2015-12346 G (Plans)RIGHT OF WAY NOTE OWNER TO OBTAIN A CONSTRUCTION PERMIT FROM THE ENGINEERING DEPARTMENT AT LEAST 48 HOURS PRIOR TO WORKING IN THE PUBLIC RIGHT OF WAY. FAILURE TO DO SO WiLL RESULT IN AN ISSUANCE OF A STOP WORK NOTICE AND DOUBLE PERMIT FEES IT IS THE RESPONSIBLIBiTY OF THE OWNER TO KNOW WHERE THE LOCATION OF THE PROPERTY LINE IS. DRAINAGE NOTE NO CONCENTRATED DRAINAGE FLOWS ARE PERMITTED OVER ADJACENT PROPERTY LINES. WATER IS TO DRAIN AWAY FROM STRUCTURES FOR A MINIMUM OF 5 FEET AT 2 PERCENT AND BE CONVEYED TO AN APPROVED DRAINAGE FACILITY. UTILITY NOTE ALL UTILITIES SERVING THIS SITE SHALL BE INSTALLED UNDERGROUND. GENERAL N07ES 1. ALL WORK SHALL BE DONE IN ACCORDANCE K1774 THESE PLANS, THE STANDARD SPECIFICATIONS FOR PUBLIC WORKS CONSTRUCTION, THE DESIGN CONSTRUCTION STANDARDS OF THE CiTY OF ENCINITAS AND THE SAN DIEGO AREA REGIONAL STANDARD DRAWINGS. ANY CHANGES OR REVISIONS THEREFROM SHALL BE APPROVED BY THE CITY ENGINEER PRIOR TO ANY REQUEST FOR INSPECTION. 2. THE SOiLS REPORT AILED "UPDATED GE07ECHNICAL RECOMMENDATIONS PROPOSED NEW DUPLEX TO BE LOCATED AT 2111 EDINBURG AVE, CARDIFF -BY -THE -SEA, CA" PREPARED BY ENGINEERING DESIGN GROUP DATED APRIL 16, 2015 AND THE ORIGINAL LIMI7ED SITE INVESTIGATION TITLED "PROPOSED TWO -STORY DUPLEX OVER BASEMENTS AND DETACHED GARAGES" PREPARED BY EAST COUNTY SOIL CONSULTATION AND ENGINEERING, INC. DATED DECEMBER 16, 2004. ALL GRADING SHALL BE DONE IN ACCORDANCE WiTH THE RECOMMENDATIONS AND SPECIFICATIONS CONTAINED IN SAiD REPORTS. 3. SEPARATE APPROVALS AND PERMITS FOR ANY CONSTRUCTION WITHIN PUBLIC RIGHT -OF- WAY OR EASEMENTS SHALL BE REQUIRED IN CONJUNC77ON W17H IMPROVEMENT PLANS. 4. WRITTEN PERMISSION SHALL BE OBTAINED FOR ANY OFFSITE GRADING. 5. CONTRACTOR SHALL TAKE ANY NECESSARY PRECAUTIONS REQUIRED TO PROTECT ADJACENT PROPERTIES DURING GRADING OPERATIONS. ANYTHING DAMAGED OR ­DESTROYED SHALL BE REPLACED OR REPAIRED TO CONDITION EXISTING PRIOR TO GRADING 6. THE DEVELOPER SHALL BE RESPONSIBLE THAT ANY MONUMENT OR BENCH MARK WHICH IS DISTURBED OR DESTROYED SHALL BE RE- ESTABLISHED AND, REPLACED BY A REGISTERED CIVIL ENGINEER OR.A LICENSED LAND SURVEYOR. 7 THE CONTRACTOR SHALL DESIGN, CONSTRUCT AND MAINTAIN ALL SAFETY DEVICES, INCLUDING SHORING, AND SHALL BE RESPONSIBLE FOR CONFORMING TO ALL LOCAL, STATE AND FEDERAL SAFETY AND HEALTH STANDARDS, LAWS AND REGULATIONS. & GRADING AND EQUIPMENT OPERATING WITHIN ONE -HALF (1/2) MILE OF A STRUCTURE FOR HUMAN OCCUPANCY SHALL NOT BE CONDUCTED BETWEEN THE HOURS OF 5:30 P.M. AND 7.30 A.M. NOR ON SATURDAYS, SUNDAYS AND CITY RECOGNIZED HOLIDAYS. 9. NO GRADING OPERATIONS SHALL COMMENCE UN77L A PRE - CONSTRUCTION MEETING HAS BEEN HELD ONS17E WITH THE FOLLOWING PEOPLE PRESENT CITY INSPECTOR, CIVIL ENGINEER, SOILS ENGINEER, GRADING CONTRACTOR AND PERMITTEEE, THE PRE- CONSTRUCTION MEETING SHALL BE SCHEDULED WITH 7HE CITY AT LEAST 48 HOURS IN ADVANCE BY CALLING (760) 633 -2770. 10. PRIOR TO HAULING DIRT OR CONSTRUCTION MATERIALS TO ANY PROPOSED CONSTRUCTION SITE WITHIN THiS PROJECT THE DEVELOPER SHALL SUBMIT TO AND RECEIVE APPROVAL FROM THE CITY ENGINEER FOR THE PROPOSED HAUL ROUTE THE DEVELOPER SHALL COMPLY WITH ALL CONDITIONS AND REQUIREMENTS 774E CITY ENGINEER MAY IMPOSE WITH REGARDS TO THE HAULING OPERATION. 11. UPON FINAL COMPLETION OF THE WORK UNDER THE GRADING PERMIT, BUT PRIOR TO FINAL GRADING APPROVAL AND /OR FINAL RELEASE OF SECURITY, AN AS GRADED CERTIFICATION" SHALL BE PROVIDED STATING: "THE GRADING UNDER PERMIT NO. 12346 -G HAS BEEN PERFORMED IN SUBSTANTIAL CONFORMANCE K1774 THE APPROVED GRADING PLAN OR AS SHOWN ON THE ATTACHED AS- GRADED PLAN". THIS STATEMENT SHALL BE FOLLOWED BY THE DATE AND SIGNATURE OF THE CIVIL ENGINEER WHO CERTIFIES SUCH GRADING OPERATION. 12 ALL GRADING SHALL BE INSPECTED AND TESTED BY A QUALIFIED SOILS ENGINEER OR UNDER HIS DIRECTION HE SHALL INSPECT AND TEST 714E EXCAVATION PLACEMENT AND COMPACTION OF FILLS AND BACKFILLS AND COMPACTION OF TRENCHES. HE SHALL SUBMIT SOILS REPORTS AS REQUIRED AND WILL DETERMINE THE SUITABILITY OF ANY FILL MATERIAL. UPON COMPLETION OF GRADING OPERATIONS HE SHALL STATE THAT OBSERVATIONS AND TESTS WERE MADE BY HIM OR UNDER HIS SUPERVISION AND THAT IN HIS OPINION, ALL EMBANKMENTS AND EXCAVATIONS ARE ACCEPTABLE FOR THEIR INTENDED 13. THE CONTRACTOR SHALL PROPERLY GRADE ALL EXCAVATED SURFACES TO PROVIDE POSITIVE DRAINAGE AND PREVENT PONDING OF WATER. HE SHALL CONTROL SURFACE WATER AND AVOID DAMAGE TO ADJOINING PROPERTIES OR FINISHED WORK ON THE SITE AND SHALL TAKE REMEDIAL MEASURE TO PREVENT EROSION OF FRESHLY GRADED AREAS UN71L SUCH TIME AS PERMANENT DRAINAGE AND EROSION CONTROL MEASURES HAVE BEEN INSTALLED. 14. ALL AREAS TO BE FILLED SHALL BE PREPARED TO BE FILLED AND FILL SHALL BE PLACED IN ACCORDANCE WITH STANDARD SPECIFICATION. ALL VEGETABLE MATTER AND OBJECTIONABLE MATERIAL SHALL BE REMOVED BY THE CONTRACTOR FROM THE SURFACE UPON WHICH THE FILL iS TO BE PLACED. LOOSE FILL AND ALLUVIAL SOILS SHALL BE REMOVED TO SUITABLE FIRM NATURAL GROUND. THE EXPOSED SOILS SHALL BE SCARIFIED TO A DEPTH OF 12 INCHES AND THEN COMPACTED TO A MINIMUM OF 90 PERCENT IT SHALL BE THE CONTRACTOR'S RESPONSIBILITY TO PLACE, SPREAD, WATER AND COMPACT THE FILL IN STRICT ACCORDANCE IMTH SPECIFICATIONS 15. CUT AND FILL SLOPES SHALL BE CUT AND TRIMMED TO FINISH GRADE TO PRODUCE SMOOTH SURFACE AND UNIFORM CROSS SECTION. THE SLOPES OR EXCAVATION AND EMBANKMENTS SHALL BE SHAPED, PLANTED, AND TRIMMED AS DIRECTED BY THE ENGINEER OF WORK AND LEFT IN A NEAT AND ORDERLY CONDITION. ALL STONES, ROOTS AND OTHER WASTE MATTER EXPOSED OR EXCAVATION OR EMBANKMENT SLOPES WHICH ARE LIABLE TO BECOME LOOSENED SHALL BE REMOVED AND DISPOSED OF. THE TOE AND TOP OF ALL SLOPES SHALL BE ROUNDED IN ACCORDANCE WITH THE GRADING ORDINANCE. 16. ALL TREES, BRUSH, GRASS, AND OTHER OBJECTIONABLE MATERIAL SHALL BE COLLECTED, PILED OR OTHERWISE DISPOSED OF OFF THE Si7E BY THE CONTRACTOR SO AS TO LEAVE THE AREAS THAT HAVE BEEN CLEARED WITH A NET AND FINISHED APPEARANCE FREE FROM UNSIGHTLY DEBRIS. APPROVAL OF LOCATION OF DEBRIS FILL SHALL BE SECURED FROM THE SOILS ENGINEER AND CITY ENGINEER PRIOR TO THE DISPOSAL OF ANY SUCH MATERIAL. 17. THE REMOVAL OF ANY AND ALL CITY TREES SHALL BE CONSISTENT WITH THE CITY'S URBAN FOREST MANAGEMENT PROGRAM. TREES LOCATED WITHIN CITY STREET RIGHT -OF -WAY, ON CITY PROPERTY, OR WITHIN CITY EASEMENTS ARE REFERRED TO AS CITY TREES AND SHALL BE PROTECTED IN PLACE DURING CONSTRUCTION UNLESS SPECIFICALLY APPROVED OTHERWISE. NO GRADING, EXCAVATION, OR DISTURBANCE OF CITY TREE ROOT SYSTEMS SHALL OCCUR WITHIN THE CITY TREE DRIP LINE AREA (THE AREA FROM THE TRUNK OF A TREE TO THE OUTERMOST EDGE OF THE TREE CANOPY PROJECTION ON THE GROUND). IF A CITY TREE IS NOT CLEARLY LABELED TO BE REMOVED, IT MUST BE PROTECTED IN PLACE. EVEN IF APPROVED IMPROVEMENTS ARE IN CONFLICT WI7H A CITY TREE, IT MUST NOT BE DISTURBED UNLESS THE PLAN 1S REVISED TO ADDRESS THE TREE REMOVAL. NOTIFICATIONS 1. THE EXISTENCE AND LOCATION OF UNDERGROUND UTILITY PIPES AND STRUCTURES SHOWN ON THESE PLANS WERE OBTAINED BY A SEARCH OF AVAILABLE RECORDS. TO THE BEST OF OUR KNOWLEDGE THERE ARE NO EXISTING UTILITIES EXCEPT AS SHOWN ON THESE PLANS, HOWEVER. THE CONTRACTOR IS REQUIRED TO TAKE DUE PRECAUTIONARY MEASURES TO PROTECT ANY EXISTING UTILITIES OR STRUCTURES LOCATED AT THE WORK SITE IT IS THE CONTRACTOR'S RESPONSIBILITY TO CONTACT THE FOLLOWING OWNERS OF SAiD UTILITIES OR STRUCTURES PRIOR TO ANY EXCAVATION, FOR VERIFICATION AND LOCATION OF UTILITIES AND NOTIFICATION OF COMMENCEMENT OF WORK. A. SEWERS - CSD - (760) 633 -2600 B. GAS & ELECTRIC - SDGE - (760) -438 -6200 C. WATER - SDWD - (760) 633 -2650 D. TELEPHONE - SBC BELL - (760) -489 -3411 E. CABLE TV - COX COMMUNICA71ONS- (760)- 806 -9809 X -2233 2. CONTRACTOR SHALL NOTIFY THE CITY ENGINEER'S OFFICE 48 HOURS PRIOR TO BEGINNING ANY WORK ON THIS PROJECT. PHONE: (760)- 633 -2770. 3. THE CONTRACTOR SHALL GIVE 24 HOURS NOTICE ON CALLS FOR INSPECTION. PHONE: (760) -633 -2770. ALL WORK PERFORMED WITHOUT BENEFIT OF INSPECTION WILL BE SUBJECT TO REJECTION AND REMOVAL. III. EROSION CONTROL ppA1W SALMDW ( bl4) A Iq- Sl,l.q 1. iN CASE EMERGENCY WORK IS REQUIRED, CONTACT 24 HOURS A DAY. 2 EQUIPMENT AND WORKERS FOR EMERGENCY WORK SHALL BE MADE AVAILABLE AT ALL TIMES DURING THE RAINY SEASON (OCTOBER 1 TO APRIL 15�. ALL NECESSARY MATERIALS SHALL BE STOCKPILED ON SITE ON OCTOBER 1 AT CONVENi NT LOCATIONS TO FACILITATE RAPID CONSTRUCTION OF TEMPORARY EROSION CONTROL MEASURES WHEN RAIN IS IMMINENT. 3. DEVICES SHOWN ON PLANS SHALL NOT BE MOVED OR MODIFIED WITHOUT THE APPROVAL ' OF THE ENGINEERING INSPECTOR. 4. 771E CONTRACTOR SHALL RESTORE ALL EROSION CONTROL DEVICES TO WORKING ORDER TO THE SATISFACTION OF THE CITY ENGINEER AFTER EACH RUN -OFF PRODUCING RAINFALL. 5. 714E CONTRACTOR SHALL INSTALL ADDITIONAL EROSION CONTROL MEASURES AS MAY BE REQUIRED BY THE CITY ENGINEER DUE TO AN INCOMPLETE GRADING OPERATION OR UNFORESEEN CIRCUMSTANCES WHICH MAY ARISE. 6. THE CONTRACTOR SHALL BE RESPONSIBLE AND SHALL TAKE NECESSARY PRECAUTIONS TO PREVENT PUBLIC TRESPASS ONTO AREAS THAT ARE UNSAFE OR ARE POTENTIALLY UNSAFE. Z ALL EROSION CONTROL MEASURES PROVIDED PER THE APPROVED GRADING PLAN SHALL BE INCORPORATED HEREON. B. GRADED AREAS AROUND THE PROJECT PERIMETER MUST DRAIN AWAY FROM THE FACE OF SLOPE AT THE CONCLUSION OF EACH WORK DAY. 9. ALL REMOVABLE PROTECTIVE DEVICES SHOWN SHALL BE IN PLACE AT ME END OF EACH WORKING DAY WHEN THE FIVE (5) DAY RAIN PROBABILITY FORECAST EXCEEDS FORTY PERCENT (40 %). SILT AND OTHER DEBRIS SHALL BE REMOVED AFTER EACH RAINFALL. STORMWATER POLLUTION CONTROL POST CONSTRUCTION BMPAMP N07ES 1. FOR STORM WATER POLLUTION CONTROL PURPOSES, ALL RUNOFF FROM ALL IMPERVIOUS SURFACES INCLUDING ROOF DRAINS SHALL DISCHARGE ONTO GRASS AND LANDSCAPE AREAS PRIOR TO COLLECTION AND DISCHARGE ONTO THE STREET AND /OR INTO THE PUBLIC STORM DRAiN SYSTEM. 2 GRASS AND LANDSCAPE AREAS DESIGNATED FOR STORM WATER POLLUTION CONTROL SHALL NOT BE MODIFIED 107HOUT A PERMIT FROM THE CITY. 3. ALL IMPERVIOUS AREAS WITHIN THE Si7E SHALL DRAIN TO APPROVED BMPAIMP FACILITIES AND /OR TO TURF OR LANDSCAPED AREAS NTH ADEQUATE GROUNDCOVER PRIOR TO DISCHARGE FROM THE SITE. ALL IMPERVIOUS AREAS MUST SLOPE TOWARD THE APPROVED BMPAIMP FACILITY AND /OR THE TURF/LANDSCAPED AREAS. 4. NO DRAINS SHALL BE INSTALLED IN HARDSCAPE, DRIVEWAYS, OR ANY OTHER IMPERVIOUS AREA UNLESS 774E FLOW FROM THE DRAIN DISCHARGES TO AN ADEQUATE iMPABMP. 5. DRIVEWAYS SHALL HAVE A MINIMUM 2% CROSS SLOPE TOWARD THE IMPABMP AREA OR HAVE AN07HER APPROVED DRAINAGE SYSTEM THAT IS DESIGNED TO COLLECT RUNOFF AND DISCHARGE IT TO AN ADEQUATE IMPABMP. 6. ALL STORMWATER IMP/BMP FACILITIES SHOWN HEREON SHALL NOT BE MODIFIED OR ALTERED W11710UT A P MIT FROM THE CITY. Z THE INSTALLATION OF ADDITIONAL IMPERVIOUS SURFACES NOT SHOWN ON THIS PLAN MAY REQUIRE THAT THIS PLAN BE REVISED OR THAT A SEPARATE ENGINEERING PERMIT BE OBTAINED. & ALL EXIS77NG AND PROPOSED TRASH ENCLOSURES SHALL BE FITTED TO COMPLY WITH STORM WATER BEST MANAGEMENT PRACTICE REQUIREMENTS. THE TRASH ENCLOSURES SHALL HAVE AN IMPERVIOUS, NON- COMBUS77BLE ROOF 774AT WILL NOT ALLOW RAIN WATER TO ENTER THE ENCLOSURE THE ENCLOSURE SHALL BE LOCKABLE AND LOCKED WHEN NOT IN USE. A BERM SHALL BE INSTALLED AT ALL OPENINGS TO HOLD IN ANY LIQUIDS THAT ESCAPE FROM THE DUMPSTER AND TO PREVENT ANY FLOW OF STORM WATER THROUGH THE TRASH ENCLOSURE AREA. THE BERM CAN BE CONSTRUCTED WIDE AND FLAT TO ALLOW ROLLING OF THE DUMPS7ER IN AND OUT THE ENCLOSURE SHALL BE SELF CONTAINED OR MAY HAVE A DRAIN THAT DISCHARGES THROUGH AN ADEQUATELY SIZED OIL/ GREASE SEPARATOR AND IS THEN FILTERED THROUGH A CiTY- APPROVED HYDROCARBON FILTER AND DISCHARGED INTO THE PUBLIC SANITARY SEWER SYSTEM, NOT TO PLANTERS OR THE STORM DRAIN SYSTEM. A SEPARATE BUILDING PERMIT MAY BE REQUIRED FOR THIS STRUCTURE. ENW7RONMENTAL NOTES: 1. THE STEEPEST EXISTING SLOPE IN THE GRADED AREA IS N/A (EXCLUDING ANY EXISTING MAN MADE SLOPES). Z THE MAXIMUM VERTICAL DEPTH OF CUT IS 10.5 FT AND THE MAXIMUM VERTICAL HEIGHT OF FILL IS 0.25 FT 3. A.) AVERAGE DEP7H = VOLUME OF CUT (C.F.) = 4.5 FT OF CUT AREA OF CUT (SF.) B.) AVERAGE DEPTH = VOLUME OF FILL (C.F.) 0.2 FT OF FILL AREA OF FILL (S.F.) EARTHWORK DATA: 845 CUBIC YARDS EXCAVATION (CUT) 25 CUBIC YARDS EMBANKMENT (FILL) 820 CUBIC YARDS EXPORT 150 CUBIC YARDS REMEDIAL • ESTIMATE DOES NOT INCLUDE S7RIPPINGS UTILITY TRENCH VOLUMES OR ANY OVEREXCAVATION, iF REQUIRED BY SITE CONDITIONS CONTRACTOR SHALL SATISFY SELF THAT ESTIMATES ARE CORRECT PRIOR TO COMMENCEMENT OF WORK. EARTHWORK QUANTITIES ARE ESTIMATED FOR PERMIT PURPOSES ONLY. (CALCULATED ON A THEORETICAL BASIS. ACTUAL QUANTITIES MAY VARY DUE TO SHRINKAGE OR SWELL FACTORS). DEPTH & QUANTITY OF REMEDIAL GRADING IS SUBJECT TO FIELD VERIFICATION BY PROJECT SOILS ENGINEER IN FIELD DURING EXCAVATION STORMWAIER POLLUTION CONTROL BMP NOTES RELATIVE TO CONSTRUCTION AC71N71ES CONCRETE WASHOUT CM7RACTOR SHALL ESTABLISH AND USE AN ADEQUATELY SIZED CONCRETE WASHOUT AREA TO CONTAIN WASHOUT WASTES ON SITE IT IS ILLEGAL TO WASH CONCRETE, SLURRY, MORTAR, STUCCO, PLASTER AND THE LIKE INTO THE STORMWA7ER CONVEYANCE SYSTEM OR ANY RECEIVING WATER. CONTRACTOR SHALL POST A SIGN DESIGNATING THE WASHOUT LOCATION. CONSTRUCTION SITE ACCESS SITE ACCESS SHALL BE PROVIDE FOR VEHICLES EGRESS AND INGRESS TO PREVENT TRACKING DIRT OFF SITE. THiS SHALL INCLUDE USING MATERIAL SUCH AS GRAVEL AND /OR CORRUGATED STEEL PANELS/PLATES. CONSTRUCTION VEHICLES A SPECIFIC AREA ROM GUTTERS AND STORMDRAIN SHALL BE DESIGNATED FOR CONSTRUCTION VEHICLES PARKING, VEHICLE REFUELING, AND ROUTINE EQUIPMENT MAINTENANCE. ALL MAJOR REPAIRS SHALL BE MADE OFF -SITE EROSION CONTROL ER030V CDATRW MUST BE PROVIDED FOR ALL EROSIVE SURFACES. SLOPED SURFACES ESPECIALLY SHALL BE PROTECTED AGAINST EROSION BY INSTALLING EROSION RESISTANT SURFACES SUCH AS EROSION CONTROL MATS, ADEQUATE GROUND COVER VEGETATION, AND BONDED FIBER MATRIX. NO EXCAVATION AND GRADING ACTIVITIES ARE ALLOWED DURING WET WEATHER. DIVERSION DIKES SHALL BE CONSTRUCTED TO CHANNEL RUNOFF AROUND 714E CONSTRUCTION SITE CONTRACTOR SHALL PROTECT CHANNELS AGAINST EROSION USING PERMANENT AND TEMPORARY EROSION CONTROL MEASURES STORMWATER POLLUTION CONTROL BMP N07ES RELATIVE 70 CONSTRUCTION ACTIVITIES CONT. EROSION CONTROL CONT... REMOVE EXISTING VEGETATION ONLY WHEN ABSOLUTELY NECESSARY. LARGE PROJECTS SHALL BE CONDUCTED IN PHASES TO AVOID UNNECESSARY REMOVAL OF THE NATURAL GROUND COVER. DO NOT REMOVE TREES OR SHRUBS UNNECESSARILY; THEY HELP DECREASE EROSION. TEMPORARY VEGETATION MUST BE PLANTED ON SLOPES OR WHERE CONSTRUCTION IS NOT IMMEDIATELY PLANNED FOR EROSION CONTROL PURPOSES EROSION SHALL BE PREVENTED BY PLANTING FAST- GROINNG ANNUAL AND PERENNIAL GRASSES TO SHIELD AND BIND THE SOIL. PLANT PERMANENT VEGETATION AS SOON AS POSSIBLE, ONCE EXCAVATION AND GRADING ACTIVITIES ARE COMPLETE WATER USAGE FOR DUST CONTROL SHALL BE MINIMIZED. ON -SITE CONSTRUCTION MATERIAL STORAGE STORED MATERIALS SHALL BE CONTAINED IN A SECURE PLACE TO PREVENT SEEPAGE AND SPILLAGE CONTRACTOR SHALL STORE 774ESE PRODUCTS WHERE THEY HILL STAY DRY OUT OF THE RAIN. CONTRACTOR SHALL PROVIDE SECONDARY CONTAINMENT FOR ALL FUEL STORED ON -SITE. ELIMINATE OR REDUCE POLLUTION OF STORMWATER FROM STOCKPILES KEPT ON -S17E STOCKPILES MAY INCLUDE SOIL, PARING MATERIALS, ASPHALT CONCRETE, AGGREGATE BASE, ETC. STOCKPILES SHALL BE LOCATED AWAY FROM CONCENTRATED STORMWA7ER FLOWS AND STORMDRAIN INLETS. STOCKPILES SHALL BE COVERED OR PROTECTED K77H SOIL STABILIZATION MEASURES AND PROVIDED WITH A TEMPORARY SEDIMENT BARRIER AROUND THE PERIMETER AT ALL TIMES. TRAINING CONTRACTORS' EMPLOYEES WHO PERFORM CONSTRUCTION IN THE CITY OF ENCINITAS SHALL BE TRAINED TO FAMILIAR MTH THE CiTY OF ENCINITAS STORMWATER POLLUTION CONTROL REQUIREMENTS THESE BMP N07ES SHALL BE AVAILABLE TO EVERYONE WORKING ON SITE. THE PROPERTY OWNER(S) AND THE PRIME CONTRACTOR MUST INFORM SUBCONTRACTORS ABOUT STORMWA7ER REQUIREMENTS AND 774EIR OWN RESPONSIBILITIES. WASTE MANAGEMENT CONTRACTOR SHALL BE RESPONSIBLE FOR PROPERLY DISPOSING OF ALL WASTE AND UNUSED CONSTRUCTION MATERIALS. DUMPING OF UNUSED OR WASTE PRODUCTS ON THE GROUND, WHERE WATER CAN CARRY THEM INTO THE CONVEYANCE SYSTEM IS STRICTLY PROHIBITED. NO SEEPAGE FROM DUMPS7ERS SHALL BE DISCHARGED INTO STORMWA7ER. BERMSADTKES SHALL BE PLACED AROUND DUMPS7ERS TO DIVERT THE NATURAL STORM RUNOFF. DUMPSTERS SHALL BE CHECKED FREQUENTLY FOR LEAKS DUMPSTER LiDS SHALL REMAIN CLOSED AT ALL TIMES DUMPS7ERS WITHOUT LIDS SHALL BE PLACED WITHIN STRUCTURES WiTH IMPERVIOUS ROOFING OR COVERED W17H TARPS IN ORDER TO AVOID RAIN CONTACT WiTH ANY TRASH MATERIAL. MANY CONSTRUCTION MATERIALS INCLUDING SOLVENTS WATER -BASED PAINTS, VEHICLE FLUIDS, BROKEN ASPHALT AND CONCRETE, WOOD, AND CLEARED VEGETATION CAN BE RECYCLED. NON- RECYCLABLE MATERIALS MUST BE TAKEN TO AN APPROPRIATE LANDFILL OR DISPOSED OF AS HAZARDOUS WASTE FOR INFORMATION ON DISPOSAL OF HAZARDOUS MATERIAL, CALL THE HAZARDOUS WASTE HOTLINE TOLL FREE AT (800) 7114 -1195. FOR INFORMATION ON LANDFILLS AND TO ORDER DUMPS7ERS CALL EDCO AT (760) 436 -4151. POLLUTANTS SHALL BE KEPT OFF EXPOSED SURFACES. PLACE TRASH CANS AND RECYCLING RECEPTACLES AROUND THE SiTE PORTABLE TOILETS MUST BE IN GOOD WORKING ORDER AND CHECKED FREQUENTLY FOR LEAKS CONTRACTOR SHALL PROVIDE SECONDARY CONTAINMENT AND LOCATE PORTABLE TOILETS AWAY FROM STORMDRAIN INLETS ON PERVIOUS SURFACES. ALL CONSTRUCTION DEBRIS SHALL BE KEPT AWAY FROM THE STREET GUTTER, AND STORMDRAIN. CONTRACTOR MUST ROU77NELY CHECK AND CLEAN UP MATERIAL THAT MAY HAVE TRAVELED AWAY FROM CONSTRUCTION SITE FOR MORE INFORMATION ON STORMWA7ER POLLUTION CONTROL MEASURES AND REQUIREMENTS PLEASE CONTACT THE ENGINEERING DEPARTMENT, CITY OF ENCINITAS AT (760) 633 -2770. SAN DIEGUITO WATER DISTRICT NOTES 1. REVIEW OF THIS PLAN BY SAN DIEGUITO WATER DISTRICT DOES NOT CONSTITUTE REPRESENTATION AS TO THE ACCURACY OF, THE LOCATION OF OR THE EXISTENCE OR NON- EXISTENCE OF, ANY UNDERGROUND UTILITY, PIPE OR STRUCTURE WITHIN THE LIMITS OF THIS PROJECT. 2. ALL EXISTING FACILITIES, WHICH MAY AFFECT FINAL DESIGN, LE., LINE CROSSING, LINE PARALLELING OR PROPOSED CONNECTION SHALL BE FIELD VERIFIED. ALL EXISTING OR PROPOSED UTILITY CROSSING WITHIN 10 FEET OF PROPOSED WATER MAINS SHALL BE SHOWN ON IMPROVEMENT PLANS ELECTRICAL AND SEWER TO CROSS UNDER WATER MAINS UNLESS GIVEN WRITTEN PERMISSION BY SAN DIEGUITO WATER DISTRICT. 3. CONTRACTOR AND OWNER ARE RESPONSIBLE TO RELOCATE AND /OR ADJUST TO GRADE ANY EXIS77NG WATER FACILITY (FIRE HYDRANT METERS, VALVES, VALVE BOXES, ETC.) WHICH iS AFFECTED BY THEIR PROJECT. ALL AFFECTED WATER FACILITIES MUST MEET CURRENT WATER AGENCIES' STANDARDS COMMITTE (WASC) STANDARDS. IF FACILITIES DO NOT MEET STANDARDS, THEN THEY SHALL BE UPGRADED TO CURRENT STANDARDS AT THE OWNER'S EXPENSE 4. UTILITIES TO MAINTAIN MINIMUM 5 -FOOT SEPARATION WHEN PARALLELING WATER SERVICES. 5. MINIMUM HORIZONTAL SEPARATION OF 10 -FEET REQUIRED BETWEEN FiRE HYDRANTS AND SAN DIEGO GAS AND ELECTRIC VAULTS. 6. ALL WATER SERVICES TO BE CONSTRUCTED CLEAR OF DRIVEWAYS AND ALL OTHER TRAVELED WAYS WATER METERS MUST BE IN FRONT OF THE PARCEL THEY ARE SERVING. Z CALIFORNIA STATE LAW ASSEMBLY BILL AB -1953 IS REQUIRING THAT NO -LEAD BRASS BE USED IN THE CONSTRUCTION OR REPAIR OF ALL POTABLE WATER SYSTEMS EFFECTIVE JANUARY 1, 2010. IN COMPLIANCE WI7H THIS LAW, ME DISTRICT SHALL REQUIRE ALL MATERIALS TO BE NO -LEAD BRASS PARTS. & ALL COPPER TUBING USED FOR AIR RELEASES, BLOW OFFS, AND SERVICES SHALL BE PROVIDED WITH CATHODIC PR07EC71ON IN ACCORDANCE WITH WC -17 OR WC -18. LANDSCAPING 1. ALL SLOPES SHALL BE PLANTED AND IRRIGATED iN ACCORDANCE WITH PLANS APPROVED BY THE CITY ENGINEER. PLANS SHALL CONFORM TO THE CITY OF ENCINITAS GRADING ORDINANCE AND ALL ADOPTED LANDSCAPE AND IRRIGAT70N STANDARDS. Z FINISH GRADING AND PLANTING SHALL BE ACCOMPLISHED ON ALL SLOPES PRIOR TO OCTOBER 1 OR IMMEDIATELY UPON COMPLETION OF ANY SLOPES GRADED BETWEEN OCTOBER 1 AND APRIL 15. EXISTING IMPERVIOUS AREA PROPOSED IMPERVIOUS AREA NET CHANGE Z 305 SF 4,055 SF +1,750 SF 1,750 SF NET NEW TWIN HOME & HARDSCAPE AS BUILT BRIAN M. ARDOLINO R.C.E. NO. 71651 EXP. 12 -31 -1, 4 LEGEND BOTTOM OF STAIR ELEVATION S D.R.S.D. _ SAN DIEGO REGIONAL STANDARD DRAWINGS PROJECT PROPERTY LINE - - EXISTING RIGHT- OF- WAYAPROPERTY LINE FG = CENTERLINE OF ROAD - EXISTiNG EDGE OF PAVEMENT FF = h7NSHED FLOOR PROPOSED PERMANENT BMP AREA (NOT TO BE GARAGE FINISHED FLOOR IE = INVERT ELEVATION MODIFIED WITHOUT A PERMIT FROM THE CITY) TOP OF GRATE ELEVATION TIN = TOP OF WALL ELEVA 77ON PROPOSED LANDSCAPING RECOMMENDATIONS, HAS BEEN SUBMITTED TO THE OFFICE OF THE CITY PROPOSED POROUS PAVERS HAVE REVIEWED THESE GRADING PLANS AND CERTIFY THAT THE RECOMMENDATIONS INCLUDED IN THE SOILS REPORT FOR THIS PROJECT HAVE BEEN INCORP AIED III PLANS AND SPECIFICATIONS PROPOSED PCC ?DING ' PROPOSED AC PAVEMENT PROPOSED CONTOUR LINE 55 EXISTING CONTOUR LINE , uG PROPOSED FLOWLINE �-- PROPOSED SETBACKS PROPOSED RETAINING WALL SAN MARCOS, CALIFORNIA 92069 PROPOSED SITE WALL (NON RETAINING) 760 - 839 -7302 PROPOSED TEMPORARY SHORING WALL PROPOSED SAWCUT LINE PROPOSED PCC RIBBON GUTTER PROPOSED 4" PVC DRAIN PIPE - PROPOSED 4" SEWER LATERAL PER WAS SS -01 a S PROPOSED i" WATER SERVICE PER WAS WS -09 EXISTING 8" VCP SEWER MAIN - S EXIS77NG ACP WATER MAIN (SIZE PER PLAN) PROPOSED 6" AREA DRAIN ABBREVIATION LEGEND BS = BOTTOM OF STAIR ELEVATION BW = BOTTOM OF WALL ELEVATION FS = FINISHED SURFACE FG = FINISHED GRADE FL = FLOW LINE FF = h7NSHED FLOOR GF = GARAGE FINISHED FLOOR IE = INVERT ELEVATION TG = TOP OF GRATE ELEVATION TIN = TOP OF WALL ELEVA 77ON NITAS FIRE PROTECTION DI REVIEWED BY- / DATE DrA TE. wmvcn/rcnm, a nac I BRA- DLEt- �.- MFl1�STEE UNDER THE BRADLEY S. MUMMURR ti P.O. BOX 1131 , 07 SITE ADDRESS 2111 EDINBURG AVENUE CARDIFF, CA 92007 LEGAL DESCRIPTION LOTS 45 & 46 & S'tY 2.5 FT OF LOT 47 BLK 41 TR 1334 A.P.N.: 260 - 412 -33 OR HIS SUCCESSO ,L-� W 417' "I Llirz gj D 2 2500 I}OOV�e PcE MAR Dn NATIDNAL cmr, C* glaso VICINITY MAP (T.B.11147 -E7) NIS OWNER'S CERTIFlC47E IT IS AGREED THAT FIELD CONDITIONS MAY REQUIRE CHANGES TO THESE PLANS. IT IS FURTHER AGREED THAT THE OWNER (DEVELOPER) SHALL HAVE A REGISTERED CML ENGINEER MAKE SUCH CHANGES, ALTERATIONS OR ADDITIONS TO THESE PLANS WHICH THE CITY ENGINEER DETERMINES ARE NECESSARY FOR AND DESIRABLE FOR THE PROPER COMPLETION OF 774E IMPROVEMENTS. I HEREBY CERTIFY THAT A REGISTERED SOILS ENGINEER OR GEOLOGIST HAS BEEN OR WILL BE RETAINED TO SUPERVISE OVER ALk GRADING AC77WTY AND ADVISE OF THE COMPACTION AND STABILI F THE fE. BRAD AY FOR ViNG TRUST DA7% P.O. BOOX X CAR , CA 92007 SOILS ENGINEER'S CER77RCA7E MZL4rN LMOM FOIL WIFIz BUIWERy ING. bAr 1, Eawl 9IS1 A REGISTERED CIVIL ENGINEER iN THE STATE OF CALIFORNIA, PRINCIPALLY DOING BUSINESS IN THE FIELD OF APPLIED SOIL MECHANICS, HEREBY CERTIFY 774AT A SAMPLING AND STUDY OF THE SOIL CONDITIONS PREVALENT WITHIN THIS SITE WAS MADE BY iE OR UNDER MY DIRECTION BETWEEN THE DATES 4-11-14 AND '1 •�s . ONE COMPLETE COPY OF THE SOILS REPORT COMPILED FROM THIS STUDY, WIN MY RECOMMENDATIONS, HAS BEEN SUBMITTED TO THE OFFICE OF THE CITY ENGINEER, FURTHERMORE, i HAVE REVIEWED THESE GRADING PLANS AND CERTIFY THAT THE RECOMMENDATIONS INCLUDED IN THE SOILS REPORT FOR THIS PROJECT HAVE BEEN INCORP AIED III PLANS AND SPECIFICATIONS ?DING ' SIGNED: R E NO.: EiSIZ2 EXP. DATE 9 2011 ENGINEERING DESIGN GROUP 2121 MON71EL ROAD SAN MARCOS, CALIFORNIA 92069 760 - 839 -7302 IA., 4a 4, t, q7( to ",sin 714E UNDERSIGNED ENGINEER AGREES THAT THE WORK PERFORMED BY THE ENGINEER SHALL COMPLY WITH THE GENERALLY ACCEPTED STANDARDS AND PRACTICES OF THE ENGiNEEER'S TRADE OR PROFESSION. THE ENGINEER FURTHER AGREES THAT THE WORK PERFORMED HEREIN SHALL BE IN ACCORDANCE WITH THE RULES AND REGULATIONS REQUIRED BY THE CITY OF ENCINITAS THE ENGINEER AGREES THAT ANY PLANCHECK OR REVIEW PERFOMED BY THE CiTY OF ENCINITAS IN ITS CAPACITY AS A PUBLIC ENTITY FOR THE PLANS PREPARED BY THE ENGINEER IS NOT A DETERMINATION BY THE CITY OF ENCINITAS OF THE 7ECHINICAL SUFFFICIENCY OR ADEQUACY OF THE PLANS OR DESIGN, AND IT THEREFORE DOES NOT RELIEVE THE ENGINEER OF RESPONSIBUITY FOR THE PLANS OR DESIGN OF IMPROVEMENTS BASED THEREON. THE ENGINEER AGREES TO INDEMNIFY AND HOLD HARMLESS THE CITY OF ENCINITAS AND ITS OFFICERS, AGENTS, AND EMPLOYEES FROM PROPERTY DAMAGE OR BODILY INJURY ARISING SOLELY FROM THE NEGLIGENT ACTS, ERRORS, OR OMISSIONS OF THE ENGINEER AND HIS /HER AGENTS OR EMPLOYEES ACTING WITHIN THE COURSE AND SCOPE OF SUCH AGENCY AND EMPLOYMENT AND ARISING OUT OF THE WORK PERFORMED BY THE ENGINEER. BRIAN MICHAEL ARDOLINO DATE RCE No. 71651 PASCO LARET SU17ER & ASSOCIATES 535 N. COAST HiGHWAY 101 SOLANA BEACH CA, 92074 PLSA 2256 O 04ED ]120011rlaTJ_ir:1l:0•u- lralfl9 Vhi- - I ►t PASCO LARET SUITER & ASSOCIATES CIVIL ENGINEERING + LAND PLANNING + LAND SURVEYING 535 North Highway 101, Ste A, Solana Beach, CA 92075 ph 858.259.8212 1 fx 858.259.4812 1 plsaengineering.com PARKS & RECREATION No. 71651 Exp. 12/31/15 BUILDING PERMIT # F BMP STATUS: STANDARD i all Q4RmWel7:��7 R E D BY.• I !I/3 i DAW REVISIONS APPROVED DATE REFERENCES DATE BENCHMARK SCALE PLANNING & BUILDING DESIGNED DRBAK CHECKED APPROVALS CITY OF ENCINITAS ENGINEERING DEPARTMENT DRAWING NO. BAK 8AK BMA APPROVAL UPDATE &ND CITY OF ENCINITAS ENC -41, 2.5" BRASS DISC, �` PLANS PREPARED UNDER THE SUPERVISION OF RECOMMENDED SIW APPROV -D TITLE SHEET FOR: ow"Wt C{NANE�S EAST SIDE HWY. 101, 0.5 MILE NORTH OF nD CHESTERFIELD HORIZONAL N� %me SAOJ z _t� - \, DATE: 10-70-15 BY M E BY. GLENN PRMM 2� 1 EDINBURG AVENUE 12346 -G �• ) R.C.E. NO. 71651 S VERTICAL N/A ` BRIAN M. ARDOLINO ELEVATION. 73812' DATUM: NAVD88 EXP. 12 -31 -15 DATE: IZ/10 /IS pq�; /2 // �(f_OQ� Q A.P.N. #260- 412 -33 SHEET 1 OF 6 PREPARED: 312712015 REVISED: 6 2512015 REVISED: 911512015 PLSA 2256 EXISTING 8* VCP- SEWER PER CS0 7' D(ISING Is ACP WATER TWI PER SDW0 W.O. 54-22 APN; 260-412-32-00 2 - W.O. 76-2904 CONSTRUCTION NOTES- NOTES= INSTALL TWI APN.- 260-412-29-00 TO 11 7.0)-, C TO REMAIN EXISTING 12s CL- TWI TW=212.2 150 ACP WATER Rip RAP. DAYLIGHT W=2105. 7 (BW=207.51 MAIN PER 17) 1 z ­ I CONSTRUCT RETAINING WALL PER SORSD C-2 1. STORM WATER POLLUTION CONTROL BMPS TO BE PRIVATELY MAINTAINED AND NOT 70 BE MODIFIED WITHOUT A PERMIT FROM THE auffu PIPE THROUGH IMPROVEMENTS CIT Y. W.O. 82 -104 70 1 5 WALL, IL' 202;0 .65 TO DUSTING CONSTRUCT RETAINING WALL PER SDRSD C-4 REMAIN .2 7, TNI 4' 3.10) INSTALL 4" PVC SEWER LATERAL PER SORSO SS-01 W1 SEWER LATERAL 2 UTILITIES ARE KNOWN TO EXIST IN THE AREA. INFORMATION SHOWN HEREON IS PER BEST AVAILABLE RECORD INFORMATION. EXACT 1 "'j TC 01.8 2 HORIZONTAL AND VERTICAL LOCATION OF EXISTING UTILITIES UNKNOWN. CONTRACTOR TO FIELD VERIFY LOCATION OF DUSTING UTILITIES BW=202V 105"'If CLEANOUT TYPE 6 PER SC-01. CONTRACTOR TO VERIFY IL' ELEVATION EWE OF 1PRIOR TO ORDERING MATERALS AND CONSTRUCTION CONTRACTOR SHALL NOTIFY ENGINEER OF WORK OF ANY DISCREPANCIES BETWEEN EXIST PVMT 202. 3.36) CONSTRUCT f x 3' OPENING IN SITE WALL TO ALLOW DRAINAGE To ACTUAL LOCATION AND PLAN LOCATION OF U77LMES UPON DISCOVERY OF DISCREPANCY 10 FS- 202.5 PASS THROUGH EXISTING 112" PIPE SURVEY MONUMENT SHALL BE PROTECTED IN PLACE. 3 ALL EXISTING AND PROPOSED UTILITIES SERVING THIS SITE SHALL BE INSTALLED UNDERGROUND amm � e�- FL=21J.J6 (FS=201,05) 16.5' (FS=21J.73) MONUMENT SHALL BE REPLACED BY A LICENSED LAND SURVEYOR AND 4. ALL EXISTING ONSITE STRUCTURES TO BE DEMOLISHED. vlo4 vpAld FS=212.55o 2( SHALL FILE A CORNER RECORD WITH THE COUNTY IF DISTURBED INS-TALL INS OR DESTROYED. LIMP PAD - 2M42' IE=44.4 DRAIN PUMP =2 a4S8WMTFI FS=21 COI FULL MOT14 INSTALL 40 PERFORATED PVC DRAINAGE OUTLET PIPE TG=202.51 , "T 7 WELL j 5i 199.5 ALLAYSMA PfADflAfL .87 FWT LEM FF - 2nW FS- 212.9 FS=205.5 I " K I INSTALL 1.5' X 3' RIP RAP, I- THICK WITH BUBBLER OUTLET DEVICE IN= 1 Fit am row SHEL .84 .6 FS=21J.0 .87 .0 COMSPUILl P0AdUS =202.75 EXISTING STRUCTURE RYSB DISTRICT TO INSTALL I' COPPER WATER SERVICE AND DUAL METER FIRE DEPT NOTES-- "CC � wl' 70 BE,DEMOUSHED Fb214.56 PER WAS WS 09, WC-17 AT OWNER'S EXPENSE PAv 1A S P I A 09rhZ L .10 05.4 4., Was Sm9ff tot 07 04.0 LIGHT WELL �.L&W B.Ol (FS=214.93) EXISTING WATER SERVICE AT OWNER'S EXPENSE UNOBSTRUCTED VERTICAL CLEARANCE OF NOT LESS THAN 1J FEET 6 INCHES CRC 4 DISTRICT TO ABANDON Exis 1. ALL FIRE APPARATUS ACCESS SHALL HAVE AN rrl 503.21 FS=212.55 TC­_ a3 1 E=205.5 INSTALL 3' WIDE TRENCH RESURFACING PER CITY OF ENCINITAS (FS=202.14) ia ice UTILITY TRENCH BACKFILL AND RESURFACING STANDARD 2 FIRE ACCESS ROADS SHALL BE DESIGNED AND MAINTAINED TO SUPPORT THE IMPOSED LOADS OF NOT LESS THAN 75,000 POUNDS 2. _V._OZ 'IJ.6Z '15.0% CONSTRUCT TEMPORARY SHORING WALL PER DETAIL SHEET 4 AND SHALL BE PROVIDED WITH AN APPROVED PAVED SURFACE TO PROVIDE ALL-WEATHER DRIVING CAPABILITIES AMENDMENT 503.2.3 Nw. 260-4V-33 (FS=215.15) PAD - 22-4Z 1 14. -rAlL THIS SHWI J. THE GRADIENT FOR A FIRE APPARATUS ROADWAY- THIS GRADE SHALL NOT EXCEED 20%. GRADES EXCEEDING 15% (INCLINE OR FL= IE=203.5 BASEM99FF�-2MI7 fL=214.78 CONSI)RULl fi10AfTfAlrl0Af &ASIA/ 8RRV PEA #a INSTALL .95 FWT LEWL FF - 2nW i DECLINE) ON FIRE APPARATUS ACCESS ROADS SHALL NOT BE PERMITTED WITHOUT MITIGATION. III Pump ---_TC,=2OJ.66 FS=203.08 TRENCH: DRAW'zo lNSlALL'X-,,WDE PCC C-4 a T0=2031 I u"i I RIBBON GUTTER NOTE.- ALL AREA DRAIN AND ROOF DRAIN PIPES MUST FS-2130 '24.6 IN= IPB.5 -212 1 0 1.0% MIN. DAYLIGHT TO THE BIORETENTION BASINS, NOT DIRECTLY 24' -Al It 05.5 FS=215.3 TO THE STREET OR THE SUMP PUMP 3 205.4 r & 2. 0. (FS=216. 10) to _ FS= 6 FS 210.1 FS=2 52.1 N07E BASIN SUBDPAIN PIPES TO BE SLOPED 70WARD .85 7 FL- .82 7 2Z5' 25.0' lO j SUMP PUMP AND TO CONNECT TO SUMP PUMP 4, D� (FS=20J. 15) N '-ww 1 6.3' 4.6' J2.2' 4.3' 51, IWI B, (FS=216.44) W�F,212., F$i*21J.05 x (bW- IW=2125 FS=2IZ6 PROPOSED .5 TWI (BIVI IE=20I -(FL=215.88) PROPOSED PCC WALKWAY TW=212.8 1 .9 'BEGIN ALLEY IMPROVEMENTS. .1 .0 BW=205.7 (81#4 10. 1) 49=244-2 4E=20" !I(BIWI M PCC WALKWAY .6)) (B1#= 215.9) TRANSITION IMPROVEMENTS ENCROACHMENT MAINTENANCE AND REMOVAL COVENANT (FS=212.2) BWI BW=2OZ8 SOUTH AS NECESSARY 21110 40' APN- 260-412 4-00 i DUST. WA MEIER RECORDED AuG- .Y, 2015 AS DOCUMENT NO. (FS=208.5) - - - - - - - - - - APN-260-412-31-00 Ozj TIVI 15- ft ift OF OFFFIC14L RECORD. 20' 20' ,_TO REIM 20 BW=205.7 BWI 7 EDGE OF EXIST. PWT a4SEMBYr FF 2017 EXISi1NG PAD - 2" j GRADING PLAN GRADE --------- CoNSrRUGT SCALE. l--10' CONSTRUCT SHORING WALL SHORING WALL PER DETAIL PER DETAIL SHEET + SHEET 4 2.5' 1'1 5.3' 11.5' UVIff OF STARS ABOVE INSTALL POROUS =P PER INSTALL 4" PVC WWR9? S FS-025 DUN PIPE RECOMMEN610ONS IE=202.0 FS=202. 0 INSTALL 6 X 16 INSTALL RETAINING PCC FLUSH CURB J 1 WALL PER SORSD C-4 BIORETENTION AREA INSTALL 1.5'X 1.5' PER DETAIL THIS SHEET RIP RAP, I' THICK NOT TO SCALE No. 71651 Exp. 12/31/15 VCP SEWER 2 GRIND AND OVERLAY EXISTING 12" ACP INSTALL 6' THICK INSTALL 6" CLASS TYPICAL SECTION - EDINBURG AVENUE WATER MAIN PCC RIBBON GUTTER Y BASE UNDER PCC CO AC NOT TO SCALE IF DA%IJ URET SUITER GRAPHIC SCALE 111=101 & ASSOCIATES TYPICAL SECTION - RIBBON GUTTER CIVIL ENGINEERING + LAND PLANNING + LAND SURVEYING NOT TO SCALE 535 North Highway 101, Ste A, Solana Beach, CA 92075 10 0 10 20 30 Aph 858.259.82121 fK 858.259.4812 1 plsaengineering.com REVISIONS APPROVED DATE REFERENCES DATE BENCHMARK SCALE AS BUILT DESIGNED By . 7�DRACANK By 7cHECKEC By APPROVALS I I BAK CITY OF ENCINITAS ENGINEERING DEPARTMENT DRAWING NO. CITY OF ENCINITAS ENC-41, 2.5" BRASS DISC, D UNDER THE SUPERVISION OF RECOMMENDED GRADING PLAN FOR. EAST SIDE HWY. 101, 0.5 MILE NORTH OF HORIZONTAL 1" P NS POE7,ARED DATE. :0,4015 BY. _oe APPROVE Z � CHESTERFIELD. _zlA, LA BY. G 01 ShOd 2111 EDINBURG AVENUE 12346 se-Nora WwLiwo DATE MASH MAHER GLENN PRUIM VERTICAL NIA TO- 1 R.C.E. NO. 71651 Coll BRIAN M. ARDOLINO EXP. 12-31-15 124110/15 A.P.N. #260-412-33- -1--lIELEVATION. 73.612' DATUM, NAVDBB It-li. K DATE. DATE: 001 SHEET 2 0771 PREPARED: 312712015 REVISED: 612512015 REVISED: 911512015 PLSA 2256 INSTALL LARGE COBBLE OR R/W 1.5, 2.8' 1.8, 1.7' VEGETATION ON OVERFLOW EDGES R/W TO ENSURE EROSION DOES NOT DROUGHT TOLERANT 2- HARDWOOD MULCHI 15, OCCUR TO THE SAIISFAC77ON OF PLANTS ((Ty GRASS COVER OR CITY Z5' Z5' THE CITY INSPECTOR AND **!SET PRO QUIVALE7ri NOTE BELOW 2-0X 2A% 2.0% ENGINEER OF WORK 2% 014 buWSL lz 6 LINER ON PRIVATE PROPERTY VARIES VARIES SIDE oNLI ag PER (EII INSTALL 6* X 6' CONSTRUCT MIN. 4' AC OVER 60 2m GRIND AND PCC FLUSH CURB 24' LAYER ENGINEERED SOIL III CLASS I/ FA OVERLAY INSTALL 40 AC *SEE NOTE BELOW SECTION TO BE DETERMINED BY fDX(lS0nNG OVER 60 FILL OPENINGS IN PAVER CLASS /I AB UN17S WITH 118 TO J/8' SOIL ENGINEER BASED ON IN PAVEMENT AGGREGATE 2' LAYER OF SITU R-VALUE TESTING. EXISTING 4* CONSTRUCT 3' X 6' SAWCUF INSTALL 60 X l6p PCC FLUSH CURB 120 SUB BASE COURSE 318* GRAVEL EXTEND BASE C E RIBBON GUTTER ACP WATER MAIN PCC RIBBON GUTTER LINE LAYER 112- TO 314- CIVCA 6" LLASS 2 19*19 4' WE COURSE ANGULAR ROCK j 12' LAYER OF 314 GRAVE; TYPICAL SECTION ALLEY LAYER 318- TO 112- 2' BIDDING COURSE LAYER AGGREGATE 118- TO 318' AGGREG47E **SEE N07E BELOW NOT TO SCALE' NOTE.- 4' PERFORATED PVC SUBDRAJN PIPE PAVER INSTALLATION SHALL BE PER MANUFACTURER'S RECOMMENDATIONS PAVER SECTION NO LINER NOTE. 4' PIPE SHALL BE CENTERED IN IF IS SHOWN FOR REFERENCE ONLY. PAVER SECTION IS REQUIRED TO MAINTAIN IMPOSED BE USED 8MP AND RUN ENTIRE LMTH SHALL BE CONNECT 70 SUMP PUM OF BMP P LOADS OF NOT LESS THAN 75,000 LBS 40' BIORETENTION 'ENGINEERED SOIL" LAYER SHALL BE MINIMUM 24" DEEP %WDY LOAM' 20' 20' PERVIOUS PAVER PARKING AREA TO BE MAINTAINED BY HOMEOWNER PER ENCROACHMENT SOIL MIX WITH NO MORE THAN 5% CLAY CONTENT. THE MIX SHALL CONTAIN 50-60% MAINTENANCE AND REMOVAL COVENANT DOC I AQtL- _4'/mI SAND, 20-30% COMPOST OR HARDWOORD MULCH, AND 20-30% TOPSOIL, FREE OF I REC Au&-Y4200 STONES STUMPS ROOTS OR SIMILAR OBJECTS AND ALSO FREE OF NOXIOUS WEEDS 11.5' 125' 24' MIN 3.5's TYPICAL SECTION - POROUS PAVERS 314' CRUSHED ROCK LAYER SHALL BE A MINIMUM OF 12m BUT MAY BE DEEPENED f XISTING 15 28' TO INCREASE THE INFILTRATION AND STORAGE ABILITY OF THE DETAIL THE EFFECTIVE GRADE NOT TO SCALE AREA OF THE BASIN SHALL BE LEVEL AND SHALL BE SIZED BASED ON CALCULATION. VARIES TYPICALLY, THE SURFACE AREA OF THE BIORETENTION BASIN IS 4% OF THE IMPERVIOUS INSTALL 6' X 16' AREA DRAINING TO IT. ALL BIORETEN77ON PLANTERS TO BE DEPRESSED AT LEAST 6' PCC FLUSH CURB BELOW ADJACENT FINISHED SURFACE INSTALL POROUS PAVERS PER MANUFACTURERS * * *BIORETENTION DROUGHT TOLERANT PLANTS SWILL BE SELECTED FROM APPROVED RECOMMENDATIONS 3' PLANT PALETTE AS LISTED IN APPENDIX E OF COUNTY OF SAN DIEGO LOW IMPACT EXISTING FLOW LINE INSTALL 6' X 16* 6'_ DEVELOPMENT HANDBOOK. EXIS71NG AC P CC FLUSH CURB la BIORETENTION AREA DETAIL PAVEMENT TO REMAIN INSTALL 4' AC OVER III NOT TO SCALE ExIS®RI 80 6* CLASS If BASE 1 2.5' 1'1 5.3' 11.5' UVIff OF STARS ABOVE INSTALL POROUS =P PER INSTALL 4" PVC WWR9? S FS-025 DUN PIPE RECOMMEN610ONS IE=202.0 FS=202. 0 INSTALL 6 X 16 INSTALL RETAINING PCC FLUSH CURB J 1 WALL PER SORSD C-4 BIORETENTION AREA INSTALL 1.5'X 1.5' PER DETAIL THIS SHEET RIP RAP, I' THICK NOT TO SCALE No. 71651 Exp. 12/31/15 VCP SEWER 2 GRIND AND OVERLAY EXISTING 12" ACP INSTALL 6' THICK INSTALL 6" CLASS TYPICAL SECTION - EDINBURG AVENUE WATER MAIN PCC RIBBON GUTTER Y BASE UNDER PCC CO AC NOT TO SCALE IF DA%IJ URET SUITER GRAPHIC SCALE 111=101 & ASSOCIATES TYPICAL SECTION - RIBBON GUTTER CIVIL ENGINEERING + LAND PLANNING + LAND SURVEYING NOT TO SCALE 535 North Highway 101, Ste A, Solana Beach, CA 92075 10 0 10 20 30 Aph 858.259.82121 fK 858.259.4812 1 plsaengineering.com REVISIONS APPROVED DATE REFERENCES DATE BENCHMARK SCALE AS BUILT DESIGNED By . 7�DRACANK By 7cHECKEC By APPROVALS I I BAK CITY OF ENCINITAS ENGINEERING DEPARTMENT DRAWING NO. CITY OF ENCINITAS ENC-41, 2.5" BRASS DISC, D UNDER THE SUPERVISION OF RECOMMENDED GRADING PLAN FOR. EAST SIDE HWY. 101, 0.5 MILE NORTH OF HORIZONTAL 1" P NS POE7,ARED DATE. :0,4015 BY. _oe APPROVE Z � CHESTERFIELD. _zlA, LA BY. G 01 ShOd 2111 EDINBURG AVENUE 12346 se-Nora WwLiwo DATE MASH MAHER GLENN PRUIM VERTICAL NIA TO- 1 R.C.E. NO. 71651 Coll BRIAN M. ARDOLINO EXP. 12-31-15 124110/15 A.P.N. #260-412-33- -1--lIELEVATION. 73.612' DATUM, NAVDBB It-li. K DATE. DATE: 001 SHEET 2 0771 PREPARED: 312712015 REVISED: 612512015 REVISED: 911512015 PLSA 2256 314" MIN COARSE AGGREGATE FILTER FABRIC ,° a° °d ° 1.0' MIN., UNLESS OTHERWISE SPECIFIED BY A SOILS ENGINEER SECTION A —A APN.- 260 - 412 -32 -00 — GRADE INTERVAL LESS THAN 2% 100' 2% TO 4% 50' 4% TO 6% tT 6% TO 8% 25' BENCHMARK ��ui��0 AS BUILT DESIB CHEMED BY APPROVALS CITY OF ENCINITAS ENGINEERING DEPARTMENT i �.3 CITY OF ENCINITAS ENC -41, 2.5" BRASS DISC, EAST SIDE H . 101, 0.5 MILE NORTH OF ELEVATION: 73.612' DATUM: NAW88 111PER i �'�`�� PLANS PREPARED UNDER �.� BRIAN M. ARDOLINO , RECOMMENDED APPROV D BY: BY: MASIH MAHE LEN PRUIM pq 12/10/15 DATE: EROSION CONTROL PLAN FOR. 2111 E D I N B U R G AVENUE N U E A.P.N. #260- 412 -33 -00 12346 -G i i �n.l A,k�aLl'� -t0 DATE �� �L�1'I°l SHEET 3 OF 6 314" MIN COARSE AGGREGATE FILTER FABRIC ,° a° °d ° 1.0' MIN., UNLESS OTHERWISE SPECIFIED BY A SOILS ENGINEER SECTION A —A APN.- 260 - 412 -32 -00 — <r EROSION CONTROL PLAN SCALE: i' =10' NOTE: CONTRACTOR TO MODIFIY CONSRUCTION ENTRANCE IN THE FIELD AS NECESSARY CONSTRUCT SEDIMENT BARRIER AND CHANNELIZE RUNOFF TO SEDIMENT TRAPPING DEVICE A ORIGINAL U�j ® ° d ° GRADE v ° ° ° ° ° ° a ° e ° � a ti • ° 4 44 s a • °d 4, ° KM20'RADIUS A IN. 20' MIN DETAIL A: CONSTRUCTION ENTRANCE NOT TO SCALE WIDTH AS REQUIRED TO ACCOMODATE ANTICIPATED TRAFFIC RUNOFF GAP BETWEEN BAGS ACTS AS SPILLWAY APN-- 260 - 412 -29 -00 15' � O • GRADE INTERVAL LESS THAN 2% 100' 2% TO 4% 50' 4% TO 6% tT 6% TO 8% 25' BENCHMARK ��ui��0 AS BUILT DESIB CHEMED BY APPROVALS CITY OF ENCINITAS ENGINEERING DEPARTMENT DRAWING NO. �.3 CITY OF ENCINITAS ENC -41, 2.5" BRASS DISC, EAST SIDE H . 101, 0.5 MILE NORTH OF ELEVATION: 73.612' DATUM: NAW88 111PER <r EROSION CONTROL PLAN SCALE: i' =10' NOTE: CONTRACTOR TO MODIFIY CONSRUCTION ENTRANCE IN THE FIELD AS NECESSARY CONSTRUCT SEDIMENT BARRIER AND CHANNELIZE RUNOFF TO SEDIMENT TRAPPING DEVICE A ORIGINAL U�j ® ° d ° GRADE v ° ° ° ° ° ° a ° e ° � a ti • ° 4 44 s a • °d 4, ° KM20'RADIUS A IN. 20' MIN DETAIL A: CONSTRUCTION ENTRANCE NOT TO SCALE WIDTH AS REQUIRED TO ACCOMODATE ANTICIPATED TRAFFIC RUNOFF GAP BETWEEN BAGS ACTS AS SPILLWAY APN-- 260 - 412 -29 -00 15' � O • GRADE INTERVAL LESS THAN 2% 100' 2% TO 4% 50' 4% TO 6% tT 6% TO 8% 25' BENCHMARK ��ui��0 AS BUILT DESIB CHEMED BY APPROVALS CITY OF ENCINITAS ENGINEERING DEPARTMENT DRAWING NO. �.3 CITY OF ENCINITAS ENC -41, 2.5" BRASS DISC, EAST SIDE H . 101, 0.5 MILE NORTH OF ELEVATION: 73.612' DATUM: NAW88 HORIZONTAL 1 " =i0' VERTICAL N/A �'�`�� PLANS PREPARED UNDER �.� BRIAN M. ARDOLINO THE SUPERVISION OF DATE: i® zai5 R.C.E. NO. 71651 EXP. 12 -31 -15 RECOMMENDED APPROV D BY: BY: MASIH MAHE LEN PRUIM pq 12/10/15 DATE: EROSION CONTROL PLAN FOR. 2111 E D I N B U R G AVENUE N U E A.P.N. #260- 412 -33 -00 12346 -G 6 �n.l A,k�aLl'� -t0 DATE �� �L�1'I°l SHEET 3 OF 6 PREPARED: 312712015 REVISED: 612512015 REVISED: 911512015 PLEA 2256 m IOEM �:c� !711'1 119 0 M It E <r EROSION CONTROL PLAN SCALE: i' =10' NOTE: CONTRACTOR TO MODIFIY CONSRUCTION ENTRANCE IN THE FIELD AS NECESSARY CONSTRUCT SEDIMENT BARRIER AND CHANNELIZE RUNOFF TO SEDIMENT TRAPPING DEVICE A ORIGINAL U�j ® ° d ° GRADE v ° ° ° ° ° ° a ° e ° � a ti • ° 4 44 s a • °d 4, ° KM20'RADIUS A IN. 20' MIN DETAIL A: CONSTRUCTION ENTRANCE NOT TO SCALE WIDTH AS REQUIRED TO ACCOMODATE ANTICIPATED TRAFFIC RUNOFF GAP BETWEEN BAGS ACTS AS SPILLWAY APN-- 260 - 412 -29 -00 15' � O • Ill TWO LAYERS OF GRAVEL BAGS WITH ENDS OVERLAPPED O INSTALL STORM DRAW INLET PR07EC71ON PER CALIFORNIA STORMWATER QUALITY ASSOCIA71ON STORMWATER BEST MANAGEMENT PRACTICE HANDBOOK, NOV 2009 EDITION (CA BMP HANDBOOK) FACT SHEET SE -6 & SE -10, DI PR07EC77ON TYPE 3 WITH GRAVEL BAGS; SEE DETAIL. O2 INSTALL SILT FENCE PER CA BMP HANDBOOK FACT SHEET SE -1 O INSTALL TEMPORARY 6' HIGH CHAIN LINK CONSTRUCTION FENCE WITH SCREENING ® INSTALL STABILIZED CONSTRUCTION ENTRANCE PER CA BMP HANDBOOK FACT SHEET TC -1 (ADJUST SIZE AS REQUIRED) O CONTRACTOR TO INSTALL SOIL BINDER IN ACCORDANCE WITH CASQA BMP EC -05 (OR CITY APPROVED EQUIVALENT) PRIOR TO FORECASTED RAIN EVENT. 1. SET POSTS AND EXCAVATE A 4 BY 4 IN (10 BY 10 CM) TRENCH UPSLOPE FROM AND ALONG THE LINE OF POSTS J. ATTACH THE FILTER FABRIC TO THE WIRE FENCE AND EXTEND IT INTO THE TRENCH. 2 STAPLE WIRE FENCING TO THE POSTS. 77S �4 IN (10 CM) 4. BACKFILL AND COMPACT THE EXCAVATED SOIL. FILTER FABRIC Q/ WIRE _ DETAIL C: SILT FENCE NOT TO SCALE BAGS Q3 ao J 1 m z� W. MAVR SAO ROW SPACAG TABLE GRADE INTERVAL LESS THAN 2% 100' 2% TO 4% 50' 4% TO 6% tT 6% TO 8% 25' BENCHMARK SCALE AS BUILT DESIB CHEMED BY APPROVALS CITY OF ENCINITAS ENGINEERING DEPARTMENT DRAWING NO. �.3 Ill TWO LAYERS OF GRAVEL BAGS WITH ENDS OVERLAPPED O INSTALL STORM DRAW INLET PR07EC71ON PER CALIFORNIA STORMWATER QUALITY ASSOCIA71ON STORMWATER BEST MANAGEMENT PRACTICE HANDBOOK, NOV 2009 EDITION (CA BMP HANDBOOK) FACT SHEET SE -6 & SE -10, DI PR07EC77ON TYPE 3 WITH GRAVEL BAGS; SEE DETAIL. O2 INSTALL SILT FENCE PER CA BMP HANDBOOK FACT SHEET SE -1 O INSTALL TEMPORARY 6' HIGH CHAIN LINK CONSTRUCTION FENCE WITH SCREENING ® INSTALL STABILIZED CONSTRUCTION ENTRANCE PER CA BMP HANDBOOK FACT SHEET TC -1 (ADJUST SIZE AS REQUIRED) O CONTRACTOR TO INSTALL SOIL BINDER IN ACCORDANCE WITH CASQA BMP EC -05 (OR CITY APPROVED EQUIVALENT) PRIOR TO FORECASTED RAIN EVENT. 1. SET POSTS AND EXCAVATE A 4 BY 4 IN (10 BY 10 CM) TRENCH UPSLOPE FROM AND ALONG THE LINE OF POSTS J. ATTACH THE FILTER FABRIC TO THE WIRE FENCE AND EXTEND IT INTO THE TRENCH. 2 STAPLE WIRE FENCING TO THE POSTS. 77S �4 IN (10 CM) 4. BACKFILL AND COMPACT THE EXCAVATED SOIL. FILTER FABRIC Q/ WIRE _ DETAIL C: SILT FENCE NOT TO SCALE BAGS Q3 ao J 1 m z� W. MAVR SAO ROW SPACAG TABLE GRADE INTERVAL LESS THAN 2% 100' 2% TO 4% 50' 4% TO 6% 40' 6% TO 8% 25' DETAIL D: GRAVEL BAG CHEVRONS NOT TO SCALE EROSION CONTROL LEGEND CONSTRUCTION ENTRANCE PER DETAIL A GRAVEL BAGS PER DETAIL B 000 SILT FENCE PER DETAIL C X HYDROSEED NOTES 1. HYDROSEEDING SHAL BE APPLIED TO ALL SLOPES THAT ARE GRADED 6:1 (HORIZONTAL TO VERTICAL) OR STEEPER WHEN THEY AREA: A. THREE FEET OR MORE IN HEIGHT IN FILL AREAS B. FIVE FEET OR MORE IN HEIGHT IN CUT AREAS UNLESS SLOPE IS NOT SUBJECT TO EROSION DUE TO THE EROSION RESISTANT CHARACTER OF 774E MATERIAL AS APPROVED BY THE CITY ENGINEER. 2. IRRIGATION SHALL MAINTAIN THE MOISTURE LEVEL OF THE SOIL AT THE OP77MUM LEVEL FOR THE GROWTH OF THE HYDROSEEDED GROWTH. 3. HYDROSEEDING MIX SHALL CONSIST OF ALL THE FOLLOWING: A. SEED MIX SHALL CONSIST OF NO LESS THAN, 1. 20 LBS PER ACRE OF ROSE CLOVER 2. 20 LBS PER ACRE OF ZORRO FESCUE 3. 3 LBS PER ACRE OF E SCHOOL CIA CALIFORNICA 5. 3 8S PER ACRE OF ALYSSUM {CARPET OF SNOW) 6. 1� LB PER ACRE OF DIMORPHOLECA WHE111TTTREEEEEEE THE APEA BEING HYDROSEEDED ISONOT VISIBLOMITTED R ITTHER AAPUBLIC STREET OR RESIDENTIAL STRUCTURES. 8. 17EM A OF THIS SUBSECTION MUST BE INOCULATED WITH A NITROGEN FIXING BACTERIA AND APPLIED DRY EITHER BY DRILLING OR BROADCASTING BEFORE HYROSEEDING. 9. ALL SEED MATERIALS SHALL BE TRANSPORTED TO THE JOBSI7E IN UNOPENED CONTAINERS WITH THE CALIFORNIA DEPARTMENT OF FOOD AND AGRICULTURE CERTIFICATION TAG ATTACHED TO, OR PRINTED ON SAID CONTAINERS 10. NON —PHYTO —TOXIC WETTING AGENTS MAY BE ADDED TO THE HYDROSEED SLURRY AT THE DISCRETION OF THE CONTRACTOR. B. TYPE 1 MULCH APPLIED AT THE RATE OF NO LESS THAN 2,000 LBS PER ACRE. TYPE 6 MULCH (STRAW) MAY BE SUBSTITUTED, ALL OR PART, FOR HYDRAULICALLY APPLIED FIBER MATERIAL. WHEN STRAW IS USED IT MUST BE ANCHORED TO THE SLOPE BY MECHANICALLY PUNCHING NO LESS THAN 50% OF THE STRAW INTO THE SOIL. C. FERTILIZER CONSISTING OF AMMONIUM PHOSPHATE SULFATE, 16 -20 -0, WHITH 15% SULFUR APPLIED AT THE RATE OF 500 LBS PER ACRE. 4. AREAS TO BE HYDROSEEDED SHALL BE PREPARED PRIOR TO HYDROSEEDING BY: A. ROUGHENING 774E SURFACE TO BE PLANTED BY ANY OR A COMBINATION OF: 1. TRACK WALKING SLOPES STEEPER THAN 6:1. 2. RIPPING AREAS THAT WILL NOT BREAK UP USING 17EM 1 ABOVE. B. COND1770NING THE SOILS SO THAT IT IS SUITABLE FOR PLANTING BY 1. ADJUS77NG THE SURFACE SOIL MOISTURE TO PROVIDE A DAMP BUT NOT SATURATED SEED BED. 2. THE ADDITION OF SOIL AMENDMENTS, PH ADJUSTMENT, LEACHING OR COVERING SALINE SOILS TO PROVIDE VIABLE CONDITIONS FOR GROWTH. HYDROSEEDED AREAS SHALL BE MAINTAINED TO PROVIDE A VIGOROUS GROWTH UNTIL THE PROJECT IS PERMANENTLY LANDSCAPED OR, FOR AREAS WHERE HYDROSEEDING IS THE PERMANENT LANDSCAPING, UNTIL THE PROJECT IS COMPLETED AND ALL SECURITY RELEASED. ADJACENT PROPERTY DISTURBANCE NOTE THIS PLAN IS ENTIRELY WITHIN THE APPLICANT'S PROPERTY. CENT PROPER77ES IS ANTICIPATED AS A RESULT OF ANY ETTER OF PERMISSION FROM THE ADJACENT PROPERTY OWNER ITTED TO THE CITY PRIOR TO START OF ANY SUCH WORK. JACENT PRIVATE PROPERTY THAT HAS NOT BEEN PREVIOUSLY 'UBMITTED TO THE CITY IS GROUNDS FOR A STOP —WORK TO UNTIL 774E REQUIRED PERMISSION IS OBTAINED. ADDITIONAL N07ES WENT 2 NO DIRECTLY CONNECTED IMPERVIOUS AREAS (DCIA) SHALL BE ALLOWED. OCIA MEANS STORM RUNOFF GENERATED AND CONVEYED VIA IMPERVIOUS AREAS, SUCH AS ROOF, ROOF DRAIN, DRIVEWAY, AND STREET. 3. ALL PARCELS ARE SUBJECT TO ARCHITECTURAL DESIGN GUIDELINES FOR FUTURE SINGLE — FAMILY RESIDENTIAL DEVELOPMENT. THESE GUIDELINES ARE AVAILABLE AT CITY HALL (505 S. VULCAN AVE, ENCINITAS, CA 92024) AND ARE APPROVED AS PER PC RES. 2006 -27. No. 71651 Exp. 12/31/15 DETAIL B: GRAVEL BAGS NOT TO SCALE ff GRAPHIC SCALE 1"=10' 10 0 10 20 30 PASCO LARET SUITER & ASSOCIATES CIVIL ENGINEERING + LAND PLANNING + LAND VURVEYING 535 North Highway 101, Ste A, Solana Beach, . ^.A 92075 ph 858.259.8212 1 fr 858.259.4812 1 plsaengineering.com REVISIONS APPROVED DATE REFERENCES DATE BENCHMARK SCALE AS BUILT DESIB CHEMED BY APPROVALS CITY OF ENCINITAS ENGINEERING DEPARTMENT DRAWING NO. K BAK CITY OF ENCINITAS ENC -41, 2.5" BRASS DISC, EAST SIDE H . 101, 0.5 MILE NORTH OF ELEVATION: 73.612' DATUM: NAW88 HORIZONTAL 1 " =i0' VERTICAL N/A �'�`�� PLANS PREPARED UNDER �.� BRIAN M. ARDOLINO THE SUPERVISION OF DATE: i® zai5 R.C.E. NO. 71651 EXP. 12 -31 -15 RECOMMENDED APPROV D BY: BY: MASIH MAHE LEN PRUIM pq 12/10/15 DATE: EROSION CONTROL PLAN FOR. 2111 E D I N B U R G AVENUE N U E A.P.N. #260- 412 -33 -00 12346 -G 6 �n.l A,k�aLl'� -t0 DATE �� �L�1'I°l SHEET 3 OF 6 PREPARED: 312712015 REVISED: 612512015 REVISED: 911512015 PLEA 2256 TEMPORARY SHORING GENERAL NOTES GENERAL 1. WHERE NO CONSTRUCTION DETAILS ARE SHOWN OR NOTED FOR ANY PART OF THE WORK. THE DETAILS USED SHALL BE THE SAME AS FOR OTHER SIMILAR WORK. PROVIDED THAT PRIOR APPROVAL IS OBTAINED FROM THE ENGINEER, 2. THE DESIGN IS BASED ON THE 2013 CALIFORNIA BUILDING CODE AND THE STATE OF CALIFORNIA TRENCHING & SHORING MANUAL, JANUARY 2011, PAGES 10 -1 TO 10 -42 CALTRANS SHORING DESIGN GUIDE IS USED AS A RESOURCE REFERENCE, MINIMUM SURCHARGE OF 100 PSF HAS BEEN USED IN THIS DESIGN TO ACCOUNT FOR NORMAL TRAFFIC LOADING. DRILL EQUIPMENT, CRANES, STOCKPILING, ETC SHALL BE SET BACK A MINIMUM OF "H" FEET (WHERE "H" EQUALS THE HEIGHT OF THE RETAINED EARTH) FROM THE BACK OF LAGGING. 3. TEMPORARY SHORING ARE CONSTRUCTED AS PART OF THE MEANS AND METHOD OF CONSTRUCTION FOR THE PROPOSED BUILDING AND NOT A PERMANENT STRUCTURAL ELEMENT OF THE BUILDING. IT IS GENERALLY UNDERSTOOD THAT THE BUILDING FOUNDATION AND STRUCTURAL SYSTEM, WHEN IN PLACE, ARE DESIGNED TO SUPPORT RETAINED EARTH AND SURCHARGE LOADS IN ADDITION TO ALL OTHER APPLICABLE BUILDING LOADS PRESCRIBED BY THE BUILDING CODE. 4. THE SOIL ENGINEER SHALL OBSERVE EXCAVATIONS, PILE PLACEMENT AND BACKFILLING SOILS CRITERIA REPORT BY: ENGINEERING DESIGN GROUP SAN MARCOS, CA REPORT NUMBER: JOB NO 155461 -1 REPORT DATE: APRIL 16, 2015 EQUIVALENT FLUID PRESSURES: ACTIVE PRESSURE: 35 PCF PASSIVE PRESSURE: 300 PCF MAX PRESSURE: N/A STRUCTURALSTEEL 1. STRUCTURAL STEEL SHALL COMPLY WITH ASTM A992 2. MATERIALS AND WORKMANSHIP SHALL COMPLY WITH AISC "SPECIFICATION FOR THE DESIGN, FABRICATION AND ERECTION OF STRUCTURAL STEEL FOR BUILDINGS." CONCRETE 1. CONCRETE WORK SHALL CONFORM TO THE "REQUIREMENTS FOR REINFORCED CONCRETE" (ACI 318) AND THE "SPECIFICATIONS FOR STRUCTURAL CONCRETE FOR BUILDINGS" (ACI 301), LATEST APPROVED EDITIONS WITH MODIFICATIONS AS NOTED IN THESE DRAWINGS AND SPECIFICATIONS. 2. CONTINUOUS INSPECTION BY A REGISTERED DEPUTY INSPECTOR IS REQUIRED FOR ALL CONCRETE WORK OF fc 3000 PSI OR GREATER (NOT REQUIRED FOR LEAN CONCRETE). 3. CONCRETE STRENGTHS: THE CONCRETE STRENGTHS SHOWN IN THE FOLLOWING TABLE ARE MINIMUM COMPRESSIVE STRENGTH AT 28 DAYS, THE AGGREGATES SHOWN ARE THE MAXIMUM SIZE (INCHES) AND THE SLUMP SHOWN IS THE MAXIMUM (INCHES). ITEM OF CONSTRUCTION STRENGTH AGGREGATE SLUMP A. CAISSON 2,500 PSI 3/8" 6- wmmki TIMBER 1. ALL LUMBER SHALL BE DOUGLAS FIR/LARCH (NORTH) OR HEM -FIR PRESSURE TREATED, AND SHALL BE GRADE MARKED #2 OR BETTER. CONSTRUCTION PROCEDURES 1. SOLDIER BEAM CONSTRUCTION: 1.1 LAY -OUT AND DRILL THE HOLE DIAMETER AND DEPTH AS INDICATED IN THE DRAWINGS. 1.2 PLACE THE SOLDIER BEAM APPROXIMATELY IN THE CENTER OF THE HOLE. 1.3 PLACE A MINIMUM OF 2,500 PSI CONCRETE FROM THE BOTTOM OF THE HOLE TO THE BOTTOM OF THE PROPOSED EXCAVATION. 1.3A °STIR N STUFF" METHODS MAY BE USED IN PLACE OF THE 2500 PSI CONCRETE TOE. RAW SACKS OF CEMENT (MIN. 3 SACK MIX) SHALL BE BLENDED WITH SOIL AND WATER WITHIN THE HOLE TO CREATE A CONCRETE SLURRY IN THE TOE SECTION. 1.4 PLACE LEAN CONCRETE (1 SACK MIX) FROM THE BOTTOM OF THE PROPOSED EXCAVATION TO EXISTING GRADE. 2. LAGGING PLACEMENT: 2.1 INSTALL LAGGING AND BACKFILL IN 5' MAXIMUM INCREMENTS. 2.2 PRIOR TO EXCAVATING THE NEXT INCREMENT OF CUT, THE LAGGING MUST BE COMPLETELY INSTALLED INSURING BEARING BETWEEN THE CUT SOIL & WOOD LAGGING, BY COMPACTING SAND, GRAVEL, COMPACTED SOIL, SLURRY OR GROUT BEHIND THE LAGGING AS PER INDUSTRY STANDARDS. 2.3 GAPS BETWEEN LAGGING SHALL NOT EXCEED 1" MAXIMUM. IF GAPS EXCEED 1" MAXIMUM, PACK GAPS WITH NON- SHRINK GROUT: 3. EXCAVATION MONITORING: 3.1 THE TOPS OF THE SOLDIER BEAMS SHOULD BE SURVEYED PRIOR TO EXCAVATION AND THAT THE TOPS OF THE SOLDIER BEAMS SHOULD BE SURVEYED ON A WEEKLY BASIS UNTIL THE PERMANENT RETAINING WALL (PER OTHERS) IS BACKFILLED TO THE DESIGN GRADE. THE SURVEYED SOLDIER BEAM DATA POINTS SHOULD BE LOCATED AT APPROXIMATELY 50 FEET ON- CENTER. INFORM SHORING ENGINEER IF ANY TIP DISPLACEMENT EXCEEDS 1/2 ". 12 PRIOR TO DRILLING ACTIVITY BEGINS, THE CONTRACTOR SHALL COMPLETE LOGS OF EXISTING IMPROVEMENTS THAT OCCUR WITHIN 100 OF THE SHORING SYSTEM AND A LICENSED SURVEYOR SHALL DOCUMENT ALL EXISTING CRACKS. 3.3 SURVEY MONUMENTS SHALL BE ESTABLISHED ON ADJACENT IMPROVEMENTS THAT EXIST WITHIN A HORIZONTAL DISTANCE (MEASURED FROM THE FACE OF LAGGING) EQUAL TO THAT OF THE RETAINED EARTH HEIGHT. THESE MONUMENTS SHALL BE MONITORED FOR BOTH VERTICAL AND HORIZONTAL MOVEMENT. SHORING ENGINEER SHALL BE NOTIFIED IF MOVEMENT EXCEEDING %" OCCURS. NDERGROUND SERVICE ALERT CALL: TOLL FREE 1 -800 422 -4133 ITWO WORKING DAYS BEFORE YOU DIG' SHEET INDEX SH -1 - TEMPORARY SHORING GENERAL NOTES AND DETAILS SH -2 - TEMPORARY SHORING PLAN AND SCHEDULE SH -3 - TEMPORARY SHORING ELEVATIONS — SOIL RETAINED of Lu \/ / w \// ® U> w d cnWi v LEAN CONCRETE PICA SH -1 SCALE; NITS 3x12 LAGGING PER ELEVATION SOLDIER BEAM PER SCHEDULE x r z z w J v F_ c: z LL z LL c LL ix 2 LL w J 0 2 SH -1 L) w d \\ \\ LEAN \' CONCRETE PER NOTES STRUCTURAL CONCRETE PER NOTES Lu \\ Lu \\ U U) w w d LAGGING PER PLAN & ELEVATION t EMBEDMENT ELEVATION PER SCHEDULE BOTTOM OF EXCAVATION SOLDIER BEAM PER SCHEDULE CAISSON PER SCHEDULE ft = PER NOTES) TYPICAL CANTILEVER SECTION SH -1 SCALE: NTS * 5NoRINb Disl &W REVIEWED hND APPROVED SY ESGIL CORPoaATIoO AS PC il IS -1843 L No. 4363 EXP.6130 /16 REVISIONS APPROVED DATE REFERENCES DATE BENCHMARK SCALE AS BUILT DESDVEO BY oDV ev cHHLEO ev APPROVALS CITY OF ENCINITAS ENGINEERING DEPARTIVIENT DRAWING- NO " CITY OF ENCINITAS ENC -41, 2.5" BRASS DISC, EAST SIDE PLANS PREPARED UNDER THE SUPERVISION OF RECOMMENDED APPROV HWY. 101, 0.5 MILE NORTH OF CHESTERFIELD. �j HORIZONTAL NOTED ir°l'it ° "" DATE:09 -10 -15 BY: �1•M BY: / (aIho DATE • NO. 9363 MASIH MAHER GLENN PRUIM 2111 EDINBURG AVENUE 12346 -G VERTICAL NOTED Uk 7KSt HAMID LIAGHATA EXP. 06 -30 -16 ELEVATION: 73.612' DATUM: NAVD68 op (.'SvlQi DATE: 12/10/15 DATE: �Z / .+i A.P.N. #260 - 412 -33 -00 SHEET 4 OF 6 SOLDIER BEAM PER SCHEDULE, TYP. -01, O.C. WOOD LAGGING =—X SLOPE BY OTHERS, TYP 1, I WOOD LAGGING PER DETAILS Sf —2 J SCALE: 1811 ° 1e On L No. 43 a= EXP, 6130116 +� SH-21 kovo) vvv--rvvv Fax. kozio) ovv--rvv1 REVISIONS APPROVED DATE REFERENCES DATE BENCHMARK SCALE AS BUILT DESDv APPROVALS CITY OF ENCINITAS ENGINEERING DEPARTMENT DRAWING NO. DV HL S• a,c CITY OF ENCINITAS ENC -41, 2.5" BRASS DISC, EAST SIDE HWY. 101, 0.5 MILE NORTH OF CHESTERFIELD. ELEVATION: 73.612' DATUM :NAVD88 HORIZONTAL NOTED VERTICAL NOTED i ��� -16 PLANS PREPARED UNDER THE SUPERVISION OF • DATE: 09-10-15 NO. 4363 HAMID LIAGHAT EXP.06 -30 -16 RECOMMENDED APPROV D BY: ,v►- �.e� -- aY: �� MASIH MAHER GLENN PRUI DATE: IA1101/-S DATE: / / /! //J 2111 EDINBURG AVENUE A.P.N. #260- 412 -33 -00 12346 -G AeM 'U001 �%swo DATE JAZ 111*16 VA, %L.ds1• 101 - SHEET 5 OF 6