City of Encinitas
P'fanning and Budding (Department
Current (Planning (}ivision
505S. Vufcan/gvenue, Encinitas, California 92024 -3633
May 20, 2008
Frank Florez
Florez Engineering, Inc.
10732 Charbono Terrace
San Diego, CA 92131
Re: 948 -SG Plan Check; 1st Review (411 Santa Fe Drive; Conoco Phillips)
Dear Frank Florez:
The Planning Department has completed the review of your grading plans for permit 948 -SG at
411 Santa Fe Drive. Based upon this review the project will require revisions. Please provide
the following corrections to the grading plans:
1. Label the associated Coastal Development Permit Number (08- 022CDP) on the plans.
2. A space for the Planning Department approval (By and Date) shall be added to Sheet 1 of
the Plans.
3. Label the following Planning Notes on Sheet 1 of the plans:
a. The associated Coastal Development Permit# 08 -022 shall be approved prior to
the removal of any tanks.
b. The applicant/ representative shall obtain approval of a demolition permit from
the Building Department prior to the removal of any tanks or infrastructure.
c. The Fire Department shall be on -site during the tank removal.
d. All tanks shall be dry iced with 15 lb. per 1000 gallon tank capacity to inert vapor.
e. The lower explosive limit shall be 10% or less prior to the tank removals.
f. No tanks shall be cut on -site, and shall be removed in the same day.
If you have any questions regarding these revisions feel free to contact me at 760 - 633 -2718 or
via email at amavnard(a)ci.encinitas.ca.us.
UW4
Andrew Maynard
Planner II
City of Encinitas
TeL (760) 633- 2710,• Ta)C (760) 633 -2818
OFFICE USE ONLY
County of San Diego ° e
Department of Environmental Health ACTIVITY CODE 428T23
Hazardous Materials Division °
1255 Imperial Avenue v°
P.O. Box 129261
San Diego, CA 92112 -9261 Permit # AT5338
Establishment # 113266
Date: November 29, 2007
T) I T Expiration Date: November 29, 2008
Permit for Underground Storage Tank Construction /Closure
SITE NAME: Conoco Phillips #2705717 1
SITE ADDRESS: 411 Santa Fe Dr, Encinitas, CA 92024 AUG j a M8
OWNER NAME: Conoco Phillips
OWNER ADDRESS: 600 N. Dairy Ashford Dr, Houston, TX 77079
DESCRIPTION OF PROPOSED WORK: Remove three (3) underground storage tanks and all associated piping
(T002, TO03, TO04)
approval. Ilpfu
of permit ll:
PERMIT CONDITIONS: For tank systems that are to be removed, the excavation shall be exposed prior to the scheduled
inspection and sampling points identified by the DEH inspector. Sampling is required for both tanks) and piping. The tank(s)
and piping must remain in the excavation until the DEH Inspector approves the removal.
1. All piping and underground storage tanks must be removed at the same time. Failure to do so will result in a re- inspection and
$674.00 re- inspection fee.
2. At least one sample must be analyzed for MTBE and related oxygenates (DIPE, TAME, ETBE, TBA) using EPA Method 8260B
3. Certificate of Disposal /manifests required for tank
4. Formerly SW RCB Forms A and B will be required to be submitted
Please be advised:
All underground storage tanks that are to be removed must be cleaned and property inerted prior to the removal
1) The tanks are visually free from all product, sludge, rinsate and debris. Residual staining caused by soil and waste
consisting of light shadows, slight streaks, or minor discolorations, and soil and waste in cracks, crevices and pits may be present.
2) Tanks that held a Hazardous material or hazardous waste that had the potential to generate flammable vapors, must be properly
inerted. A combustible gas indicator (CGI), which is properly calibrated, shall be used to measure the concentration of flammable
vapor at the top, center and bottom of the underground storage tank. The concentration of flammable vapor must be below twenty
percent of the Lower Explosive Limit (LEL) for the material that was contained in the tank(s) and the oxygen concentration shall be the
same as that of ambient air, approximately 20.8 %. The underground storage tank(s) must inerted with dry ice using a minimum of 15
pounds for every 1000 gallons of tank capacity.
3) Failure to have the tank property cleaned prior to the time of the removal will result in the cancellation of the removal and will require a
re- inspection and $385.00 re- inspection fee.
This office must be given at least 48 hours notice for all required Underground Storage Tank Activity. Please call at (619) 338 -2214 to schedule
an appointment. For cancellations, please call (619) 237 - 8451.
THIS PERMIT DOES NOT EXCUSE ANY OWNER OR OPERATOR FROM COMPLYING WITH ALL APPLICABLE FEDERAL, STATE, COUNTY OR
LOCAL LAWS, ORDINANCES OR REGULATIONS. THE OWNER OR OPERATOR IS REQUIRED TO DETERMINE IF ANOTHER PERMIT OR
APPROVAL FROM ANY OTHER AGENCY OR DEPARTMENT IS NECESSARY. THE COUNTY, BY ISSUING THIS PERMIT, DOES NOT RELINQUISH
RIGHT TO ENFORCE ANY VIOLATION OF LAW
Plans Reviewed and Approved By: Cecilia Lewallen Date: 11/29/07
Noted
Backfill Recommendations for
Tank Excavation, Station No. 2705717
411 Sante Fe Drive
Encinitas, California
Prepared For:
Mr. Toby Kish, Director Constr. Mgmt.
CONOCO Phillips
P.O. Box 25376
Santa Ana, California 92799 -5376
Date:
May 09, 2008
Project Na
09 -2851
PREPARED BY.•
Anthony- Taylor Consultants
304 Enterprise Street
Fscon&do, California 92029
(760) 738 -8800
U. i
Y
I
I
ANTHONY- TAYLOR CONSULTANTS
304 Enterprise Street • Escondido, G 92029 • (760) 7388800 • (760) 7388232 fax
May 09, 2008
CONOCO Phillips Project No. 08-2851
P.O. Box 25376
Santa Ana, California 92799 -5376
Attention: Mr. Toby Kish, Director Construction Management
Subject: Backfill Recommendations for Tank Excavation, Station No. 2705717
411 Sante Fe Dr., Encinitas, California
Reference: "Standard Specifications, for Public Works Construction" 1997 Edition.
Dear Mr. Kish:
In accordance with your authorization, Anthony - Taylor Consultants, Inc. presents the
following recommendations for backfill of the tank excavations on the subject site at 411
Santa Fe Dr. in Encinitas, California. These recommendations are provided at the request of
the City of San Diego. C->.jc ..� try
RECOMMENDATIONS
U Ground Water is Encountered
We recommend that the tank removal excavations be backfilled with either select backfill (I -
inch minus) or float rock (3/4 -inch minus) to slightly above the ground water level
encountered (a minimum of 2 to 3 inches). The material shall be provided some compaction
effort to consolidate the material prior to placing a layer of Mirafi 140N (or equivalent) over
the top of the coarse backfill. Following the filter fabric placement, the remainder of the
excavation can be backfilled with approved fill soils up to finished subgrade elevations. The
backfill above the filter fabric should be predominantly granular and shall be placed in uniform
lifts (not exceeding 8 inches in compacted thickness) and be compacted by mechanical means
to at least 90 percent relative compaction (based on ASTM D 1557 -00). Use of on -site soils
may permitted for backfill if free of deleterious material (trash, debris) and over size material
greater than 6 inches in maximum dimension. Placement and compaction of fill should be
performed in accordance with local grading ordinances under the observation and testing of
the geotechnical consultant.
Architects • Engineers • Planners • Construction Managers
CONOCO Pe1wrS PROJECT No. 08 -2851
411 SANTA FE DR.. ENCINITAS, CA May 09, 2008
Page -2-
If Ground Water is not Encountered
The excavation can be backfilled with approved fill soils up to finished subgrade elevations.
The back-fill material should be predominantly granular and shall be placed in uniform lifts
(not exceeding 8 inches in compacted thickness) and be compacted by mechanical means to
at least 90 percent relative compaction (based on ASTM D1557 -00). Use of on -site soils may
permitted for backfill if free of deleterious material (trash, debris) and over size material
greater than 6 inches in maximum dimension. Placement and compaction of fill should be
performed in accordance with local grading ordinances under the observation and testing of
the geotechnical consultant.
This opportunity to be of service is appreciated. Should you have any questions or require
additional information please contact the undersigned at (760) 738 -8800.
Respectfully submitted,
ANTHONY - TAYLOR CONSULTANTS
"'� "'_� E�ppOFESSipN
try L. [ hal, P.E. ��e Pv Mic
Senior ect Engineer
GE 2515 No. 1515
Distribution: (2) Addressee
(2) Gus Guerrero - QPM
CITY OF ENCINITAS 2007 ENGINEERING FEE SCHEDULE F7 " " Jha4r
I r1 //_ 7 . /16 - i -fa _
DATE: 1an
PERMIT NO..
TECH INT.
CODE SERVICE NAME FEE AMOUNT ACCOUNT NUMBER
B1
Building Permit New /Addition 0 -500 SF
$ 150.00
1 101- 6010 - 451 -4240
101 -0000- 345 -2210
B2
Building Permit New /Addition 500 -2000 SF
$ 250.00
101- 0000 - 345 -2220
B3
Building Permit New /Addition 2000 -5000 SF
$ 450.00
101 -0000- 345 -2230
B4
Building Permit New /Addition >= 5000 SF
$ 600.00
101- 0000 - 345 -2240
EP
Building Permit - Pool
$ 250.00
101- 0000.345 -2600
B5
Bldg Permit Comm New /Add 0 to 500 SF
$ 150.00
101 - 0000 -345 -2410
B6
Bldg Permit Comm New /Add 500 to 2000 SF
$ 250.00
101 -0000- 345 -2420
B7
Bldg Permit Comm New /Add 2000 to 10000
$ 550.00
101 -0000- 345 -2430
B8
Bldg Permit Comm New /Add. =10000 SF
$ 750.00
101.0000- 345 -2440
B9
Building Permit, Commercial, Remodel, TI
$ 300.00
101- 0000 - 345 -2800
C3
Certificate of Correction
$ 110.00
101 -0000- 345 -2900
C4
Construction change - Minor - per sheet
$ 200.00
101- 0000- 345 -3210
C5
Construction change - Major- per sheet
$ 350.00
101- 0000 - 345 -3220
PM
Final Parcel Map- Sheet
$ 2,000.00
101 - 0000 - 345 -3400
FM
Final Subdivision Ma - Sheet
$ 1,600.00
101 -0000- 345 -3600
SG
Simplified Grading Plan
$ 900.00
qoo Q
101- 0000 - 345 -4110
GR
Grading Plan Check - Sheet
$ 1,450.00
101- 0000 - 345 -4120
NP
NPDES Plan Check - Sheet
$ 125.00
101 -0000- 345 -4200
M1
Structural Plan Check - Sheet
$ 240.00
101 - 0000 - 345 -4400
EO
Erosion Plan Check - Sheet
$ 175.00
101 - 0000- 345 -4600
GS
GIS Map Fee
$ 375.00
101- 0000 - 345 -5000
TE
Temporary Encroachment Pen-nit
$ 150.00
101 -0000- 345 -5410
PE
Permanent Encroachment
$ 290.00
101- 0000- 345 -5420
LP
Landsca a /Irr Plan Check Private - Sheet
$ 130.00
101- 0000 - 345 -5510
LV
Landsca a /Irr Plan Check Public - Sheet
$ 260.00
101 - 0000 - 345 -5520
CN
ROW Construction Permit and Ins p- Minor
$ 300.00
101 -0000- 345 -5610
CJ
ROW Construction Permit and Ins p- Major
$ 900.00
101 -0000- 345 -5620
EX
Utility Construction Permit
$ 250.00
101 - 0000 - 345 -5700
TB
Temporary Encroachment Permit - Beach
$ 1,500.00
101- 0000 - 345 -5430
VA
Street Vacation Application
$ 3,500,00
101 - 0000- 345 -5810
SN
Street Name Change Application
$ 3,500.00
101- 0000 - 345 -5820
GI
Grading Inspection
101 -®000- 345 -6010
II
Improvement Inspection
101 -0000- 345.6020
NI
NPDES - Inspection
101- 0000 - 345 -0200
IR
Im rovement Plan Check - Sheet
$ 1,700.00
101 - 0000 - 345 -4800
EV ISpecial
Event
$ 300.00
101 -0000 -345 -7000
TR
Traffic Control Plan
$ 250.00
101- 0000 -345 -7400
PP ISWPPP
Project Disturbin > Ac 1
$ 750.00
101 -0000- 345 -7600
TOTAL 90Pi °O
Fwtda to talc % of ACE did not charge, fee h 5% of" $100,000 and 3% of each 5100,000 above that level.
This lee is new and must be phased (1% of first 5100.000 and 0.6% of each 5100,000 above) Mr, (1% of first $700,000 and 0.6% of each 5100,000 over)
CODE DEPOSIT ACCTS. (NO CREDIT CARDS) TOTAL
MR
Structural
1 101- 6010 - 451 -4240
SY
ISecurity Deposits.
101- 0000 - 218 -0000
Paget GlaandalFrownnin Fea sannM 2falr.11A er.6na fmn