2017-13499 I (Plans)GENERAL RMHT- OF-WAY NO
1. NO ACCESS OR WORK SHALL BE PERFORMED WITHIN THE CITY RIGHT -OF -WAY WITHOUT THE
FULL KNOWLEDGE OF THE ASSIGNED CITY INSPECTOR WHO SHALL BE GIVEN NOT LESS THAN
48 HOURS ADVANCE NOTICE OF THE INITIATION OF PERMITTED USE AT (760) 633 -2796 OR
633 -2797, OR AS STATED ON THE PERMIT.
2.AT LEAST 48 HOURS PRIOR TO STARTING WORK, UNDERGROUND SERVICE ALERT (USA) SHALL
BE NOTIFIED FOR LOCATION OF UNDERGROUND UTILITIES AT 1 -800- 422 - 4133. THE
PROPOSED DIG AREA MUST BE MARKED IN WHITE PAINT PRIOR TO CONTACTING (USA).
3. ALL WORK COVERED BY THIS PERMIT SHALL BE PERFORMED BY A CONTRACTOR POSSESSING
A VALID CALIFORNIA CONTRACTOR'S LICENSE OF THE APPROPRIATE CLASS.
4.ALL TRAFFIC CONTROL WITHIN THE CONSTRUCTION AREA SHALL BE SUBJECT TO AN
APPROVED TRAFFIC CONTROL PLAN AND SHALL BE FLAGGED AND BARRICADED TO THE
SATISFACTION OF THE CITY INSPECTOR IN COMPLIANCE WITH THE "WORK AREA TRAFFIC
CONTROL HANDBOOK, LATEST EDITION PUBLISHED BY BUILDING NEWS, INC. IN THE EVENT
THAT THE INSPECTOR DETERMINES PROPER TRAFFIC CONTROL IS NOT IN PLACE, ALL WORK
SHALL CEASE AND PERMITTEE AUTHORIZES THE DIRECTOR OF ENGINEERING SERVICES OR HIS
DULY AUTHORIZED REPRESENTATVE TO ORDER, ON THE RENTAL BASIS, SUCH TRAFFIC
CONTROL DEVICES AS SHALL BE' NECESSARY AND PROPER TO PROTECT THE PUBLIC SAFETY
AND FURTHER AGREES TO PAY ANY AND ALL COSTS AND CHARGES THAT THE CITY MAY
INCUR IN PROVIDING SAID TRAFFIC CONTROL.
5.APPLICANT AGREES THAT IT SHALL BE HIS RESPONSIBILITY TO PROVIDE THE CONTRACTOR,
SUBCONTRACTOR, OR ANY OTHER AGENT RESPONSIBLE FOR CONSTRUCTION OF PERMITTED
WORKS WITHIN THE CITY RIGHT -OF -WAY, WITH A COPY OF THE PERMIT INCLUDING THESE
STANDARD CONDITIONS AND A COMPLETE SET OF APPROVED PLANS. THE PERMIT, PLANS
AND WORK AREA TRAFFIC CONTROL HANDBOOK SHALL BE AVAILABLE AT THE PERMIT SITE
WHENEVER WORK IS IN PROGRESS.
&PERMITTED WORKS SHALL BE CONSTRUCTED IN ACCORDANCE WITH THE CITY SPECIFICATIONS
AND APPROVED PLANS, SUBJECT TO INSPECTION AND APPROVAL BY THE DIRECTOR OF
ENGINEERING SERVICES OR HIS DULY AUTHORIZED REPRESENTAT7VE. CERTIFICATION FOR ALL
MATERIALS AND WORK, INCLUDING COMPACTION TESTS, SHALL BE FURNISHED BY THE
APPLICANT UPON REQUEST BY THE CITY INSPECTOR. PAYMENT FOR ANY COMPAC77ON
TESTING SHALL BE BY THE PERMITTEE. CERTIFICATION SHALL BE MADE BY A CER77FIED
TESTING AGENCY OR FIRM ACCEPTABLE TO THE CITY
7. NO WORK WITHIN THE PUBLIC RIGHT -OF -WAY IS PERMITTED ON SATURDAYS, SUNDAYS, OR
HOLIDAYS. ANY DEVIA770N FROM THE WORK SCHEDULE PRESENTED IN THESE CONDITIONS
MUST RECEIVE PRIOR, WRITTEN APPROVAL OF THE DIRECTOR OF ENGINEERING SERVICES OR
HIS DULY AUTHORIZED REPRESENTATIVE. ANY QUESTIONS REGARDING DAYS CITY HALL IS
CLOSED, CALL (760) 633 -2770.
S.NO WORK ON ANY PUBLIC ROADWAY, EXCLUDING PRIME ARTERIALS AND MAJOR ROADS,
SHALL BE STARTED BEFORE 7:30 A.M. OR CON77NUE AFTER 5:00 P.M. ON WEEKDAYS.
9.NO WORK SHALL BEGIN BEFORE 9 :00 A.M. OR CONTINUE AFTER 3:00 P.M. ON PRIME
ARTERIALS AND OTHER MAJOR ROADS, UNLESS AUTHORIZED ON THE PERMIT BY THE CITY
ENGINEER. ALL WORK ON PRIME ARTERIALS AND OTHER MAJOR ROADS, ALL AS SHOWN ON
THE CIRCULATION ELEMENT OF THE CITY'S GENERAL PLAN, WILL REQUIRE A TRAFFIC CONTROL
PLAN ACCEPTABLE TO THE CITY TRAFFIC ENGINEER WHOSE OFFICE CAN BE CONTACTED AT
(760) 633 -2704.
10. THE ROADWAY SHALL BE CLEAN AND FREE OF ALL OBSTRUCTIONS AND COMPLETELY
OPEN TO TRAFFIC AT THE END OF EACH WORKING DAY (NO LATER THAN 3:00 P.M. ON
MAJOR ROADS, DEFINED HEREIN.)
11. TWO -WAY TRAFFIC SHALL BE MAINTAINED AT ALL 77MES. MINIMUM TRAVEL LANE WIDTH
FOR MOTOR VEHICLES SHALL BE 12 FEET IF STREET WIDTH PREVENTS MAINTAINING TWO -WAY
TRAFFIC, PERMITTEE AND DIRECTOR OF ENGINEERING SERVICES SHALL AGREE ON AN
ADEQUATE TRAFFIC CONTROL PLAN PRIOR TO STARTING WORK, WHICH SHALL INCLUDE THE
USE OF A FULL -TIME FLAGMAN.
12. ALL EXCAVATIONS IN EXISTING PAVEMENT SHALL BE SAW CUT TO NEAT LINES AND AC
REPLACEMENT SHALL BE MADE TO THE SATISFACTION OF THE CITY ENGINEER OR HIS DULY
AUTHORIZED REPRESENTA77VE.
13. OPEN TRENCH MUST BE BACKFILLED AND CAPPED WITH AT LEAST 2" OF COLD MIX
ASPHALT OR METAL PLATED ACCORDING TO CITY SPECIFICATIONS DURING NON- WORKING
HOURS. METAL PLATES ARE REQUIRED TO HAVE COLD MIX ASPHALT RAMPS ON ALL (4)
SIDES AND MUST BE MAINTAINED. REFER TO THE CITYS STANDARD DRAWING DATED JULY 31,
1990.
14. NA77VE MATERIAL MAY BE USED UPON APPROVAL OF THE CITY ENGINEER OR HIS DULY
AUTHORIZED REPRESENTATIVE. REFER TO THE CITY'S STANDARD DRAWING DATED SEPTEMBER
30, 1996.
15. NO TUNNELING UNDER CURB AND GUTTER OR OTHER IMPROVEMENTS SHALL BE PERMITTED.
IMPROVEMENTS SHALL BE REMOVED AND REPLACED JOINT TO JOINT.
16. TWO SACK SAND - CEMENT SLURRY MIX SHALL BE REQUIRED AS BACKFILL ON ALL
L /ATERAL EXCAVATIONS WITHIN PRIME ARTERIALS, MAJOR ROADS AND COLLECTORS AS WELL
AS ALL LOCATIONS WHERE THE INSPECTOR DEEMS THE NATIVE MATERIAL TO BE
UNACCEPTABLE FOR USE AS BACKFILL.
17. CARE SHALL BE EXERCISED TO PREVENT WATER, SOIL AND DEBRIS FROM DEPOSITING IN
GUTTERS, STREETS AND STORM DRAINS. NO WASHING OUT OF MIXERS OR CONCRETE PUMPS
WILL BE ALLOWED ON CITY STREETS. VIOLATIONS WILL BE REFERRED FOR NPDES
ENFORCEMENT AND PENALTIES.
18. ANY ROADWAY STRIPING OR MARKINGS DAMAGED OR REMOVED DURING THE OPERATIONS
OF THIS PERMIT SHALL BE MATCHED AND REPLACED BY THE APPLICANT USING THE LATEST
EDITION OF STATE DEPARTMENT OF TRANSPORTATION SPECIFICATIONS FOR PAINT OR
THERMOPLASTIC, ALL TO THE SATISFACTION OF THE CITY ENGINEER OR HIS DULY
AUTHORIZED REPRESENTATIVE.
19. ALL CONCRETE WORK SHALL BE TRANSIT MIXED AND CONFORM TO THE STANDARD
SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION, LATEST EDITION, SECTION 201, AND BE
APPROVED BY THE CITY ENGINEER OR HIS DULY AUTHORIZED REPRESENTATIVE.
20. TRENCHING FOR INSTALLATIONS ACROSS ANY INTERSECTING ROADWAY OPEN TO TRAFFIC
SHALL BE PROGRESSIVE. NOT MORE THAN HALF OF THE WIDTH OF A TRAVELED ROADWAY
SHALL BE DISTURBED AT ONE 77ME AND THE REMAINING WIDTH SHALL BE KEPT OPEN TO
TRAFFIC BY BRIDGING OR BACKFILLING.
21. WHERE STREET DIMENSIONS AND STATE DEPARTMENT OF HEALTH SERVICES REGULATIONS
ALLOW, ALL PIPES AND CONDUITS LAID PARALLEL TO THE ROADWAY SHALL BE PLACED AT
LEAST FIVE (5) FEET FROM THE EDGE OF THE PAVEMENT OR GRADED TRAVELED ROADWAY,
UNLESS OTHERWISE AUTHORIZED IN WRITING BY THE CITY ENGINEER. THE SHALLOWEST
POR77ON OF ANY PIPELINE OR OTHER FACILITY SHALL BE INSTALLED NOT LESS THAN THIRTY
(30) INCHES BELOW THE ROADWAY SURFACE.
F 21(A). WHERE STREET DIMENSIONS AND STATE DEPARTMENT OF HEALTH SERVICES
REGULATIONS ALLOW, ALL PIPES AND CONDUITS LAID PARALLEL TO EXIS77NG UTILITIES
SHALL MAINTAIN A MINIMUM SEPARATION OF THREE (3) FEET MEASURED FROM THE
NEAREST EDGE OF THE FACILITY. ANY DEVIATION FROM THIS REQUIREMENT IS NOT ALLOWED
UNLESS APPROVED BY THE CITY ENGINEER OR HIS DULY AUTHORIZED REPRESENTATIVE.
22. ALL EXCAVATED MATERIAL SHALL BE CAST AWAY FROM THE IMPROVED POR77ON OF THE
HIGHWAY. AFTER THE WORK HAS BEEN COMPLETED, ALL EXCESS MATERIAL, INCLUDING
TRENCH SPOILS, SHALL BE REMOVED FROM THE RIGHT -OF -WAY. THE ROADWAY SHALL BE
LEFT IN NEAT AND ORDERLY CONDITION.
23. ALL ROADSIDE DRAINAGE DITCHES SHALL BE RESTORED TO TRUE GRADES AND THE
INTAKE AND OUTLET ENDS AT ALL CULVERTS SHALL BE LEFT FREE FROM ALL EXCESS
MATERIALS AND DEBRIS.
24. ALL APPROACHES TO PRIVATE DRIVEWAYS AND INTERSECTING ROADS AND STREETS SHALL
BE KEPT OPEN TO TRAFFIC AT ALL TIMES, UNLESS OTHERWISE APPROVED BY THE CITY
ENGINEER.
25. CLAY AND EARTH WHICH ADHERE TO THE PAVED SURFACE OF THE ROADWAY SHALL BE
REMOVED BY HAND SCRAPING, WASHING AND SWEEPING, OR BY ANY OTHER METHOD WHICH
WILL LEAVE A CLEAN NON -SKID SURFACE WITHOUT IMPAIRING, DAMAGING OR LOOSENING THE
SURFACE.
26. PERMITTEE SHALL COMPLY WITH ANY AND ALL DIRECTIVES ISSUED BY THE CITY ENGINEER
OR HIS DULY AUTHORIZED REPRESENTATIVE IN ORDER TO PREVENT DUST OR OTHER
MATERIALS FROM BECOMING A NUISANCE OR ANNOYANCE.
•
27. TEMPORARY PATCHING OF TRENCH IS REQUIRED ON LATERAL CUTS IN SURFACED STREETS
IMMEDIATELY AFTER BACKFILLING. AFTER COMPLETION OF THE REFILLING AND COMPACTING
OF THE BACKFILL MATERIAL IN THE EXCAVATION, ALL AS SPECIFIED IN THE STANDARD
DRAWING DATED SEPTEMBER 30, 1996, AND THE REMOVAL OF OBSTRUCTION(S), THE
PERMITTEE SHALL PROMPTLY REPLACE WITH TEMPORARY OR PERMANENT PATCHING
MATERIAL, OR REPAIR ANY PORTION OF THE HIGHWAY SURFACE REMOVED OR DAMAGED
BY THE EXCAVATION, OBSTRUCTION, OR CONSTRUCTION OPERATIONS, ALL TO THE
SATISFAC77ON OF THE CITY ENGINEER, AND AS SPECIFIED ELSEWHERE HEREIN. THE CITY
ENGINEER MAY, AT HIS OPTION, ELECT TO DO THE SURFACING OR REPAIRING HIMSELF; IN
SUCH CASE, THE PERMITTEE SHALL BEAR THE COST OF SUCH WORK. TEMPORARY
PATCHING MATERIAL MAY BE LEFT IN PLACE FOR UP TO 30 DAYS, BUT MUST BE
CON77NUALLY MAINTAINED.
28. WHERE THE PAVEMENT, EXCEPT PORTLAND CONCRETE CEMENT PAVEMENT, OR OTHER TYPE
OF SURFACE HAS BEEN REMOVED BY OTHERS, THE PERMITTEE SHALL REPLACE IT WITH A
STANDARD REPAIR OF FOUR (4) INCHES AC OVER APPROVED BACKFILL OR REPAIR
SECTION SHALL BE ONE (1) INCH AC GREATER THAN EXISTING STRUCTURAL SECTION,
WHICHEVER IS GREATER. REFER TO THE MOST CURRENT STANDARD DRAWING. REPAIRS TO
PCC PAVEMENT SHALL BE MADE PURSUANT TO THE SPECIFICATIONS OF THE ASSIGNED
ENGINEERING INSPECTOR.
29. IF, AFTER THE REFILLING OF AN EXCAVATION, THE PERMITTEE FAILS OR REFUSES TO
RESURFACE OR REPAIR THAT PORTION OF THE SURFACE OF THE ROADWAY DAMAGED BY
HIM, OR IF THE CITY ENGINEER HAS ELECTED TO DO SUCH RESURFACING OR REPAIRING,
THE CITY ENGINEER SHALL CAUSE THE REPAIR TO OCCUR, AND THE PERMITTEE SHALL BE
CHARGED WITH THE COST THEREOF COMPUTED BY THE DIRECTOR OF ENGINEERING
SERVICES.
30. WHEN SHORING IS REQUIRED, AN ENGINEERED DETAIL DRAWING WILL BE REQUIRED FOR
APPROVAL BY THE CITY ENGINEER. ALL OSHA REGULATIONS SHALL BE MET.
31. ALL DIRECTIONAL BORES SHALL BE SUBJECT TO APPROVAL OF THE METHOD IN THE FIELD
BY THE ASSIGNED ENGINEERING INSPECTOR, ACTING AS THE DULY AUTHORIZED AGENT OF
THE CITY ENGINEER. A THOROUGH EXAMINA77ON OF THE SUBSURFACE CONDITIONS IS A
PREREQUISITE. THE APPLICANT SHALL IDENTIFY THE BORE METHOD ON THE PERMIT
APPLICATION EITHER AS AUGER, HAMMER, HYDRAULIC, ETC., AND SHOW THE BORE PITS.
GROUTING AND INTERMEDIATE BORE PITS MAY BE REQUIRED.
32. ALL SUBSURFACE UTILITIES SHALL BE ACCURATELY SHOWN ON THE APPLICANT'S SITE
PLAN FOR THOSE EXCAVATIONS IN EXCESS OF 250 LINEAR FEET, TRAVERSING SIGNALIZED
INTERSECTIONS, CROSSING INTERCONNECT WIRES, OR OTHERWISE WHERE THE CITY
ENGINEER HAS A SPECIAL CONCERN.
33. PAVEMENT CUTS IN STREETS REHABILITATED OR NEWLY CONSTRUCTED WITHIN THE PAST
TWO YEARS SHALL BE CATEGORICALLY DENIED.
34. THE DEVELOPER SHALL BE RESPONSIBLE THAT ANY MONUMENT OR BENCH MARK WHICH IS
DISTURBED OR DESTROYED SHALL BE RE- ESTABLISHED AND REPLACED BY A REGISTERED
CIVIL ENGINEER OR A LICENSED LAND SURVEYOR.
35. THE REMOVAL OF ANY AND ALL CITY TREES SHALL BE CONSISTENT WITH THE CITY'S
URBAN FOREST MANAGEMENT PROGRAM. TREES LOCATED WITHIN CITY STREET
RIGHT -OF -WAY, ON CITY PROPERTY, OR WITHIN CITY EASEMENTS ARE REFERRED TO AS
CITY TREES AND SHALL BE PROTECTED IN PLACE DURING CONSTRUCTION UNLESS
SPECIFICALLY APPROVED OTHERWISE. NO GRADING, EXCAVATION, OR DISTURBANCE OF CITY
TREE ROOT SYSTEMS SHALL OCCUR WITHIN THE CITY TREE DRIP LINE AREA (THE AREA
FROM THE TRUNK OF A TREE TO THE OUTERMOST EDGE OF THE TREE CANOPY
PROJECTION ON THE GROUND). IF A CITY TREE IS NOT CLEARLY LABELED TO BE
REMOVED, IT MUST BE PROTECTED IN PLACE. EVEN IF APPROVED IMPROVEMENTS ARE IN
CONFLICT WITH A CITY TREE, IT MUST NOT BE DISTURBED UNLESS THE PLAN IS REVISED
TO ADDRESS THE TREE REMOVAL.
36. THE TRAFFIC LOOPS SHALL BE REPLACED WITHIN 3 DAYS OF COMPLETING WORK IN THE
AREA TO CURRENT CALTRANS STANDARD TO DETECT BICYCLES PER TRAFFIC OPERATIONS
POLICY DIRECTIVE 09 -06 AT NO COST TO THE CITY.
EROSION CO L:
1. IN CASE EMERGENCY WORK IS REQUIRED, CONTACT SEAN SANTA CRUZ AT
858) 481 -3310 24 HOURS A DAY.
2. EQUIPMENT AND WORKERS FOR EMERGENCY WORK SHALL BE MADE AVAILABLE AT ALL
TIMES DURING THE RAINY SEASON (OCTOBER 1 TO APRIL 15). ALL NECESSARY MATERIALS
SHALL BE STOCKPILED ON SITE ON OCTOBER 1 AT CONVENIENT LOCATONS TO FACILITATE
RAPID CONSTRUCTION OF TEMPORARY EROSION CONTROL MEASURES WHEN RAIN IS
IMMINENT.
3. DEVICES SHOWN ON PLANS SHALL NOT BE MOVED OR MODIFIED WITHOUT THE APPROVAL
OF THE ENGINEERING INSPECTOR.
4. THE CONTRACTOR SHALL RESTORE ALL EROSION CONTROL DEVICES TO WORKING ORDER TO
THE SATISFACTION OF THE CITY ENGINEER AFTER EACH RUN -OFF PRODUCING RAINFALL.
5. THE CONTRACTOR SHALL INSTALL ADDITIONAL EROSION CONTROL MEASURES AS MAY BE
REQUIRED BY THE CITY ENGINEER DUE TO AN INCOMPLETE GRADING OPERATION OR
UNFORESEEN CIRCUMSTANCES WHICH MAY ARISE.
6. THE CONTRACTOR SHALL BE RESPONSIBLE AND SHALL TAKE NECESSARY PRECAUTIONS TO
PREVENT PUBLIC TRESPASS ONTO AREAS THAT ARE UNSAFE OR ARE POTENTIALLY UNSAFE.
7. ALL EROSION CONTROL MEASURES PROVIDED PER THE APPROVED IMPROVEMENT PLAN
SHALL BE INCORPORATED HEREON.
8. GRADED AREAS AROUND THE PROJECT PERIMETER MUST DRAIN AWAY FROM THE FACE OF
SLOPE AT THE CONCLUSION OF EACH WORK DAY.
9. ALL REMOVABLE PROTECTIVE DEVICES SHOWN SHALL BE IN PLACE AT THE END OF EACH
WORKING DAY WHEN THE FIVE (5) DAY RAIN PROBABILITY FORECAST EXCEEDS FORTY
PERCENT (40%). SILT AND OTHER DEBRIS SHALL BE REMOVED AFTER EACH RAINFALL.
TIFICATIONS:
1. THE EXISTENCE AND LOCATION OF UNDERGROUND UTILITY PIPES AND STRUCTURES SHOWN
ON THESE PLANS WERE OBTAINED BY A SEARCH OF AVAILABLE RECORDS. TO THE BEST OF
OUR KNOWLEDGE THERE ARE N 0 EXISTING UTILITIES EXCEPT AS SHOWN ON THESE PLANS
HOWEVER: THE CONTRACTOR IS REQUIRED TO TAKE DUE PRECAUTIONARY MEASURES TO
PROTECT ANY EXISTING UTILITIES OR STRUCTURES LOCATED AT THE WORK SITE. IT IS
THE CONTRACTOR'S RESPONSIBILITY TO CONTACT THE FOLLOWING OWNERS OF SAID
UTILITIES OR STRUCTURES PRIOR TO ANY EXCAVATION, FOR VERIFICATION AND LOCATION
OF UTILITIES AND NOTIFICATION OF COMMENCEMENT OF WORK:
A. SEWERS - LWD - (760)- 753 -0155
B. GAS & ELECTRIC - SDGE - (760)-438-6200
C. WATER - SAN DIEGUITO WATER DISTRICT- 1- 800 - 227 -2600
D. TELEPHONE - SBC BELL - (760)- 489 -3411
E. CABLE TV - COX COMMUNICA7IONS- (760)- 806 -9809 X -2233
2. CONTRACTOR SHALL NOTIFY THE CITY ENGINEER'S OFFICE 48 HOURS PRIOR TO BEGINNING
ANY WORK ON THIS PROJECT. PHONE: 760) -633 -2770.
3. THE CONTRACTOR SHALL GIVE 24 HOURS NOTICE ON CALLS FOR INSPECTION. PHONE:
(760)633 -2770. ALL WORK PERFORMED WITHOUT BENEFIT OF INSPECTION WILL BE SUBJECT
TO REJECTION AND REMOVAL.
DESCRIPTION I APPROVED I DATE I BENCHMARK
C% n ► i t% - t -10. I DESCRIPTION-- FNC 10 54 750 M
SIDEWALK SE QUADRANT LEUCADIA BLVD
LOCATION: 37' EASTERLY OF TRAFFIC SIGNAL
RECORD FROM. RECORD OF SURVEY NO.
18416
ELEVA77ON: 178.543'
DATUM: NAVD88
LE %)LA'p,A MI4KiEWCZ )6dW1 hlXW&j
vo of 9-2�
r2 5. W� SCI, ?Ir TLC 'DA TC
Y _'-;•
• • 1 *
CONCRETE WASHOUT
CONTRACTOR SHALL ESTABLISH AND USE AN ADEQUATELY SIZED CONCRETE
WASHOUT AREA TO CONTAIN WASHOUT WASTES ON SITE. IT IS ILLEGAL TO WASH CONCRETE, SLURRY, MORTAR,
STUCCO, PLASTER AND THE LIKE INTO THE STORMWATER CONVEYANCE SYSTEM OR ANY RECEIVING WATER.
CONTRACTOR SHALL POST A SIGN DESIGNATING THE WASHOUT LOCA770N.
CONSTRUCTION SITE ACCESS
A STABILIZED CONSTRUCTION SITE ACCESS SHALL BE PROVIDED FOR VEHICLES EGRESS AND INGRESS TO PREVENT
TRACKING DIRT OFF SITE. THIS SHALL INCLUDE USING MATERIAL SUCH AS 3° CRUSHED ROCK AND /OR
CORRUGATED STEEL PANELS/PLATES,
CONSTRUCTION VEHICLES
A SPECIFIC AREA AWAY FROM GUTTERS AND STORM DRAW SHALL BE DESIGNATED FOR CONSTRUCTION VEHICLES
PARKING, VEHICLE REFUELING, AND ROU77NE EQUIPMENT MAINTENANCE. ALL MAJOR REPAIRS SHALL BE MADE
OFF -SITE.
EROSION CONTROL
EROSION CONTROL MUST BE PROVIDED FOR ALL EROSIVE SURFACES. SLOPED SURFACES ESPECIALLY SHALL BE
PROTECTED AGAINST EROSION BY INSTALLING EROSION RESISTANT SURFACES SUCH AS EROSION CONTROL MATS,
ADEQUATE GROUND COVER VEGETATION, AND BONDED FIBER MATRIX.
NO EXCAVATION AND GRADING ACTIVITIES ARE ALLOWED DURING WET WEATHER.
DIVERSION DIKES SHALL BE CONSTRUCTED TO CHANNEL RUNOFF AROUND THE CONSTRUCTION SITE. CONTRACTOR
SHALL PROTECT CHANNELS AGAINST EROSION USING PERMANENT AND TEMPORARY EROSION CONTROL MEASURES.
REMOVE EXISTING VEGETATION ONLY WHEN ABSOLUTELY NECESSARY. LARGE PROJECTS SHALL BE CONDUCTED IN
PHASES TO AVOID UNNECESSARY REMOVAL OF THE NATURAL GROUND COVER. DO NOT REMOVE TREES OR SHRUBS
UNNECESSARILY,° THEY HELP DECREASE EROSION.
TEMPORARY VEGETATION MUST BE PLANTED ON SLOPES OR WHERE CONSTRUCTON IS NOT IMMEDIATELY PLANNED
FOR EROSION CONTROL PURPOSES. EROSION SHALL BE PREVENTED BY PLANTING FAST - GROWING ANNUAL AND
PERENNIAL GRASSES TO SHIELD AND BIND THE SOIL.
PLANT PERMANENT VEGETATION AS SOON AS POSSIBLE, ONCE EXCAVATION AND GRADING ACTIVITIES ARE
COMPLETE.
WATER USAGE FOR DUST CONTROL SHALL BE MINIMIZED.
ON -SITE CONSTRUCTION MATERIAL STORAGE
STORED MATERIALS SHALL BE CONTAINED IN A SECURE PLACE TO PREVENT SEEPAGE AND SPILLAGE. CONTRACTOR
SHALL STORE THESE PRODUCTS WHERE THEY WILL STAY DRY OUT OF THE RAIN. CONTRACTOR SHALL PROVIDE
SECONDARY CONTAINMENT FOR ALL FUEL STORED ON -SITE. ELIMINATE OR REDUCE POLLUTION OF STORMWATER
FROM STOCKPILES KEPT ON -SITE. STOCKPILES MAY INCLUDE SOIL, PARING MATERIALS, ASPHALT CONCRETE,
AGGREGATE BASE, ETC. STOCKPILES SHALL BE LOCATED AWAY FROM CONCENTRATED STORMINATER STORMINATER
FLOWS AND STORM DRAIN INLETS. STOCKPILES SHALL BE COVERED OR PROTECTED WITH SOIL STABILIZATION
MEASURES AND PROVIDED WITH A TEMPORARY SEDIMENT BARRIER AROUND THE PERIMETER AT ALL 77MES.
TRAINING
CONTRACTORS' EMPLOYEES WHO PERFORM CONSTRUCTION IN THE CITY OF ENCINITAS SHALL BE TRAINED TO BE
FAMILIAR WITH THE CITY OF ENCINITAS STORMWATER POLLU7ION CONTROL REQUIREMENTS. THESE BMP NOTES
SHALL BE AVAILABLE TO EVERYONE WORKING ON SITE. THE PROPERTY OWNER(S) AND THE PRIME CONTRACTOR
MUST INFORM SUBCONTRACTORS ABOUT STORMWATER REQUIREMENTS AND THEIR OWN RESPONSIBILITIES.
WASTE MANAGEMENT
CONTRACTOR SHALL BE RESPONSIBLE FOR PROPERLY DISPOSING OF ALL WASTE AND UNUSED CONSTRUCTION
MATERIALS. DUMPING OF UNUSED OR WASTE PRODUCTS ON THE GROUND, WHERE WATER CAN CARRY THEM INTO
THE CONVEYANCE SYSTEM IS STRICTLY PROHIBITED.
NO SEEPAGE FROM ANY DUMPSTER SHALL BE DISCHARGED INTO STORMWATER. BERMS/DIKES SHALL BE PLACED
AROUND ALL DUMPSTERS TO DIVERT THE NATURAL STORM RUNOFF. DUMPSITES SHALL BE CHECKED FREQUENTLY
FOR LEAKS. DUMPSTER LIDS SHALL REMAIN CLOSED AT ALL TIMES. DUMPSTERS WITHOUT LIDS SHALL BE PLACED
WITHIN STRUCTURES WITH IMPERVIOUS ROOFING OR COVERED WITH TARPS IN ORDER TO AVOID RAIN CONTACT WITH
ANY TRASH MATERIAL.
MANY CONSTRUCTION MATERIALS, INCLUDING SOLVENTS, WATER -BASED PAINTS, VEHICLE FLUIDS, BROKEN ASPHALT
AND CONCRETE, WOOD, AND CLEARED VEGETATION CAN BE RECYCLED. NON - RECYCLABLE MATERIALS MUST BE
TAKEN TO AN APPROPRIATE LANDFILL OR DISPOSED OF AS HAZARDOUS WASTE. FOR INFORMATION ON DISPOSAL
OF HAZARDOUS MATERIAL, CALL THE HAZARDOUS WASTE HOTLINE TOLL FREE AT (800) 714 -1195. FOR
INFORMATION ON LANDFILLS AND TO ORDER DUMPSTERS CALL EDCO AT (760) 436 -4151.
POLLUTANTS SHALL BE KEPT OFF EXPOSED SURFACES. PLACE TRASH CANS AND RECYCLING RECEPTACLES
AROUND THE SITE.
PORTABLE TOILETS MUST BE IN GOOD WORKING ORDER AND CHECKED FREQUENTLY FOR LEAKS. CONTRACTOR
SHALL PROVIDE SECONDARY CONTAINMENT AND LOCATE PORTABLE TOILETS AWAY FROM STORMDRAIN INLETS ON
PERVIOUS SURFACES.
ALL CONSTRUCTION DEBRIS SHALL BE KEPT AWAY FROM THE STREET, GUTTER, AND STORMDRAIN. CONTRACTOR
MUST ROUTINELY CHECK AND CLEAN UP MATERIAL THAT MAY HAVE TRAVELED AWAY FROM CONSTRUCTION SITE
FOR MORE INFORMA77ON ON STORMWATER POLLUTION CONTROL MEASURES AND REQUIREMENTS PLEASE CONTACT
THE ENGINEERING DEPARTMENT, CITY OF ENCINITAS AT (760) 633 -2770.
•���ilR
IMPERVIOUS AREA PRIOR TO CONSTRUCTION: 356 SQFT
IMPERVIOUS AREA AFTER CONSTRUCTION: 346 SQFT
DECREASE IN IMPERVIOUS AREA: SQFT
IMPERVIOUS AREA REPLACED: SQFT
TOTAL AREA OF LAND DISTURBANCE= 1.195 SQFT
SHEETINDEX
SHEET DESCRIPTION
1 TITLE SHEET
2 NOTES & DETAILS
3 IMPROVEMENT PLAN
URANIA 4, LLC
740 LOMAS SANTA FE DRIVE, SUITE 204
SOLANA BEACH, CA 92075
858 -481 -3310
SITE ADDRESS
964 URANIA AVE
ENCINITAS, CA 92024
APN: 254 - 363 -10 & 13
LOT 31, HILLSIDE ACRES, ACCORDING TO MAP
THEREOF NO. 1992, FILED IN THE OFFICE OF
THE COUNTY RECORDER OF SAN DIEGO
COUNTY JANUARY 25, 1922 EXCEPTING THE
SOUTHERLY 152 FEET OF THE EASTERLY 140
FEET THEREOF.
TOFVGRAPW
PASCO LARET SUITER & ASSOCIATES
PH 619 - 259 -8212
DATE OF SURVEY.° SEPTEMBER 15, 2015
NTS
OWNER'S CERTIFICATE
I (WE) HEREBY CERTIFY THAT A REGISTERED SOILS ENGINEER OR GEOLOGIST HAS BEEN OR WILL BE RETAINED TO
SUPERVISE OVER ALL GRADING ACTIVITY AND ADVISE ON THE COMPACTION AND STABILITY OF THE SITE.
I (WE) HEREBY AGREE TO INDEMNIFY, DEFEND, AND HOLD CITY AND CITY'S OFFICERS, OFFICIALS, EMPLOYEES, AND
AGENTS HARMLESS FROM, AND AGAINST ANY AND ALL LIABILITIES, CLAIMS, DEMANDS, CAUSES OF ACTIONS,
LOSSES, DAMAGES AND COSTS, INCLUDING ALL COSTS OF DEFENSE THEREOF, ARISING OUT OF OR IN ANY
MANNER CONNECTED DIRECTLY OR INDIRECTLY WITH ANY ACTS OR OMISSIONS OF OWNER OR OWNER'S AGENTS,
EMPLOYEES, CONTRACTORS, SUBCONTRACTORS, OFFICIALS, OFFICERS, OR REPRESENTATIVES FOR ANY AND ALL
WORK OR CONSTRUCTION COVERED IN THE PERMIT OR CONNECTED DIRECTLY OR INDIRECTLY TO THE PERMIT OR
APPROVED PLANS MOTH THE PRI ATE PROPERTY OR PUBLIC EASEMENTS.
SIGNATURE: / DATE: l LS ZO!
CHRISTOPHER R. HALL
URANIA 4, LLC
i, TREVOR E. MYERS A REGISTERED CIVIL ENGINEER IN THE STATE OF CALIFORNIA, PRINCIPALLY
DOING BUSINESS IN THE FIELD OF APPLIED SOIL MECHANICS, HEREBY CERTIFY THAT A SAMPLING AND STUDY OF
THE SOIL CONDITIONS PREVALENT WITHIN THIS SITE WAS MADE BY ME OR UNDER MY DIRECTION ON 1 -18 -2016
AND FOR AN UPDATE ON 10 -6 -2016. ONE COMPLETE COPY OF 7HE SOILS REPORT COMPILED FROM THIS
STUDY, WITH MY RECOMMENDATIONS, HAS BEEN SUBMITTED TO THE OFFICE OF THE CITY ENGINEER.
FURTHERMORE, I HAVE REVIEWED THESE GRADING PLANS AND CER77FY THAT THE RECOMMENDATIONS INCLUDED
IN THE SOILS REPORT FOR THIS PROJECT HAVE BEEN INCORPORATED IN THE GRADING PLANS AND
SPECIFICATIONS. _- i At
SIGNED: r iS l�� �^� �pFESS /0
TREVOR E MYERS7 m �--\ N,
RCE NO.: 663 Z,3
c�
EXP. DATE: No. RCE63773 09 3018 �
JOB #. G1942 -32 -01 sr1 Olw_
GEOCON INCORPORATED, INC. ALt
6960 FLANDERS DRIVE
SAN DIEGO, CA 92121
PHONE: (858) - 558 -2974
ai Z/ • • •
THE UNDERSIGNED ENGINEER AGREES THAT THE WORK PERFORMED BY THE ENGINEER SHALL COMPLY WITH
THE GENERALLY ACCEPTED STANDARD5S AND PRACTICES OF THE ENGINEER'S TRADE OR PROFESSION. THE
ENGINEER FURTHER AGREES THAT THE WORK PERFORMED HEREIN SHALL BE IN ACCORDANCE WITH THE
RULES AND REGULATIONS REQUIRED BY THE CITY OF ENCINITAS, TO THE EXTENT THAT THE ENGINEER
CONTROLS SUCH PERFORMANCE. THE ENGINEER AGREES THAT ANY PLANCHECK OR REVIEW PERFORMED BY
THE CITY OF ENCINITAS IN ITS CAPACITY AS A PUBLIC ENTITY FOR THE PLANS PREPARED BY THE ENGINEER
IS NOT A DETERMINATION BY THE CITY OF ENCINITAS OF THE TECHNICAL SUFFICIENCY OR ADEQUACY OF THE
PLANS OR DESIGN AND IT THEREFORE DOES NOT RELIEVE THE ENGINEER OF RESPONSIBILITY FOR THE PLANS
OR DESIGN OF IMPROVEMENTS BASED THEREON. THE ENGINEER AGREES TO INDEMNIFY AND HOLD HARMLESS
THE CITY OF ENCINITAS AND ITS OFFICERS, AGENTS, AND EMPLOYEES FROM PROPERTY DAMAGE OR BODILY
INJURY ARISING SOLELY FROM THE NEGLIGENT ACTS, ERRORS, OR OMISSIONS OF THE ENGINEER AND
HIS/HER AGENTS OR EMPLOYEES ACTING WITHIN THE COURSE AND SCOPE OF SUCH AGENCY AND
EMPLOYMENT AND ARISING OUT OF THE WORK PERFORMED BY THE ENGINEER.
QRof ESSipy
AEL qP!
SIGNATURE: DATE: 7.1.19 `�� moo` <�
BRIAN M. A OLI RCE No. 71651
n z m
PASCO LARET SUITER & ASSOCIATES Exp. o12 /31/19 0
535 N. COAST HIGHWAY 101
SOLANA BEACH CA, 92074
RCE EXPIRES 12 -31 ®19 STgT� FIC iF���P
M06cr 5'rATU5 : PDP
ii9li[iiiiiiiiii1l It It �
PLANNING DIVISION PARKS AND RECREATION
DA It
`,`
DATE
INT.
DATE
I PLANS PREPARED UNDEF
PUBLIC WORKS
DA TE
SIGN
PLANNING
DATE SIGN
DATE
SIGN t DATE
DA It
`,`
DATE
INT.
DATE
I PLANS PREPARED UNDEF
PUBLIC WORKS
/vA
---
PLANNING
'rlh
110
REVIEWER
L
S�
BRIAN M. ARD NO
INSPECTOR
_
loll I I
DATE. SUPERVISION OF RECOMMENDED: APPROVED:
JAI 641�yt/.
dPM#tDOSKU
►• TE DA TE
- : \ .X
URANIA ,
. -
SIGN DATE
-.-
DRAWING NO.
13499 -1
PLSA 2451
a
U
0
¢o�
cov
or 3`71
2Q
�zC)
to
¢om
QZQ
a��
LWD SEWER NOTES
1. LWD APPROVAL OF THESE PLANS DOES NOT RELIEVE THE APPLICANT, PRIVATE ENGINEER OF WORK,
OR CONTRACTOR FROM RESPONSIBILITY FOR THE CORRECTION OF ERRORS AND OMISSIONS
DISCOVERED DURING OR AFTER CONSTRUCTION.
2. ALL DESIGN, MATERIALS, AND CONSTRUCTION WORK SHALL CONFORM TO THE LEUCADIA
WASTEWATER DISTRICT LWD SEWER STANDARDS AND TO THE REQUIREMENTS OF THE STANDARD
SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION (GR .. BOO AND THE REGIONAL STANDARD
DRAWINGS. MOST CURRENT EDITIONS. IN THE EVENT OF CONFLICT THE LWD SEWER STANDARDS
3. OSHA SAFETY ORDERS AND OSHA CONFINED SPACE ENTRY REQUIREMENTS SHALL BE FOLLOWED AT
ALL TIMES WITHOUT EXCEPTION.
4. THE CONTRACTOR SHALL HAVE A COPY OF THE SEWER NOTES 2. & 3. DOCUMENTS ON THE JOB
SITE AT ALL TIMES.
5. THE CONTRACTOR SHALL GUARANTEE ALL WORK FOR A PERIOD OF ONE YEAR AFTER THE DATE OF
FINAL ACCEPTANCE BY LWD AND SHALL REPAIR OR REPLACE ANY WORK THAT MAY PROVE
DEFECTIVE IN WORKMANSHIP AND /OR MATERIALS WITHIN THE ONE YEAR PERIOD WITHOUT EXPENSE
WHATSOEVER TO LWD.
6. QUANTITIES SHOWN HEREON ARE FOR BOND ESTIMATE PURPOSES ONLY NEITHER THE PRIVATE
ENGINEER NOT LWD GUARANTEE THE ACCURACY OR COMPLETENESS OF THE SEWER QUANTITIES.
7 PRIOR TO CONSTRUCTION, THE CONTRACTOR SHALL SUBMIT SHOP DRAWINGS REPRESENTING ALL
MATERIALS AND SUPPLIES SATISFACTORY TO LWD. WORK SHALL NOT COMMENCE UNTIL SUCH
MATERIALS ARE APPROVED BY LWD.
8. PRIOR TO BEGINNING SEWER WORK, THE LWD INSPECTOR SHALL BE FURNISHED THREE SETS OF CUT
SHEETS AND SHALL COMPLY WITH LWD STANDARD SPEC SURVEY REQUIREMENTS.
9. PRIOR TO BEGINNING SEWER WORK, THE CONTRACTOR SHALL SECURE A LWD PERMIT FOR
CONSTRUCTION AND SHALL PROVIDE A MINIMUM OF 72 HOURS NOTICE TO LWD PRIOR TO
CONSTRUCTION.
10. NO WORK SHALL BE COMMENCED UNTIL ALL PERMITS HAVE BEEN OBTAINED FROM THE
JURISDICTIONAL CITY, COUNTY, AND /OR OTHER APPROPRIATE AGENCIES.
11. THE CONTRACTOR SHALL CONFORM TO LABOR CODE SECTION 6705 BY SUBMITTING A DETAIL PLAN
TO THE DISTRICT ENGINEER SHOWING THE DESIGN OF SHORING, BRACING, SLOPING, OR OTHER
PROVISIONS TO BE MADE FOR PROTECTION OF WORKERS FROM THE HAZARD OF CAVING GROUND
DURING TRENCH EXCAVATION AND PIPE INSTALLATION THEREIN. THIS PLAN MUST BE PREPARED FOR
ALL TRENCHES FIVE FEET OR MORE IN DEPTH. IF THE PLAN VARIES FROM THE SHORING SYSTEM
STANDARDS ESTABLISHED BY THE CONSTRUCTION SAFETY ORDERS, TITLE 8, CALIFORNIA
ADMINISTRATIVE CODE, THE PLAN SHALL BE PREPARED BY A REGISTERED ENGINEER. A COPY OF
THE OSHA EXCAVATION PERMIT MUST BE SUBMITTED TO THE LWD INSPECTOR PRIOR TO
EXCAVATION.
12. ALL SEWER FACILITIES SHALL BE INSTALLED IN DRY EXCAVATIONS AND TRENCHES. CONTRACTOR
SHALL DEWATER AND MAINTAIN DEWATERING CONTINUOUSLY UNTIL THE WORK IS COMPLETED
INCLUDING PLACEMENT AND COMPACTION OF BACKFILL MATERIALS IN A DRY STATE. ALL PIPE ZONE
MATERIAL LOCATED IN WET OR AREAS SUSPECTED TO BE WET IN THE FUTURE SHALL BE ENCASED
IN GEOTEXTILE MATERIAL. SUITABLE GEOTEXTILE MATERIAL SHALL BE SUBMITTED TO THE DISTRICT
ENGINEER FOR REVIEW AND APPROVAL. CONTRACTOR SHALL OBTAIN DEWATERING PERMITS AS
NECESSARY AND RETURN OF GROUNDWATER TO THE SEWER SHALL NOT BE ALLOWED.
13. THE EXISTENCE AND LOCATION OF UNDERGROUND UTILITIES SHOWN ON THESE PLANS WAS
OBTAINED BY AVAILABLE RECORDS SEARCH BY THE PRIVATE ENGINEER. TO THE BEST OF THE
PRIVATE ENGINEER'S KNOWLEDGE, THERE ARE NO EXIS77NG UTILITIES EXCEPT THOSE SHOWN ON
THESE PLANS. ATTENTION IS CALLED TO THE POSSIBLE EXISTENCE OF OTHER UTILITIES OR
STRUCTURES NOT SHOWN, OR IN A DIFFERENT LOCATION FROM THAT SHOWN ON THE PLANS. THE
CONTRACTOR SHALL TAKE DUE PRECAUTIONARY MEASURES TO PROTECT THE UTILITIES SHOWN ON
THE PLANS AND OTHER EXISTING FACILITIES OR STRUCTURES NOT SHOWN.
14. APPROVAL OF THIS PLAN BY LWD DOES NOT CONSTITUTE A REPRESENTATION OF THE ACCURACY
OF THE LOCATION OF, OR THE EXISTENCE OR NONEXISTENCE OF, ANY UNDERGROUND UTILITY, PIPE,
OR STRUCTURE WITHIN THE LIMITS OF THIS PROJECT.
15. CONTRACTOR SHALL NOTIFY UNDERGROUND SERVICE ALERT (800) 422 -4133, AS REQUIRED BY
STATE LAW. ALL UTILITY CROSSINGS SHALL BE POT HOLED PRIOR TO TRENCHING.
16. CONTRACTOR IS RESPONSIBLE FOR COMPLYING WITH ALL LOCAL, STATE, AND FEDERAL SAFETY
REGULATIONS INCLUDING, BUT NOT LIMITED TO, TRENCH SAFETY AND CONFINED SPACE ENTRY.
17. SOILS REPORTS SHALL BE SUBMITTED TO LWD BY A QUALIFIED SOILS ENGINEER WHICH CERTIFIES
THAT TRENCH BACKFILL WAS COMPACTED AS DIRECTED BY THE SOILS ENGINEER IN ACCORDANCE
WITH ON SITE EARTHWORK SPECIFICATIONS AND THE LWD STANDARD SPEC.
18. SEWER ELEVATIONS SHOWN ARE INVERT ELEVATION (I.E.), INSIDE BOTTOM OF PIPE. SEWER LENGTHS
SHOWN ARE FROM CENTER OF MANHOLE TO CENTER OF MANHOLE.
19. ALL REVISIONS TO DRAWINGS SHALL BE APPROVED BY THE LWD DISTRICT ENGINEER AS
CONSTRUCTION CHANGES TO THE ORIGINAL MYLAR DINGS. WITH INITIALED APPROVAL ON THE
MYLARS.
20. CONTRACTOR IS RESPONSIBLE FOR KEEPING COMPLETE RECORD OF CHANGES AND SHALL MAKE
SUCH RECORD AVAILABLE TO THE PRIVATE ENGINEER. THE PRIVATE ENGINEER SHALL PROVIDE
AS -BUILT DRAWINGS TO LWD FOR REVIEW AND APPROVAL PRIOR TO FINAL ACCEPTANCE OF THE
PROJECT.
21. LENGTH OF OPEN TRENCH SHALL BE LIMITED TO 350 FEET, INCLUDING COLLECTORS AND LATERALS,
UNLESS OTHERWISE APPROVED IN WRITING BY THE DISTRICT TRENCH SHALL BE BACKFILLED OR
PLATED AT THE CONCLUSION OF EACH DAY OF WORK,
22. THE CONTRACTOR SHALL PROTECT ALL SURVEY MONUMENTA770N. IF ANY SURVEY MONUMENTS ARE
DISTURBED OR DESTROYED, THE CONTRACTOR SHALL RETAIN A LICENSED SURVEYOR TO
REESTABLISH AND RECORD THE MONUMENT CHANGE PER STATE LAW.
23. A MINIMUM OF 12 INCHES VERTICAL CLEARANCE SHALL BE PROVIDED BETWEEN THE SEWER PIPE
AND ANY OTHER UTILITIES.
24. SEPARATION OF SEWER / WATER AND SEWER / RECLAIMED WATER SHALL COMPLY WITH LWD STD
DWG S -2 AND WITH ALL COUNTY AND STATE HEALTH DEPT REGULA77ONS
25. CONNECTIONS TO EXIS77NG SEWER PIPE OR MANHOLES SHALL ONLY BE DONE IN THE DIRECT
PRESENCE OF THE LWD INSPECTOR. NEW SEWER SHALL NOT BE CONNECTED OR ALLOWED TO FLOW
TO EXISTING SEWER UNTIL AFTER FINAL ACCEPTANCE OF ALL UPSTREAM WORK BY THE LWD
INSPECTOR, OR AS APPROVED BY DISTRICT ENGINEER.
26. ALL SERVICE LATERALS SHALL BE LOCATED AT RIGHT ANGLES TO THE SEWER MAIN UNLESS
OTHERWISE SHOWN AS APPROVED BY LWD ON THE PLANS.
27 A 2 -INCH HIGH "S" SHALL BE INSCRIBED ON THE CURB FACE AT EACH LATERAL LOCATION BY THE
CONTRACTOR.
28. A 10 GAGE SHIELDED COPPER WIRE SHALL BE BURIED OVER EACH LATERAL. THE WIRE SHALL
EXTEND UP TO A 2" COPPER TAG TIED AND SOLDERED TO THE WIRE. THE TAG OVER THE SEWER
MAIN SHALL TERMINATE 6" ABOVE PAVING SUBGRADE WITH FINAL LOCATION JUST BELOW PAVING.
THE TAG OVER THE CUSTOMER END OF THE LATERAL SHALL EXTEND ABOVE GRADE UNTIL
CONNECTED AND SHALL THEREAFTER BE BURIED AT THE POINT OF CONNECTION.
29. ALL PIPE SHALL BE HANDLED AND INSTALLED SO AS TO PROTECT PIPE, JOINTS, LINING, AND
COATING. THE PIPE SHALL BE CAREFULLY BEDDED TO PROVIDE CONTINUOUS BEARING AND PREVENT
UNEVEN SETTLEMENT PIPE SHALL BE PROTECTED AGAINST FLOTATION AT ALL TIMES. OPEN ENDS
OF PIPE SHALL BE SEALED AT ALL TIMES WHEN CONSTRUCTION IS NOT IN PROGRESS.
30. PIPE JOINTS SHALL NOT BE DEFLECTED UNLESS SO DESIGNED AND SHALL THEN BE LIMITED TO
LESS THAN ONE -HALF OF THE ANGLE RECOMMENDED BY THE PIPE MANUFACTURER.
31. SEWER PIPE ZONE AND TRENCH BACKFILL SHALL BE PER THE LWD SEWER STANDARDS. WATER
JETTING SHALL NOT BE ALLOWED.
LWD SEWER NOTES
32. ALL LATERALS SHALL BE CONSTRUCTED CLEAR OF DRIVEWAYS.
33. JOB MIXING OF CONCRETE IS NOT ALLOWED WITHOUT EXCEPTION. CONCRETE TESTING BY LWD WILL BE
AT CONTRACTOR EXPENSE.
34. MANHOLE BASES SHALL BE MONOLITHICALLY PLACED, FINISHED, AND COMPLETED AT TIME OF
PLACEMENT. GPK PRODUCTS, INC., OR APPROVED EQUAL, MANHOLE ADAPTERS SHALL BE SET IN THE
BASE FOR EACH PIPE CONNECTION. SETTING OF MH RINGS SHALL NOT BE ALLOWED FOR 48 HOURS
AFTER CONCRETE PLACEMENT. PRECAST MANHOLE BASES ARE ACCEPTABLE FOR USE WITH 8" SEWERS
WITH DISTRICT ENGINEER APPROVAL.
35. JOINTS BETWEEN MH BASE, SHAFTING, CONE SECTIONS, AND RING SHALL HAVE A 2" BY 2" BUTYL
RUBBER GASKET PLACED WITHIN THE FULL CIRCUMFERENCE. GASKET SHALL BE CPS -210 BY
PRESS -SEAL GASKET CORP., OR APPROVED EQUAL.
36. ALL MANHOLES SHALL BE VACUUM TESTED 1) BEFORE BACKFILL, 2) AFTER BACKFILL, AND 3)
SUBSEQUENT TO ANY SUSPECTED MOVEMENT OR DAMAGE AFTER BACKFILL.
37. ALL SEWERS AND LATERALS SHALL BE WAYNE BALLED OR JETTED, LOW PRESSURE AIR TESTED, AND
TELEVISED AT THE APPLICANT /CONTRACTORS EXPENSE PRIOR TO CONSIDERATION FOR FINAL
ACCEPTANCE BY LWD. AIR TEST SHALL BE DONE AFTER CONSTRUCTION OF ALL OTHER UTILITIES AND
UTILITY LATERALS.
38. ALL SEWERS AND LATERALS SHALL BE IN PLACE AND SHALL HAVE FINAL APPROVAL BY THE LWD
INSPECTOR PRIOR TO PAVING.
39. MANHOLES SHALL BE 4 -FEET DIAMETER FOR PIPE UP TO 15 -INCH DIAMETER PER LWD STD DWG S -3.
MANHOLES SHALL BE 5 -FEET DIAMETER FOR PIPE 18- INCHES AND LARGER PER LWD STD DWG S -4.
40. ALL NEW MH'S SHALL BE LINED WITH AN INTEGRALLY LOCKING PVC (T -LOCK) PROTECTIVE LINING
SYSTEM. ALL EXISTING MH'S WITH MODIFICATIONS SHALL BE PROVIDED WITH URETHANE OR EPDXY LINING
SYSTEM. LINING SYSTEM TO MATCH EXISTING LINING, IF ANY. T -LOCK, URETHANE, AND EPDXY LINING
SYSTEMS SHALL BE PER SECT 500 -2 OF THE GREENBOOK.
41. MAXIMUM DEPTH OF SEWER FOR SDR35 PVC PIPE IS 15'. C900 PIPE IS REQUIRED FOR DEPTH OF COVER
OVER 15'.
42. FINAL APPROVAL OF PLANS BY DISTRICT ENGINEER IS VALID FOR A PERIOD OF TIME NOT TO EXCEED
ONE YEAR FROM APPROVAL DATE TO START OF CONSTRUCTION. IF THE ONE YEAR TIME LIMIT IS
EXPIRED PRIOR TO START OF CONSTRUCTION THE DEVELOPER SHALL RESUBMIT THE PLAN CHECK TO
THE DISTRICT ENGINEER FOR AN UPDATED REVIEW AND APPROVAL. ANY CHANGES REQUIRED TO THE
PLANS SHALL BE MADE AT THE DEVELOPERS EXPENSE AND APPROVED BY THE LWD DISTRICT ENGINEER
PRIOR TO THE START OF CONSTRUCTION.
43. WHEN CONNECTION TO EXISTING MANHOLES IS NECESSARY AND SHOWN ON THE DRAWINGS, THE
CONTRACTOR SHALL CONNECT TO EXIS77NG MANHOLE STRUCTURES AND CONSTRUCT THE NEW
FLOW - THROUGH CHANNELS IN EACH MANHOLE BASE TO ACCOMMODATE THE NEW SEWER LINES AS
REQUIRED. SMOOTH TRANSITIONS SHALL BE INSTALLED FROM THE INVERTS OF NEWLY INSTALLED PIPES
TO THE EXIS77NG MANHOLE STRUCTURES. MANHOLES SHALL BE CORE DRILLED AND MANHOLE
CONNECTION FITTINGS SHALL BE CONNECTED TO THE CORE DRILLED HOLE BY LINK -SEAL, OR APPROVED
EQUAL. THE FIRST FLEXIBLE JOINT SHALL BE LOCATED WITHIN ONE -FOOT OF THE MANHOLE BASE. JACK
HAMMERING SHALL NOT BE ALLOWED,
44. ALL NEW CONNECTIONS TO EXISTING SEWER SI4ALL BE MADE TO EXISTING WYES, MADE WITH GASKETED
PVC SADDLE WYE, OR SHALL BE MADE BY INSTALLING NEW MANUFACTURED WYES. FOR INSTALLING NEW
MANUFACTURED WYES, STANDARD BELL AND SPIGOT OR PLAIN END WYES AND PLAIN END PIPE SPOOLS
MATCHING 774E ADJACENT EXISTING PIPE MAY BE USED FOR INSERTING WYES INTO AN EXISTING SEWER.
ALL CONNECTIONS NOT MADE TO EXISTING WYES MUST BE IN ACCORDANCE WITH LWD STANDARD
DRAWING S -32.
45. IF NECESSARY DURING THE LATERAL CONNECTION WORK, UPSTREAM FLOW IN THE EXISTING SEWER
SHALL BE TEMPORARILY PLUGGED AND BY- PASSED BY PUMPING OR PUMPER TRUCKS FOR DISPOSAL TO
A DOWNSTREAM LWD SEWER. IN LOCATIONS WITH SIGNIFICANT UPSTREAM FLOW, LWD MAY REQUIRE
TEMPORARY PROVISION OF DUTY AND BYPASS EQUIPMENT WITH FULL -71ME MANNED MONITORING. NO
UNMANNED BYPASS SHALL BE ALLOWED.
46. FOR CONNECTION OF PLAIN END TO PLAIN END PVC SEWER, REPAIR COUPLINGS SHALL BE MADE OF
PVC MATERIAL MEE77NG THE SAME MATERIAL REQUIREMENTS AS THE PIPE BEING REPAIRED. PVC SEWER
REPAIR COUPLINGS SHALL BE RUBBER GASKETED WITH NO CENTER STOP. PIPE ENDS SHALL BE
THOROUGHLY CLEANED PRIOR TO INSTALLATION OF THE REPAIR COUPLING(S). THE REPAIR COUPLING
SHALL BE SLIPPED ALL THE WAY ON TO ONE PLAIN END PIPE, THEN THE PIPE AND ADJOINING PIPES
SHALL BE ALIGNED TOGETHER AND THE REPAIR COUPLING SLIPPED BACK INTO A POSITION EQUALLY
SPACED BETWEEN THE TWO PLAIN END PIPES. PVC SEWER REPAIR COUPLINGS SHALL BE AS
MANUFACTURED BY PIN PIPE OR EQUAL APPROVED BY THE LWD DISTRICT ENGINEER.
47. PVC OR VITRIFIED CLAY PIPE (VCP) SEWER PIPE AND WYES MAY BE USED TO TIE -IN TO EXISTING VCP.
FOR CONNECTION OR REPAIR OF PLAIN END VCP TO VCP A ROMAC INDUSTRIES, INC. STYLE 501
COUPLING OR EQUAL SHALL BE USED. FOR CONNECTIONS OF VCP TO PVC, A ROMAC INDUSTRIES, INC.
STYLE RC 501 REDUCING COUPLING WITH MATCHING INVERTS, OR APPROVED EQUAL, SHALL BE USED
WITH A GASKET RANGE TO MATCH THE OUTSIDE DIAMETER OF THE PIPE ON THAT SIDE OF THE
COUPLING BEING JOINED. THE CENTER RINGS SHALL BE DUCTILE IRON PER ASTM A536, GRADE
65 -45 -12 AND SHALL BE PROVIDED WITH 16 MILS FUSION BONDED EPDXY COLOR CODED TO THE TYPE
OF CONNECTING PIPE. GASKETS SHALL BE SBR PER ASTM D2000 MBA710, COMPOUNDED FOR WATER
AND SEWER SERVICE. ALL NUTS AND BOLTS SHALL BE TYPE 316 STAINLESS STEEL.
48. FOR CONNECTION OF NEW LATERALS TO EXISTING PIPE GREATER THAN 8 -INCH DIAMETER CONTRACTOR
SHALL CUT IN A NEW WYE PER ABOVE OR MAY USE A SUITABLY SIZED ROMAC STYLE "CB" SEWER
SADDLE PER STD. DWG. S -32.
49. WHEN WORK IS CONDUCTED IN PROXIMITY TO THE LEUCADIA WASTEWATER DISTRICT SEWER SYSTEM,
CARE WILL BE TAKEN THAT NO DIRT, DEBRIS, EXCESS WATER, OR GROUNDWATER WILL ENTER THE
SYSTEM. THE CONTRACTOR WILL BE HELD LIABLE OR ANY REQUIRED CLEANING OR REPAIRS.
50. CONTRACTOR TO REVIEW CCTV OF SEWER MAIN AND CONFIRM LOCATIONS OF EXISTING LATERALS.
EXISTING LATERALS ARE TO BE SERVICED DURING CONSTRUCTION BY REDIRECTING FLOW WITH SUMPS.
THE CONTRACTOR MAY SUBMIT AN ALTERNATIVE BYPASS PLAN TO THE LWD FIELD INSPECTOR PRIOR TO
START OF WORK FOR APPROVAL BY THE DISTRICT. THE BYPASS PLAN SHALL ALSO CONSIDER THE
REQUIREMENT FOR THE NEW SEWER MAIN TO PASS AN AIR PRESSURE TEST THE CONTRACTOR WILL NOT
START WORK UNTIL THE FINAL BYPASSING PLAN IS APPROVED BY LWD AND SHALL COORDINATE WITH
NEIGHBORING HOMEOWNERS TO LIMIT DISRUPTION OF SEWER SERVICE.
PROPERTY 8.!
r LINE
4' PCC BL CK i" WATER MEIER
COVERED Sil EWALK PER WAS WS -01, WC -17 z
2'� PER SDRS G -7 %� 2%
SAN DIEGUffO WATER DISTRICT NOTES e
LEGEND
1. WATER MAINS, LATERALS AND APPURTENANCES SHALL BE CONSTRUCTED ACCORDING TO THE STANDARD
SUBDIVISION BOUNDARY - -
SPECIFICATIONS OF THE CURRENT WATER AGENCIES' STANDARDS COMMITTEE (WASC). THE CONTRACTOR
AS -BUILT APPROVALS
SHALL AND HEREBY DOES GUARANTEE ALL WORK FOR A PERIOD OF ONE YEAR AFTER THE DATE OF
EXISTING SPOT ELEVATION T,i' -' • %'
ACCEPTANCE.
EXISTING CONTOUR -- -- 1100 - -- -
2.THE CONTRACTOR SHALL NOTIFY THE DISTRICT'S INSPECTION DEPARTMENT 48 HOURS IN ADVANCE OF
LOT LINE
BEGINNING WORK TO ARRANGE FOR INSPECTION OF PROJECT THE CONTRACTOR SHALL GIVE 24 HOURS
SnA
NOTICE ON CALLS FOR INSPECTION. PHONE: (760 633 -2709. ALL WORK PREFORMED WITHOUT BENEFIT
PROPOSED ASPHALT PAVING
DESCRIPTION: ENC 1024 2.5 DISC IN
SIDEWALK SE QUADRANT LEUCADIA BLVD
LOCATION: 37' EASTERLY OF TRAFFIC SIGNAL
RECORD FROM. RECORD OF SURVEY NO,
EELLEEVAATION: 178.543'
DATUM: NAVOSS
OF INSPECTION WILL BE SUBJECT TO REJECTION AV REMOVAL.
lNT..
PROPOSED PERVIOUS PAVER
PLANS PREPARED UNDER SUPERVISION OF
DATE: 3'I'IS
R.C.E. NO.: 71651
BRIAN-0 ARDOLI
EXP.: 12 -31 -19
RECOMMENDED; APPROVED:
Cs.V1/t.-
JES E 0 EN CHRIST HER L. MA OSKU
3 �� 3 -5 ZDI
DATE DATE
3.THE CONTRACTOR WILL BE REQUIRED TO SCHEDULE A MANDATORY PRE - CONSTRUCTION CONFERENCE WITH
13499 °I
THE SAN DIEGUITO WATER DISTRICT INSPECTOR PRIOR TO COMMENCEMENT OF WORK ON WATER
PROPOSED BLACK PCC SIDEWALK
IMPROVEMENTS. PHONE: (760) 633 -2709.
4.UNLESS OTHERWISE NOTED, ALL CONNECTIONS TO EXISTING MAINS WILL BE MADE BY THE CONTRACTOR,
PROPOSED LIMIT OF GRADING y w
UNDER THE SUPERVISION OF SAW DIEGUITO WATER DISTRICT, AFTER PAYMENT OF THE ESTIMATED COST BY
PROPOSED 8" PVT SEWER S
THE DEVELOPER.
L DATE
PLANNING
PROPOSED SEWER LATERAL n
S.WHERE ELEVA110NS AND GRADES ARE NOT SHOWN ON THE WATER MAIN PROFILE, TOP OF PIPE PROFILE IS
48 INCHES BELOW CENTERLINE FINISH GRADE OF STREET.
PROPOSED WATER SERVICE w -- -�
6.ALL SERVICES TO BE CONSTRUCTED CLEAR OF DRIVEWAYS.
7. CONTRACTOR TO FURNISH ONE INCH COPPER WATER SERVICE AND METER BOX FOR EACH RESIDENTIAL
LOT.
&CONTRACTORS SHALL ACQUIRE A TRENCHING PERMIT FROM THE CALIFORNIA DIVISION OF SAFETY FOR ALL
NGINEER DATE
5
TRENCH WORK.
" LATERAL
9.INSTALL FIRE HYDRANTS 2.5 FEET FROM FACE OF CURB, IF NO SIDEWALK EXISTS, OR 7 FEET FROM FACE
INSPECTOR
OF CURB WHERE SIDEWALK EXISTS OR WILL BE CONSTRUCTED.
4„
10. PROVIDE AIR RELEASE ASSEMBLIES AT ALL HIGH POINTS IN WATER MAIN.
6-P
SEWER
11. CONTRACTOR SHALL OBTAIN AN ENCROACHMENT PERMIT FROM THE CITY OF ENCINITAS FOR ANY
MAIN \
R3"
DROP
EXCAVATION WITHIN EXISTING CITY RIGHTS -OF -WAY.
- - - - -
0 MAIN
12. THE DISTRICT REQUIRES THAT COMPACTION TESTS BE TAKEN WHERE WATER LINES ARE INSTALLED WITHIN
I
EXISTING COUNTY RIGHTS -OF -WAY, CITY OF ENCINITAS RIGHTS -OF -WAY, OR PRIVATE EASEMENTS, AND
LE~ *SEE SCHEDULE
THE RESULTS APPROVED BY THE CITY OF ENCINITAS, BEFORE THE WATER LINES ARE ACCEPTED AND A
TO DROP ON SHEET 3 OF
COPY SENT TO THE SAN DIEGUITO WATER DISTRICT OFFICE.
3 FOR DIMENSIONS.
13. PRIOR TO AWARDING WATER LINE CONTRACT, OWNER SHALL ADVISE PROSPECTIVE CONTRACTORS TO
OBTAIN AND REVIEW CURRENT WATER AGENCIES' STANDARDS COMMITTEE (WASC) SPECIFICATIONS.
^
SEWER DROP TO MAIN
14. FILL AREAS MUST BE COMPACTED TO 907., PRIOR TO PIPE INSTALLATION.
NTS
15. APPROVAL OF THIS PLAN BY SAN DIEGUITO WATER DISTRICT DOES NOT CONSTITUTE A REPRESENTATION
AS TO THE ACCURACY OF, THE LOCATION OF, OR THE EXISTENCE OR NON - EXISTENCE OF ANY
UNDERGROUND UTILITY, PIPE OR STRUCTURE WITHIN THE LIMITS OF THIS PROJECT.
16. ALL EXISTING FACIL177ES WHICH MAY EFFECT FINAL DESIGN, I.E., LINE CROSSINGS, LINE PARALLELING, OR
PROPOSED CONNECTION SHALL BE FIELD VERIFIED. ALL EXISTING OR PROPOSED UTILITY CROSSINGS WITHIN
PL
CL
10 FEET OF PROPOSED WATER MAINS SHALL BE SHOWN ON IMPROVEMENT PLANS. ELECTRICAL AND
SEWER TO CROSS UNDER WATER MAINS UNLESS GIVEN WRITTEN PERMISSION BY SAN DIEGUITO WATER
20.00' -
20.00'
DISTRICT.
14.00'
17 WATER CONNECTIONS TO COMMERCIAL DEVELOPMENTS SHALL HAVE AN APPROVED BACKFLOW DEVICE
EXISTING AC
EXISTING AC
EXISTING
PAVERS
INSTALLED TO THE DISTRICT'S SATISFACTION AND CURRENT WATER AGENCIES' STANDARDS COMMITTEE
SIDEWALK
(WASC) STANDARDS. BACKFLOW DEVICES ARE TO BE INSTALLED DIRECTLY OUTSIDE CITY OR COUNTY
VARIES
VARIES
RIGHT -OF -WAY OR OUTSIDE WATER DISTRICT EASEMENT. REPAIR, MAINTENANCE AND ANNUAL TESTING OF
-
BACKFLOW DEVICE ARE RESPONSIBILITY OF OWNER.
18. MINIMUM HORIZONTAL SEPARATION OF 10 FEET REQUIRED BETWEEN FIRE HYDRANTS AND SAN DIEGO GAS
EXISTING EXISTING
AC 0"
AND ELECTRIC VAULTS.
AC CURB
PER SD G -05, HT CURB
19. UTILITIES TO MAINTAIN MINIMUM 5 -FOOT SEPARATION WHEN PARALLELING WATER SERVICES.
URANIA AVENUE - TYPICAL SECTION
20.CONTRACTOR AND DEVELOPER ARE RESPONSIBLE TO RELOCATE ANY EXISTING WATER FACILITY (FIRE
SCALE: 1 " =10'
HYDRANT, METERS, VALVES, VALVE BOXES, ETC.) THAT ARE EFFECTED BY THEIR PROJECT.
21. CONTRACTOR TO SUPPLY DOCUMENTATION SHOWING THAT ANY ASBESTOS WATER PIPES REMOVED FROM
THE GROUND WERE DISPOSED OF IN A MANNER ACCEPTABLE TO THE SAN DIEGO COUNTY WASTE DIVISION.
22.USE THE FOLLOWING VARIOUS COMBINATIONS OF PLAIN END PIPE LENGTHS WITH HIGH DEFLECTION
COUPLINGS AND INTEGRAL BELL END PIPE FOR CURVED ALIGNMENTS IN BOTH HORIZONTAL AND VERTICAL
DIRECTIONS. DO NOT BEND PIPE BETWEEN COUPLINGS. SAW CUT INTEGRAL BELL END OF STANDARD PIPE
AND BEVEL END FOR USE WITH DEFLECTION COUPLINGS. USE 9.5 -FOOT PLAIN END PIPE LENGTHS WITH
DEFLECTION COUPLINGS FOR ALL RADII BETWEEN 140 FEET TO 270 FEET. USE 19 -FOOT PIPE LENGTHS
WITH DEFLECTION COUPLINGS FOR ALL RADII BETWEEN 270 FEET TO 560 FEET. USE AND INTEGRAL BELL
END PIPE LENGTH JOINED TOGETHER WITH A 19 -FOOT PLAIN END PIPE LENGTH TO FORM A CHORD. USE
�- CL
DEFLECTION COUPLINGS ON EACH END OF THE CHORD AND CONTINUE THIS COMBINAT70N THROUGH THE
l�L 14.00' 14.00' - -�
CURVED ALIGNMENT FOR ALL RADII BETWEEN 560 FEET TO 1,150 FEET. PIPE LENGTHS SHORTER THAN 9
I
12.00' 12.00'
FEET WILL NOT BE USED UNLESS SPECIFICALLY AUTHORIZED THE BY THE DISTRICT'S REPRESENTATIVE.
I
i
22.1. CLIFORNIA STATE LAW ASSEMBLY BILL AB -1953 IS REQUIRING THAT NO -LEAD BRASS BE USED IN
I
THE CONSTRUCTION OR REPAIR OF ALL POTABLE WATER SYSTEM EFFECT JANUARY 1, 2010. IN
I
COMPLIANCE KITH THIS LAW, THE DISTRICT SHALL REQUIRE ALL MATERIALS TO BE NO -LEAD BRASS
PARTS.
22.2. AL COPPER TUBING USED FOR AIR RELEASES, BLOW OFFS, AND SERVICES SHALL BE PROVIDED WITH
6" CURB PER PCC CURB
CATHODIC PROTECTION IN ACCORDANCE WITH WC -17 OR WC -18.
SDRSD G -1 WALL
22.3. ATER SERVICES TO BE ABANDONED THAT ARE CONNECTED TO PIPELINES THAT WILL REMAIN IN
PERVIOUS PAVER
SERVICE SHALL BE DISCONNECTED AT THE CORPORATION STOP, SHALL HAVE THE CORPORATION STOP
SECTION PER
REMOVED AND SHALL HAVE A BRASS PLUG INSTALLED; OR BE BANDONED AS DIRECTED BY THE SDWD
8" PVC
13499 -G
INSPECTOR.
PRIVATE
SEWER
ENCROACHMENT MAINTENANCE
AND REMOVAL AGREEMENT
RECORDED _MvL%AY 'S I 2018 AS
DOC NO. Zol$- ooMOa► \\ B9#B OR
EX. URANIA AVE
STREET SEC71ON
PARKING AREA (ON URANIA AV
NOT TO SCALE
PVT. DRIVEWAY - TYPICAL SECTION
PER 13499 -G SCALE. 1 " =10'
INSTALL DECORATIVE 2" BEDDING PER
PERVIOUS PAVERS Y MANUFACTURER'S SPECS
ACKERSTONE OR CI TY
APPROVED EQUIV
4" - NO. 57 STONE
OPEN GRADED BASE
C, 6" MIN THICK - NO.
2 STONE SUBBASE
SOIL SUBGRADE
DETAIL: PER VIOUS PA VER ��o�HAE('
NOT TO SCALE Q�
NOTES. `='
-ALL AGGREGATE MUST BE CLEAN/WASHED AND FREE OF FINES (SAND, SILT ETC.) w m No. 71651
-THE PAVERS SHALL NOT BE SEALED ONCE THE VOID FILLER HAS BEEN ADDED `r Exp. 12/31/19
-EACH COURSE SHALL BE VIBRATORY COMPACTED BEFORE PLACEMENT OF NEXT COURSE
-NO IMPERVIOUS LINER OR FILTER FABRIC TO BE USED `, ClV1\�
- SPECIAL APPROVAL REQUIRED FOR USE W HIGHLY EXPANSIVE SOIL - SUBDRAIN MAY qTF OF CAN-
BE REQUIRED
J
0`
CHANGE NO.1
DESCRIPTION
APPROVED
DATE
BENCHMARK
AS -BUILT APPROVALS
1 UGJIW 0T: UN±M C3 T: 1 L.P1tl F%rU WT:
ENGINEERING DIVISION APPROVALS
CITY OF ENCINITAS - DEVELOPMENT SERVICES DEPARTMENT
DRAWING NO.
1
SnA
-\Vt
DESCRIPTION: ENC 1024 2.5 DISC IN
SIDEWALK SE QUADRANT LEUCADIA BLVD
LOCATION: 37' EASTERLY OF TRAFFIC SIGNAL
RECORD FROM. RECORD OF SURVEY NO,
EELLEEVAATION: 178.543'
DATUM: NAVOSS
-L3 KS
lNT..
DATE
PLANS PREPARED UNDER SUPERVISION OF
DATE: 3'I'IS
R.C.E. NO.: 71651
BRIAN-0 ARDOLI
EXP.: 12 -31 -19
RECOMMENDED; APPROVED:
Cs.V1/t.-
JES E 0 EN CHRIST HER L. MA OSKU
3 �� 3 -5 ZDI
DATE DATE
IMPROVEMENT PLAN FOR:
964 URANIA AVE
URANIA 4 LLC
'
254- 363 -10 & 13
16 -156 7F.M
13499 °I
PUBLIC WORKS
--
L DATE
PLANNING
Crl
REVIEWER
A
NGINEER DATE
5
SHEET 2 OF 3
INSPECTOR
PLEA 2451
Q
`
0
vI ^
Ad } N
��
"I
Z Q
WN
o
QC)
l i•irt -, ri ,
PRIVATE ON -SITE SEWER PROFILE
SCALE: HORIZ: 1 " =20'
VERT. 1'=4'
= PRIVATE SEWER DATA TABLE
LINE
LENGTH
CHORD /BEARING
RADIUS
I DELTA
COMMENTS
L1
226.00'
N894835 "W
--
1
16" PVC PRIVATE SEWS
LWD SEWER - S -22 TABLE
MANHOLE ID NUMBER
DESCRIPTION
PIPE
PIPE
PIPE
SLOPE
LOCATION OF MANHOLE (ADDRESS)
MH RIM EL
MH INVERT EL
MH DEPTH [FT]
MANHOLETYPE
No. OF LINES
MANHOLE LINING
COMMENTS
UPS DOWN
UPS MH COORDINATES
LENGTH
DIAMETER
MATERIAL
IMPROVEMENT PLAN FoR:
964 URANIA AVE
13499 -1
URANIA 4, LLC
APN: 254 - 363 -10 13
116 -156 7nM SHEET 3 OF Z
UPSTREAM DOWNSTREAM
[FT]
[FT]
(ANG, STD, DE, ORP, SMT)
THROUGH MH
UPSTREAM
TO
B IN DATE
1 -t�
^DATE
X
Y
[FT]
[IN]
[ %]
ADDRESS
DESCRIPTION
ADDRESS
DESCRIPTION
UPS
DOWN
UPS
DOWN
UPS
DOWN
UPS
DOWN
UPS
DOWN
TYPE
MFR
04-2250.
04 -2246
6243324 32
1969245 38
7180
8
SDR 3 PVC
5
6.9
URANIA AVE
R
U ANIAAVE
186.75
185.55
178.10
172.80
8.65
12.96
DE
STD
1
2
EPX
042246.
04 -2243
624331606
196932167
9144
8SDR35PVC
1.0
URANIAAVE
URANIAAVE
185.55
183.63
172.62
171.65
12.96
12.06
STD
STD
2
2
IPVC
04 -2443.
04 -2240.
6243283.30
1969619.80
203.48
8VCP
3.8
URANIAAVE
URANIAAVE
183.63
174.86
171.57
163.84
12.06
11.02
STD
STD
2
2
IPVC
ML
C EX.. LWD MANHOLE No. 04- 240
E ISPNG LWD 8" VCP z � � ;' (APPROX. 185' N) .�
EWER MAIN W, 705F`- " t � RIM= 174.86,
7 137.3' N7 IE= 164.06
%q EXl", E � y • NEW MANHOLES TO BE LINED WITH INTEGRALLY
i �P "r;k`. ,r> n «;s „ �� ° -GAS EI#E �, EX.: -PAV$ ,EXISTING 8 PVC LOCKING PVC PER LWD STANDARD SPECIFICATIONS
� r ��f EXISTING 14" C ��� D > } WATER IN DIVISION 1 PART 3 SECTION 3.04.
MA
WATER MAIN' RA IA Tom_ +3.48'
�EPROTECTEI) -IN -PLACE �,1 SEWER MANHOCE.04 -2243
EXISTING WATER' ETER PER L NH
TO E s REM =1 3.63
PR MpNU -
MENT�
- - - _ OTTED IN =PLACE -'
E OUT 171657
j`
T PP _ �; �, nvN EX. ASPHALT
� D CA SI
E r;s. DISTRICT "71 r G I. C SIDEWAL
El K
� ABANDON EXISTING � `� -
� � r
�� �. AREA II � � �" �PPER WATER SERVICE � !
SEWER LATERAL. #1 -
PARG'L 1 ,:A T OWNER'S EXPENSE
FFT7d9 SAWCUT EX PAVEMENT
I \ x I
PAD 1782 {� I LANDSCAPE
_ PARCB 4 PERVIOUS PAVER
-- - - #AD 179.5 Y e .' I PARKWAY: 8'X63,
FF AM
�❑ } Al I . o EXISTING
I~iIi . t� f k
i
J= !� „ may- l
� � i �' - - ] '
- SEWER LATERAL.
�14
III a >. -
II �
SEWER R
�,D 1r1StR1.4��/ S
,. � [ ❑ ❑ �� LWD STD DWG. t;�fi,, .0
vll ' II ➢ LAIR f r.A F'H
S -25 ��M? CoSFF�oas
4" SEWER LATERAL x- .,u ----
" PER LWD � t7. ° DISTRICT TO JNSTAL
_ -'" 4 -1" WATER•METERS '
PER LWD 5 -32 '(TYPE I SEWER CO PER 5 -32 (TYPE,JI)
�, / LWD STD. DWG. ` �' ; �. , ; x� w PER WAS WS-01, wc� 17
[ .
AND D TgI 3 s k -, _ _ - SQR_v5j0T 1 AT OWNERS EXPENSE '
SERVES L S -25 LOT 4
TRENCH RESURFACING
S t- PER CITY OF ENCINITAS
LOT t s _
STANDARD DETAIL
Hd0 EXIS77NG' SPE €D
NEW MANHOLES TO BE LINED WITH INTEGRALLY
S ;... S S S BUMP CUSHIONS
� I }400 'Y -" SEWER C PER FE f LOCKING PVC PER LWD STANDARD SPECIFICATIONS
TO BE RELOCATED
6" PVC PRfVATE j Lytr gip, = - DIVISION 1 PART 3 SECTION 3.04.
STA i +00.00 *� SEWER; STA 3 +24. 7-
" DW 5 -25 -
6 SEWER CLEANOUT II w -' URANIA STAB,,; +99.92
PER LWD S -8 SEWER MANHOLE 04 -2246
PER - u +`.. , 11 M 18W5 55 -3
Iw _
it
1 - .- - STA 1 +55.61- `}' t EXISTING -J,
.. I LE IN= 172.80
F "y °nF., MIT • �llf GA
a
PUBLIC SEWER PROFILE
SCALE: HORIZ 1 " =20'
VERT.• 1 " =8'
DIRT I U D °a°°
xL.
1,
= PUBLIC SEWER DATA TABLE
LINE LENGTH CHORD /BEARING RADIUS I DELTA COMMENTS
L2 96.44' N06°16'15 "W __ -- 8" PVC PUBLIC SEWER
L3 76.80' N06'16'15 "W -- ®- 8" PVC PUBLIC SEWER
Ja�
FS 184.9
FL 184.8
(STING 14� ACP EXISTING 8" PVC -rrees
VX WATER MAIN
WATER MAIN
fEX1 ASPHALT PROPOSED
SIDEWALK --, LWD SEWER
TC 1'84.2 MH 04-2243
EXISTING 2"
1 (AGAS LINE
F5 183.5
_,4
DISTRICT TO ABANDON
EXISTING 1" COPPER - - - -
WATER SERVICE EXISTING SEWER LATERAL 11
AT OWNER'S EXPENSE
FS 184.2 ' I
17' EASEMENT FOR PUBLIC
STREET ROW'
SAWCUT X.
' 1 PAVEMENT 20'
I
20�
14'
I
184.7
I -
t A`• 2p --
PERVIOUS PAVER <� -
�� PARKWAY,• 8`A63', _ EXISTING SEWER
EXISTING LWD 8" LATERAL 12
' SEWS TO $E
LLIW PER
PLANS.
c.
t F 185.01 DISTRICT TO INSTALL
TC 185.5: 4 -1 " WATER METERS
FL 185.0 _ PER WAS WS -01, WC -17
AT NER'S FxPF��E
, $rd CU IW I _lttsn S�GC
❑ , ❑ ❑ ❑ ❑
5 -25 ° _ RIM = 1$.75
IE =178 0 ' '
( I r
❑ o L0T8 - / GRAPHIC SCALE 1 " =20' SIDEWALK & PERVIOUS PAVER PARKWAY
- -- E P SCALE. 1 =10
PARCEi 3 , ee 71NG - - "
Fr_ v" ❑ ., EXIST( LATERAL #4 LWDXSELWER NOTE #40 0 20 40 60
J
o�
ILJ
Q
v
O
0
=U
Ul
QUA
OZQ
B M O
Q�h(n
No. 71651
Exp. 12/31/19
CHANGE NO.
DESCRIPTION
APPROVED
DATE
BENCHMARK
AS -BUILT APPROVALS
ENGINEERING DIVISION APPROVALS
CITY OF ENCINITAS - DEVELOPMENT SERVICES DEPARTMENT DRAWING NO.
. -�
DESCRIPTTO : ENC 1024 27 DISC IN
SIDEWALK SE QUADRANT LEUCADIA BLVD
LOCATION: 37' EASTERLY OF TRAFFIC SIGNAL
RECORD FROM: RECORD OF SURVEY NO.
ELEVATION: 178.543
DATUM: NAM88
-
INT.
DATE PLANS PREPARED UNDER SUPERVISION OF
- DATE: 3+f8
°� iti
R.C.E. NO.: 71651
q o
��� BRI ARDOL EXP.: 12 -31 -19
RECOMMENDED: APPROVED:
��
JES E 0 EN CHRISTOPHER L. MA OSKU
5, 5ZI 13 3- S�Zof�
DATE DATE
IMPROVEMENT PLAN FoR:
964 URANIA AVE
13499 -1
URANIA 4, LLC
APN: 254 - 363 -10 13
116 -156 7nM SHEET 3 OF Z
PUBLIC WORKS
A/A
B IN DATE
1 -t�
^DATE
PLANNING
T
REVIEWER
VEER
A
INSPECTOR
0