND TRAVEL LANES >6 / f , 6" CURB &GUTTER PER SDRSD G -2; SEE SHEET 3 { f I 1 / TRANSITION 8' WIDE BIKE LANE TO MATCH EXISTING GREEN BIKE ; LANE, SEE CALTRANS STD PLAN' I : t I I �) A20D D-EtAIL 39AWITH GREEN` END PROPOSED LANE \1 i ! t ( TRAFFIC PAINT / STRIPING MATCH TOg��j"" l EXISTING EXISTING RIGHT t TURN LANE TO REMAIN zs' m, 0 63' !F IC 1 6311 1 / STRIPING PLAN - EL CAMINO REAL SCALE: 1"= 40' HORIZONTAL y No. 80356 z Exp. 12/31/20 PASCO LARET SUITER & ASSOCIATES CIVIL ENGINEERING + LAND PLANNING + LAND SURVEYING 595 North Highway 101, Ste A, Solana Beach, CA 92075 ph 858.259.8212 1 ft 858.259.4812 1 piaaenglneering.com PL5A 2235 -02 CHANGE NO. DESCRIPTION APPROVED DATE BENCHMARK AS -BUILT APPROVALS DESIGNED BY. DRAWN BY CHECKED B`Y ENGINEERING DIVISION APPROVALS CITY OF ENCINITAS - DEVELOPMENT SERVICES DEPARTMENT DRAWING NO. BAK BAK TGL DESCRIPTION: STATION "ENC -36" POINT 1038 LOCATION: NE CORNER OF DRAINAGE CURB INLET IN EAST SIDE OF MANCHESTER AVE, 0.1 MILE SOUTH OF EL CAMINO REAL INTERSECTION INT. DATE PLANS PREPARED UNDER SUPERVISION OF DATE: �_ e7 R.C.E. NO.: 80356 TYLER G LAWSON EXp.: 12/31/20 REC MMENDED: A OV 9 JE SE OWENS DWARD J. MER S ( CITY `I B r DATE DAT Z� PEDESTRIAN RAMP DETAILS / OFFSITE IMPROVEMENTS / STRIPING PLAN FOR: WESTMONT OF ENCINITAS 1920 S. EL CAMINO REAL APN: 262- 160 -26 & 27 PLANNING CASE NO: 16 -131 MUP / DR 1 PMW / CDP 14075 -1 PUBLIC WORKS TYLER G LAWSON DATE PLANNING RECORD FROM: ROS 18416 ELEVATION: 37.521' DATUM: NAVD -88 EDWARD J. WINNER DATE CITY ENGINEER REVIEWER INSPECTOR SHEET 4 OF 4 PL5A 2235 -02