Loading...
2010-10489 SGK SOIL a TSSTINO, INC ■ 0 Y IS ST IS a 0 N µAR 2 2 2010 San Diego Office PHONE P.O. Box 600627 (619) 280 -4321 (760) 775-5983 San Diego, CA 92 160-062 7 TOLL FREE (877) 215 -4321 6280 Riverdale Street San Diego, CA 92120 F A X (619) 280.4717 www.scst.com Indio Office PHONE 83.740 Citrus Avenue (760) 775-5983 Suite G TO L L F R E E (877) 215 -4321 Indio, CA 92 201 -34 38 FAX (760) 775 -8362 www.scst.com GEOTECHNICAL INVESTIGATION MAGDALENA ECKE YMCA PLANNED PRESCHOOL ADDITION 200 SAXONY ROAD ENCINITAS, CALIFORNIA PREPARED FOR: MR. RON LELAKES MAGDALENA ECKE YMCA 200 SAXONY ROAD ENCINITAS, CALIFORNIA 92024 PREPARED BY: SOUTHERN CALIFORNIA SOIL 3 TESTING, INC. 6280 RIVERDALE STREET SAN DIEGO, CALIFORNIA 92120 Providing Professional Engineenng Services Since 1959 9 SOIL 4 TESTING, INC. r O V ! S r Y 0 O N San Diego Office PHONE P.Q. BOX 600627 (619) 280 -4321 San Diego, CA 9 2160 -062 7 O R T L F E E L 215-43.21 6280 Riverdale Street - San Diego, CA 92120 F A X (619) 280.4717 www.scst.com September 2, 2009 Mr. Ron Lelakes Magdalena Ecke YMCA 200 Saxony Road Encinitas, California 92024 Subject: GEOTECHNICAL INVESTIGATION MAGDALENA ECKE YMCA PLANNED PRESCHOOL ADDITION 200 SAXONY ROAD ENCINITAS, CALIFORNIA Dear Mr. Lelakes: Indio Office PHONE 83 -740 Citrus Avenue (760) 775 -5983 TO L L F R E E Suite G (877) 215.4321 Indio, CA 92201.3438 FAX (760) 775 -8362 www.scst.com SCS &T No. 0911114 Report No. 1 This letter transmits Southern California Soil & Testing Inc.'s (SCS &T) report describing the geotechnical investigation performed for the planned addition to the preschool at the Magdalena Ecke YMCA located in the City of Encinitas, California. This investigation was conducted in general conformance with the scope of work presented in SCS &Ts proposal dated August 6, 2009. If you have any questions concerning this report, or need additional information, please call us at (619) 280 -4321. S �k1 (c IA SOIL AND TESTING, INC. ti No .2 = m Ga k �� 6 e 27 Fir! Obod I Engineer GBF:aw (4) Addressee TABLE OF CONTENTS SECTION PAGE EXECUTIVE SUMMARY.... ...._..__ -...._ ............... _.._ .... .... .... »..» »... » »..... ».» 1. INTRODUCTION. ».. ».._ ..... ..»»..»»...... ... ..» ....... » » ... .... ... _ ..... .............. »..... »»..1 1.1 GENERAL ........................................................................................................ ..............................1 1.2 SCOPE OF WORK ............................................................................................. ............................... 1 1.1.1 Field Explorat ion ................................................................................... ............................... 1 1.2.2 Laboratory Testing ................................................................................ ............................... 1 1.2.3 Analysis and Report ............................................................................... ............................... 1 2. SITE AND SUBSURFACE CONDITIONS....... —..Y 2.1 SITE DESCRIPTION .......................................................................................... ............................... 2 2.2 SUBSURFACE CONDITIONS .......................................................................»... ............_.................. 2 2.3 SEISMIC DESIGN PARAMETERS ....................................................................... ............................... 2 3. CONCLUSIONS ...............__...»........_ » » . ... ... .. .. ... .. ... ».. ».. 2 4. 4.1 SITE PREPARATION AND GRADI NG ................................................................. ............................... 3 4.1.1 Site Preparation ..................................................................................... ............................... 3 4.1.2 Earthwork .............................................................................................. ..............................3 4.1.3 Site Excavation Characteristics ............................................................. ............................... 3 4.1.4 Imported Soil ............................................... a......................................................... .............. 3 Surface4.1.5 Drainage ................................................................................... ............................... 4 4.1.6 Grading Plan Review ............................................................................. ............................... 4 4.1.7 Temporary Excavations ......................................................................... ............................... 4 4.2 FOUNDATIONS ................................................................................................. ..............................5 4.2.1 Shallow Spread Footings ....................................................................... ............................... 5 4.2.2 Existing Footings to Support New Loads .............................................. ............................... 5 4.2.3 Settlement Characteristics ..................................................................... ............................... 5 4.2.4 Foundation Plan Review ....................................................................... ............................... 5 4.2.5 Foundation Excavation Observations ................................................... ............................... 5 4.3 SLABS -ON -GRADE .......................................................................................... ............................... 6 4.3.1 Interior Concrete Slabs -on- Grade ......................................................... ............................... 6 4.3.2 Exterior Slabs -On -Grade ...................................................................... ............................... 6 5. GEOTECEMCAL ENGINEERING DURING CONSTRUCTION......._.__...._.. . 7 6. CLOSURE— ......................... »..» ...__. ........ ... » »........... .._.... » »..7 ATTACHMENTS FIGURES Figure 1 - Site Location Map Figure 2 - Exploratory Test Pit Location Map APPENDICES Appendix I - Logs of Exploratory Test Pits Appendix 11- Laboratory Testing 15C ST EXECUTIVE SUMMARY This report presents the results of the geotechnical investigation Southern California Soil and Testing, Inc. performed for the planned addition to the preschool at the Magdalena Ecke YMCA located at 200 Saxony Road in the City of Encinitas, California. We understand that the addition will consist of a single story structure. The purpose of our work is to provide conclusions and recommendations regarding the geotechnical aspects of the project. Two exploratory test pits were excavated using hand -tools to a depth of about 5 feet. Materials encountered in the test pits consisted of fill and formational materiel commonly identified as very old surficiat deposits. The fill is comprised of loose clayey sand. The surficial deposits are comprised of medium dense to dense clayey sand. No groundwater was encountered in our test pits. The main geotechnical consideration affecting the planned additions is the presence of loose fill material and potentially compressible surficiat deposits that are considered unsuitable for the support of settlement sensitive structures. In the areas beneath the planned improvements, the existing fill should be excavated in its entirety. Additionally, a portion of the surficial deposits should be excavated. It is anticipated the excavated materials can be replaced as compacted fill. The planned addition can be supported on spread footings with bottom levels in compacted fill material. The grading and foundation recommendations herein will need to be updated once final grading and foundation plans are developed. 1. INTRODUCTION 1.1 GENERAL This report presents the results of the geotechnical investigation Southern California Soil and Testing, Inc. performed for the planned addition to the preschool located at Magdalena Ecke YMCA located in the City of Encinitas, California. Existing improvements consist of a single - story structure and associated hardscape. We understand that the project will consist of a lateral addition to the existing structure. The purpose of our work is to provide conclusions and recommendations regarding the geotechnical aspects of the project. The location of the site is shown on Figure 1. 1.2 SCOPE OF WORK 1.2.1 Field Exploration Subsurface conditions were explored by excavating 2 exploratory test pits that extended approximately 5 feet deep at the locations shown on Figure 2. A SCSBT geologist logged the test pits and obtained samples for examination and laboratory testing. The logs of the test pits are in Appendix I. Soils are classified according to the Unified Sal Classification System illustrated on Figure 1 -1. 1.2.2 Laboratory Testing The laboratory program consisted of tests for : Sieve Analysis • Maximum Density and Optimum Moisture Content • Direct Shear The results of the laboratory tests, and brief explanations of test procedures, are in Appendix II. 1.2.3 Analysis and Report The results of the field and laboratory tests were evaluated to develop conclusions and recommendations regarding: 1. Subsurface conditions beneath the site. 2. Site preparation recommendations. 3. Criteria for seismic design in accordance with California Building Code procedures. 4. Alternatives for foundation support along with geotechnical engineering criteria for design of the foundations. 5. Resistance to lateral loads. 6. Estimated foundation settlements. 7. Support for concrete slabs -on - grade. v; 51 : T Ecke YMCA Preschool Expansion September 2. 2009 200 Saxony Road SCSBT No. 0911114 -01 Enclndes, California Page 2 2. SITE AND SUBSURFACE CONDITIONS 2.1 SITE DESCRIPTION The location of the planned addition is located at the southeast corner of the existing structure. The area is bounded by a parking lot on the west, play area on the east, and typically landscaping on the south. At the time of site investigation the area was covered with asphalt concrete and grass. Topographically the area of the planned improvement is a relatively flat site with a total elevation difference of about 1 foot over a span of about 80 feet. 2.2 SUBSURFACE CONDITIONS Materials encountered in the test pits consisted of fill and formational material mapped as very old surficial deposits. The fill is comprised of loose clayey sand. The surficiai deposits are comprised of medium dense to dense clayey sand. Groundwater was not encountered in the test pits. The permanent groundwater level is expected to be below a depth that will influence planned construction. However, groundwater levels can fluctuate seasonally, and can rise significantly following periods of precipitation. 2.3 SEISMIC DESIGN PARAMETERS A geologic hazard likely to affect the project is groundshaking as a result of movement along an active fault zone in the vicinity of the subject site. The site coefficients and adjusted maximum considered earthquake spectral response acceleration parameters in accordance with the 2007 California Building Code based on the 2006 International Building Code are presented below: Site Coordinates: Latitude 33.0510 Longitude 117.2850 Site Class: D Site Coefficient F, = 1.0 Site Coefficient F, = 1.5 Spectral Response Acceleration at Short Periods S, = 1.356 Spectral Response Acceleration at 1- Second Period S, = 0.508 Sms =F,S, SM, =FxS, SDs=2l3' Sw SD, =2/3• Sm, 3. CONCLUSIONS Earthwork for the project is expected to consist of cuts and fills of less than 7 feet in depth. The new buildings can be supported on shallow foundations founded in compacted fill following site preparation in accordance with ft following recommendations. S Ecke YMCA Preschool Expansion Seplember 2, 2009 200 Saxony Road SCSBT No. 0911114-01 EnonNas, Callfomla Page 3 4. RECOMMENDATIONS 4.1 SITE PREPARATION AND GRADING 4.1.1 Site Preparation Site preparation should begin with the removal of vegetation and debris. The existing soils should be excavated to a depth of two feet below planned footing bottom levels in the structure area and two feet below the planned subgrade elevation of the hardscape improvements. Additionally, the existing fill should be excavated in its entirety. Excavations up to about 7 feet in depth should be anticipated. Horizontally, the excavation should extend at least five feet outside perimeter footing lines or planned hardscape improvements or up to existing improvements whichever is less. A SCS &T representative should observe conditions exposed in the bottom of the excavation to determine if additional removal is required. 4.1.2 Earthwork The material exposed in the bottom of the excavation should be scarified to a depth of 12 inches, moisture conditioned and compacted to at least 90% relative compaction. Excavated materials, except for soil containing roots and organic debris, can be used as compacted fill. Fill should be placed in 6- to 8 -inch thick loose lifts, moisture conditioned to near optimum moisture content, and compacted to at least 90% relative compaction. The maximum dry density and optimum moisture content for the evaluation of relative compaction should be determined in accordance with ASTM D 1557. Utility trench backfill within 3 feet of the structure and beneath pavements and hardscape should be compacted to a minimum of 90% relative compaction. The upper 12 inches of subgrade beneath slabs and paved areas should be compacted to at least 95% relative compaction. Site preparation should begin with the removal of the existing improvements, vegetation and debris in the areas to receive new structures. The existing fill should be excavated in its entirety to a depth of 1 8-inches below lowest planned footing. 4.1.3 Site Excavation Characteristics It Is anticipated that excavation can be achieved with conventional earthwork equipment in good working order. However, it should be noted that well cemented zones and boulders may be encountered during grading. 4.1.4 Imported Soil Imported fill should consist of predominately granular soil free of organic material and rocks greater than 6 inches in maximum dimension. Imported soil should have an Expansion ST Ecke YMCA Preschool Expansion Sectembor 2, 2009 200 Saxony Road SCS &T No. 0911114-01 Encinitas, Caliromia Page 4 Index of 20 or less and should be inspected and, if appropriate, tested by SCS &T prior to transport to the site. 4.1.5 Surface Drainage Final surface grades around the building should be designed to collect and direct surface water away from the structure and toward appropriate drainage facilities. The ground around the structure should be graded so that surface water flows rapidly away from the structure without ponding. In general, we recommend that the ground adjacent to the structure slope away at a gradient of at least 2 %. Densely vegetated areas where runoff can be impaired should have a minimum gradient of at least 5% within the first 5 feet from the structure. Roof gutters with downspouts that discharge directly into a dosed drainage system are recommended on structures. Drainage pattems established at the time of fine grading should be maintained throughout the life of the proposed structures. Site irrigation should be limited to the minimum necessary to sustain landscape growth. Should excessive irrigation, impaired drainage, or unusually high rainfall occur, saturated zones of perched groundwater can develop. 4.1.6 Grading Plan Review The grading plans should be submitted to SCS &T for review to ascertain whether the intent of the recommendations contained in this report have been implemented, and that no revised recommendations are necessary due to changes in the development scheme. 4.1.7 Temporary Excavations Temporary slopes in FlII should not be steeper than 1:1 (horizontal:vertical). Temporary slopes in the surficial deposits should not be steeper than ' /Y:1 (horizontal: vertical). The faces of temporary slopes should be inspected daily by the contractor's Competent Person before personnel are allowed to enter the excavation. Any zones of potential instability, sloughing or raveling should be brought to the attention of the Engineer and corrective action implemented before personnel begin working in the trenches or excavations. Existing fill should be classified as Type C soils in accordance with CaIOSHA guidelines. The surficial deposits can be classified as Type B soil in accordance with CalOSHA guidelines. The footings supporting the existing structure should be supported in areas where the horizontal distance between the top of the excavation and the existing footing is less than the depth of the excavation. Ecke YMCA Preschool Expansion September 2, 2009 200 Saxony Road SCS& T No. 091111401 Encinitas, Cadfamia Page 5 4.2 FOUNDATIONS 4.2.1 Shallow Spread Footings Shallow spread footings can be used to support the planned addition. The footings should extend to a minimum depth of 18 inches below lowest adjacent finish pad grade. A minimum width of 12 inches is recommended for continuous footings. Isolated footings should be at least 24 inches wide. A bearing capacity of 2,500 pounds per square foot (psq can be used. This value can be increased by % when considering the total of all loads, including wind or seismic forces. Footings located adjacent to slopes should be extended to a depth such that a minimum distance of 7 feet exists between the outside bottom footing edge and the face of slopes. Lateral loads will be resisted by friction between the bottoms of footings and passive pressure on the faces of footings and other structural elements below grade. A friction factor of 0.30 can be used. Passive pressure can be computed using a lateral pressure value of 300 psf per foot of depth below the ground surface. The upper 1 foot of soil should not be relied on for passive support unless the ground is covered with pavements or stabs. 41.2 Existing Footings to Support New Loads The existing footings to support new loads should extend down to competent material as determined by the project geotechnical engineer. This will need to be verified in the field during construction. In areas where the footings do not extend into competent material the footings should be strengthened with grade beams that extend to the proper depth as determined by the project geotechnical engineer. 4.2.3 Settlement Characteristics Total footing settlements are estimated to be less than '/2 inch. Differential settlements between adjacent footings, and between the middle and ends of continuous footings, are estimated to be less than '/2 inch. Settlements should occur rapidly, and should be completed shortly after structural loads are applied. 4.2.4 Foundation Plan Review The foundation plans should be submitted to SCS &T for review to ascertain that the intent of the recommendations in this report have been implemented and that revised recommendations are not necessary as a result of changes after this report was completed. 4.2.5 Foundation Excavation Observations It is recommended that foundation excavations be approved by a representative from SCS &T prior to forming or placing reinforcing steel. a� 1 Ecke YMCA Preschool Expansion September 2. 2009 200 Saxony Road SCSBT No. 0911114 -01 Encinitas, CaGlomia Page 6 4.3 SLABS -ON -GRADE 4.3.1 Interior Concrete Slabs -on -Grade Concrete slabs- on-grade should have a thickness of at least 5 inches and be reinforced with at least No. 3 reinforcing bars placed at 18 inches on- center each way. Slab reinforcement should be placed approximately at mid - height of the slab and extend at least 6 inches down into the footings. Slabs -on -grade should be underlain by a 4 -inch thick blanket of clean, poorly graded, coarse sand or crushed rock. A moisture vapor retarder /barrier should be placed beneath slabs where floor coverings will be installed. Typically, plastic is used as a vapor retardant. If plastic is used, a minimum 10-mil is recommended. The plastic should comply with ASTM E 1745. Plastic installation should comply with ASTM E 1643. Current construction practice typically includes placement of a two-inch thick sand cushion between the bottom of the concrete slab and the moisture vapor retarder/barrier. This cushion can provide some protection to the vapor retarder /barrier during construction, and may assist in reducing the potential for edge cutting in the slab during curing. However, the sand layer also provides a source of moisture vapor to the underside of the slab that can increase the time required to reduce moisture vapor emissions to limits acceptable for the type of floor covering placed on lop of the slab. The floor covering manufacturer should be contacted to detennine the volume of moisture vapor allowable and any treatment needed to reduce moisture vapor emissions to acceptable limits for the particular type of floor covering installed. 4.3.2 Exterior Slabs-On -Grade The upper 2 feet of soil below exterior concrete slabs-0n -grade should have an Expansion Index of 20 or less. Exterior concrete stabs -on -grade should have a minimum thickness of 4 inches; reinforced with at least No. 3 bars at 18 inches on center each way. Slabs should be provided with weakened plane joints. Joints should be placed in accordance with the American Concrete Institute Guidelines. The landscape architect should be consulted in selecting the final joint patterns. A 1 -inch maximum size aggregate mix is recommended for concrete for exterior slabs. A water /cement ratio of less than 0.45 also is recommended, to decrease the potential for shrinkage cracks. The corrosion potential of on -site soils with respect to reinforced concrete will need to be taken into account in concrete mix design. Coarse and fine aggregate in concrete should conform to the °Greenbook" Standard Specifications for Public Works Construction. M Eck@ YMCA Preschool Expansion September 2, 2009 200 Saxony Road SCSdT No. 0911114 -01 Encirxtas, California Page 7 S. GEOTECHNICAL ENGINEERING DURING CONSTRUCTION The geotechnical engineer should review project plans and specifications prior to bidding and construction to check that the intent of the recommendations in this report has been incorporated. Observations and tests should be performed during construction. If the conditions encountered during construction differ from those anticipated based on the subsurface exploration program, the presence of the geotechnical engineer during construction will enable an evaluation of the exposed conditions and modifications of the recommendations in this report or development of additional recommendations in a timely manner. SCSBT should be advised of any changes in the project scope so that the recommendations contained in this report can be evaluated with respect to the revised plans. Changes in recommendations will be verified in writing. The findings in this report are valid as of the date of this report. Changes in the condition of the site can, however, occur with the passage of time, whether they are due to natural processes or work on this or adjacent areas. In addition, changes in the standards of practice and government regulations can occur. Thus, the findings in this report may be invalidated wholly or in part by changes beyond our control. This report should not be relied upon after a period of two years without a review by us verifying the suitability of the conclusions and recommendations to site conditions at that time. In the performance of our professional services, we comply with that level of care and skill ordinarily exercised by members of our profession currently practicing under similar conditions and in the same locality. The client recognizes that subsurface conditions may vary from those encountered at the pit locations, and that our data, interpretations, and recommendations are based solely on the Information obtained by us. We will be responsible for those data, interpretations, and recommendations, but shall not be responsible for interpretations by others of the Information developed. Our services consist of professional consultation and observation only, and no warranty of any kind whatsoever, express or implied, is made or intended in connection with the work performed or to be performed by us, or by our proposal for consulting or other services, or by our furnishing of oral or written reports or findings. CZ f W a t Atl �S ICyco wn as _ S Boa s n o pa M3IA Y C) VIA ^ ■ i yp�a �tl 11I143o '� m ,�As� �a5 •: VIA A L boy^ "■ 2W 210 M H51Na0� m 5`•: g C- 210 O1111'93I0 IN5 v �° � i h p � bd N3V�lY -i f CI PfR PL co! m s + m m rn 80 GdDllols PL ° b r = RD o N S N Z s< �, Project OR ?ACTFIC !!FViIEEW LN to M1 O -' 3TW) Oce WEST v F ST 210 SN30 C� OCE.� In y x ds ..T _. _ r mom „r — VI91f to T DELPNINI 30 ON IWV3 w . GLOX INA ST `� p `' yP m 4113 ROSERAY DR 4 m +� D��ss OOMI00 13 NO Atlg�501i xc tw _ Q M FRAXINELLA ST Am w RRI MUSE LN �� �� S� yy r- 0 V m N Date: September 1, 2009 Figure: EkSOUTHERN CALIFORNIA ECKE YMCA PRESCHOOL By: AKN SOIL & TESTING, INC. EXPANSION Job No.: 0911114 -1 4 �• i •� Al •••' AI EXPLANATIO t E '�• �� � 1 • 1 ,1 • Deposits I Very w) ~ �. �!■r■ ns�■ c, as • _ Wnv, \ • _ ■ ... ■ '1 353 It APPENDIX I APPENDIX I FIELD INVESTIGATION Two exploratory test pits were excavated using hand tools at the locations indicated on Figure 2 on August 25, 2009. The fieldwork was performed under the observation of our geotechnical engineer, who also lagged the pits and obtained samples of the materials encountered. Relatively undisturbed chunk samples and disturbed bulk samples were obtained from the excavated material. The test pit logs are presented on Figures 1 -2 through 1 -3. Soils are described in accordance with the Unified Soil Gassi ication System illustrated on Figure 1 -1. SC ST SUBSURFACE EXPLORATION LEGEND UNIFIED SOIL CLASSIFICATION CHART SOIL DESCRIPTION GROUP SYMBOL TYPICAL NAMES _ 1. COARSE DRAINED, more than W1. of material is larger than No. 200 sieve size. GRAVELS CLEAN GRAVELS GW Well graded gravels, gravel -sand mixtures, little or no fines. More than half of coarse fraction is GP Poorly graded gravels, gravel sand mixtures, little or no fines. larger than No.4 slave size but GRAVELS WITH FINES GM Silty gravels, poorly graded gravel- sand -silt mixtures. smaller than 3 ". (Appreciable amount of fines) GC Clayey gravels, poorly graded gravel -sand, clay mixtures. SANDS CLEAN SANDS SW Well graded sand, gravelly sands, little or no fines. More than half of coarse fraction Is SP Poorly graded sands, gravelly sands, little or no fines. smaller than No. 4 sieve size. SANDS WITH FINES SM Silty sands, poorly graded sand and silty mixtures. (Appreciable amount of fines) SC Clayey sands, poorly graded sand and clay mixtures. II. FINE GRAINED, more than W% of material is smaller than No. 200 sieve size. SILTS AND CLAYS ML Inorganic slits and very fine sands, rock flour, sandy slit (Liquid Limit or clayey -silt -sand mixtures with slight plasticity. less than 50) CL Inorganic clays of low to medium plasticity, gravelly clays, sandy clays, silty clays, lean days. OL Organic silts and organic silty clays or low plasticity. SILTS AND CLAYS MH Inorganic silts, micaceous or diatomaceous fine (Liquid Limit sandy or silty soils, elastic silts. greater than 50) CH Inorganic clays of high plasticity, fat clays. OH Organic clays of medium to high plasticity. III. HIGHLY ORGANIC SOILS PT Peat and other highly organic soils. Q Water level at time of excavation or as indicated MS - Maximum Size of Particle ®- Bulk Sample MAX - Maximum Density AL - Atterberg Limits pH - pH & Resistivity CAL - Modifled California pentratlon test sampler RC - Relative Compaction CK - Undisturbed chunk sample RV - R Value CL - Chloride SA - Sieve Analysis CON - Consolidation SC - Sand Cone COR - Corrosivlty Test SF - Sulfate & Chloride - Sulfate SPT - Standard penetration test sampler . Chloride ST - Shelby Tube - pH and Resistivity TX - Triaxial Compression DS - Direct Shear UC - Unconfined Compression El - Expansion index ECKE YMCA PRESCHOOL EXPANSION OUTHERN CALIFORNIA By: AKN Date: 912109 SOIL & TESTING, INC. [&: Job Number. 09111141 Figure: 41 LOG OF BORING NUMBER HA -1 Date Excavated: 8125109 Logged by: AKN Equipment: Hand Tools Project Manager GF Surface Elevation (ft): NIA Depth to Water (ft): N/A SAMPLES LU zi, M U d Q _ U V Y W K O N P w Cn SUMMARY OF SUBSURFACE CONDITIONS LU 0 z z a~ 0 >- Co 0 SC Very Old Parallc Deposits (Qvop,a): Medium reddish- SA, DS, MAX brown, medium dense to dense, mottled, fine to medium grained, CLAYEY SAND. 1 2 Becomes dense at 2 feet. 3 4 5 TERMINATED AT S FEET. NO GROUNDWATER OR SEEPAGE ENCOUNTERED 6 7 8 9 1 101 ECKE YMCA PRESCHOOL EXPANSION SOUTHERN CALIFORNIA By; AKN Date: September 1, 2009 SOIL 8 TESTING, INC. Job Number: 0911114 -1 Figure: 1-2 LOG OF BORING NUMBER HA -2 Date Excavated: 8125109 Logged by AKN Equipment: Hand Tools Project Manager: GF Surface Elevation (ft): WA Depth to Water (ft): N/A SAMPLES W a r = U D Y _ � r $ Q ~ a N SUMMARY OF SUBSURFACE CONDITIONS � d w W Z) N a CO z O � O � > o aa0 6 Inches of sod and associated topsoil sc ARTIFICIAL FILL (Q-C: Medium brown, medium dense, 1 CLAYEY SAND. Scattered concrete and asphaltic concrete debris and gravel up to 3 inches in diameter. 2 3 4 SC Very Old Paralic Deposits (Qvop,sl: Medium reddish - brown, moist, dense, mottled, fine to medium grained, CLAYEY SAND. 5 TERMINATED AT 5 FEET. NO GRAOUNDWATER OR SEEPAGE ENCOUNTERED 6 7 8 9 10 ECKE YMCA PRESCHOOL EXPANSION SOUTHERN CALIFORNIA & By: AKIN Date: September 1, 2009 SOIL & TESTING, INC. Job Number: 09111141 Figure: 1-3 APPENDIX 11 APPENDIX II LABORATORY TESTING SUMMARY Laboratory tests were performed to provide geotechnical parameters for engineering analyses. The following tests were conducted: • CLASSIFICATION: Field classifications were verified in the laboratory by visual examination. The final soil classifications are in accordance with the Unified Soil Classification System. • GRAIN SIZE DISTRIBUTION: A Grain size distribution was determined for one sample in accordance with ASTM D 422. The result of this test is presented on Figure II -1. • MAXIMUM DENSITY AND OPTIMUM MOISTURE CONTENT: The maximum density and optimum moisture content of one sample was determined in accordance with ASTM D 1557. The results are presented on Figure II -2. • DIRECT SHEAR: Direct shear tests were performed in accordance with ASTM D 3080. The shear stress was applied at a constant rate of strain of approximately 0.003 inch per minute. The results of these tests are presented on Figure 11 -3. Soil samples not tested are now stored in our laboratory for future reference and analysis, if needed. Unless notified to the contrary, all samples will be disposed of 30 days from the date of this report. 5 C fl Cobbles C Y 1 -W W 310- w sd 010 Nis 030 SQ&W 0100 0200 100 80 Coarse I Flne I Coarse Mwium I Fine 1 - — — -- 70 — — €� so 50 —� - G -- 4 20 - 10 — 1000 100 10 1 0.1 0.01 Grain Size In Millimeters Cobbles I vel I Sand j Sitt or Clay Coarse I Flne I Coarse Mwium I Fine SAMPLE LOCATION UNIFIED SOIL CLASSIFICATION: Sc ATTERSERG LIMITS HA -1 0 Od DESCRIPTION CLAYEY SANG LIO D UST L ASTIC LUAIY P PLASTICITY INDEX SOUTHERN CALIFORNIA SOIL 8 TESTING, INC. ECKE YMCA PRESCHOOL EXPANSION B GF Date: SspumWr t, 2009 .In61Jum1ur 09111141 Finurn• 11-1 MAXIMUM DENSITY & OPTIMUM MOISTURE CONTENT ASTM D 1557 -00 SAMPLE DESCRIPTION DRY DENSITY MOISTURE .� HA -1 @ 0 -5 ft Medium reddish -brown CLAYEY SAND 128.6 9.4 SOUTHERN CALIFORNIA SOIL & TESTING, INC. ECKE YMCA PRESCHOOL EXPANSION By: GF I Date: s.ptembx 1, 200 Job Number: 0811114 -1 Fi gure: II -2 F 1 50 46 40 33 W 3.0 5 2,5 y ti q 2.0 1.6 1.0 0.s 00 Direct Shear Test Results 0.0 0S +d 13 20 23 3.0 3.6 4.0 ..s &0 Confining Pressure (uerl INTERNAL COHESION FRICTION INTERCEPT SAMPLE DESCRIPTION i Ivor-) HA1 QO_5 SILTY SAND ■ Shear Strengtb at Q.2 inches of Deformation Remolded to 90% Relative Compaction Shear Strength at 36 202 0.2 inches of Deformation ECKE YMCA PRESCHOOL EXPANSION SOUTHERN CALIFORNIA SOIL & TESTING BY, GF IN Job Number: 09711141 FI ure: 11-3 • 00 OF 00 ON 0.0 0S +d 13 20 23 3.0 3.6 4.0 ..s &0 Confining Pressure (uerl INTERNAL COHESION FRICTION INTERCEPT SAMPLE DESCRIPTION ANGLE DEG. Ivor-) HA1 QO_5 SILTY SAND Remolded to 90% Relative Compaction Shear Strength at 36 202 0.2 inches of Deformation ECKE YMCA PRESCHOOL EXPANSION SOUTHERN CALIFORNIA SOIL & TESTING BY, GF Date: 9/2/2009 Job Number: 09711141 FI ure: 11-3